Ошибки тепловых насосов HISEER: коды и расшифровка
Расшифровка кодов на дисплее тепловых насосов HISEER и что делать — по инструкциям производителя. Один и тот же код в разных сериях может означать разное: найдите свою серию.
Серии HISEER
HISEER AS07-10-20V: 17 кодов
Инструкция, стр. 56 →| Код | Что означает |
|---|---|
| AL37 | Switch off the unit |
| AL38 | Switch off the unit |
| AL71 | Unit's action to deal with the fault ST replaces RT as temperature control reference. control water temperature +5C on heating mode, -5C on cooling mode. If ST sensor faulted too, unit is switched off. Cooling mode is invalid |
| AL72 | Heating and DHW mode is valid,no high outlet water temperature protection and pump PWM = 100%. T(cooling)=ST01. T(heating)=ST02 |
| AL73 | Aux. electric backup heater, crankcase heater and anti-freezing function etc works without OT condition limitation. |
| AL74 | Hot water mode is invalid. Alarm code does not display if SF05=0. |
| AL75 | Switch off the unit |
| AL76 | Relative function is canceled. |
| B1 | Unit's action to deal with the fault ST replaces RT as temperature control reference. control water temperature +5C on heating mode, -5C on cooling mode. If ST sensor faulted too, unit is switched off. |
| B2 | Cooling mode is invalid |
| B3 | Heating and DHW mode is valid,no high outlet water temperature protection and pump PWM = 100%. T(cooling)=ST01. T(heating)=ST02 |
| B4 | Aux. electric backup heater, crankcase heater and anti-freezing function etc works without OT condition limitation. |
| B5 | Hot water mode is invalid. Alarm code does not display if SF05=0. |
| B6 | Switch off the unit |
| B7 | Switch off the unit |
| B8 | Switch off the unit Relative function is canceled. |
| B9 | Switch off the unit |
Источник: «Инверторные тепловые насосы воздух-вода Hiseer серии AS07-10-20V», стр. 56. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
HISEER AS10-13-20S/L: 9 кодов
Инструкция, стр. 56 →| Код | Что означает |
|---|---|
| B1 | Unit will continue to run until it reaches preset temperature. CM02 later, it will start again. |
| B2 | Switch off the unit |
| B3 | Unit will continue to run according to SF04=0 on heating mode. |
| B4 | Hot water mode is invalid. Alarm code displays if SF05=1. Alarm code does not display if SF05=0. |
| B5 | Switch off the unit |
| B6 | Cancel AL20 protection, increase ST01 2 degree Celsius more. |
| B7 | Switch off the unit |
| B11 | Switch off the unit |
| B12 | Switch off the unit |
Источник: «Тепловые насосы воздух-вода Hiseer серии AS10-13-20S/L», стр. 56. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
HISEER AS15V/LF: 17 кодов
Инструкция, стр. 60 →| Код | Что означает |
|---|---|
| AL37 | Switch off the unit |
| AL38 | Switch off the unit |
| AL71 | Unit's action to deal with the fault ST replaces RT as temperature control reference. control water temperature +5C on heating mode, -5C on cooling mode. If ST sensor faulted too, unit is switched off. Cooling mode is invalid |
| AL72 | Heating and DHW mode is valid,no high outlet water temperature protection and pump PWM = 100%. T(cooling)=ST01. T(heating)=ST02 |
| AL73 | Aux. electric backup heater, crankcase heater and anti-freezing function etc works without OT condition limitation. |
| AL74 | Hot water mode is invalid. Alarm code does not display if SF05=0. |
| AL75 | Switch off the unit |
| AL76 | Relative function is canceled. |
| B1 | Unit's action to deal with the fault ST replaces RT as temperature control reference. control water temperature +5C on heating mode, -5C on cooling mode. If ST sensor faulted too, unit is switched off. |
| B2 | Cooling mode is invalid |
| B3 | Heating and DHW mode is valid,no high outlet water temperature protection and pump PWM = 100%. T(cooling)=ST01. T(heating)=ST02 |
| B4 | Aux. electric backup heater, crankcase heater and anti-freezing function etc works without OT condition limitation. |
| B5 | Hot water mode is invalid. Alarm code does not display if SF05=0. |
| B6 | Switch off the unit |
| B7 | Switch off the unit |
| B8 | Switch off the unit Relative function is canceled. |
| B9 | Switch off the unit |
Источник: «Инверторные тепловые насосы воздух-вода Hiseer серии AS15V/LF», стр. 60. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
HISEER GS07-30, GS07-30B: 7 кодов
Инструкция, стр. 66 →| Код | Что означает |
|---|---|
| B1 | Unit will continue to run until it reaches preset temperature. CM02 later, it will start again. |
| B2 | Switch off the unit and display alarm code |
| B3 | Unit will continue to run according to SF04=0 on heating mode. |
| B4 | Hot water mode is invalid. Alarm code displays if SF05=1. Alarm code does not display if SF05=0. |
| B5 | Switch off the unit and display alarm code |
| B6 | Cancel AL20 protection, increase ST01 2 degree Celsius more. |
| B7 | Switch off the unit and display alarm code |
Источник: «Геотермальные тепловые насосы вода-вода Hiseer серии GS07-30, GS07-30B», стр. 66. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.