Инструкция на Тепловые насосы воздух-вода Hiseer серии AS10-13-20S/L
Тепловые насосы воздух-вода Hiseer серии AS10S/L, AS13S/L, AS20S/L. Руководство по эксплуатации, установке и техническому обслуживанию.
Смотрите также: Коды ошибок: 2 кода →
Загружаем документ…
Текст инструкции
-
AIR TO WATER HEAT PUMP
-
Working principle
Working principle RT Buffer tank OT SAK ET ② PT ① ST ⑤ FI AIV ③ EXP FI ④ ⑥ P1 FL HEAT PUMP 1. The low pressure and low temperature liquid refrigerant coming out of expansion valve exacts heat energy from the air through finned coil heat exchanger ① and evaporates into gas state. 2. The gas state…
-
Specialist Tools
Specialist Tools Specialist tools that might be used on installation, commissioning and maintenance. The tools as exclusive tools for R410A refrigerant. 1 Gauge manifold ·Only for R410A ·Use the existing fitting specifications.(G1/4”) ·Use high-tension side pressure of 5.3MPa·G or over. 2 Charge…
-
Pre-installation Pre-Installation
Movement and Storage The unit must not be transported, moved or stored at greater than a 30° angle from the upright position. Store the unit in a dry area until required. The unit must be installed by a suitably qualified tradesperson and all electrical wiring must be completed by a licensed…
-
Pre-Installation
Do not un-weld or flame cut the refrigerant lines including any refrigerant circuit components until the entire refrigerant (liquid and vapour) has been removed from unit. Traces of vapour should be displaced with dry nitrogen. Refrigerant in contact with an open flame will produces toxic gases.…
-
Installation Location
Installation Location The unit must be installed on a solid level surface on a concrete pad foundation not connected to the house foundation. Rubber cushions can be added to reduce vibration and noise if required. The unit should be place so that it is well away from bedrooms or noise sensitive…
-
Positioning
-
Buffer Tank
Buffer Tank A buffer tank is recommended to ensure a trouble free heat pump operation. A suitable buffer tank can avoid excessive heat pump cycling (switching on and off). The buffer tank provides a hydraulic separation from the volume flow in the heat pump and heating circuits. The volume flow in…
-
Frost Protection Frost Protection
The plate heat exchanger, the piping and the hydraulic pump can be damaged by frost, despite the built-in anti-freeze protection of the unit. In frost prone areas refer to installation location instructions. To avoid freezing-up of the water contained in the system, one of the precautions must be…
-
System Overview Heating Hot Water Production
RT Buffer tank OT SAK ET ② ① PT ST ⑤ FI AIV ③ EXP FI ④ ⑥ P1 FL HEAT PUMP Name Description Included Name Description Included P1 Circulation pump External RT Inlet water temperature sensor Internal AIV Air vent valve External ST Outlet water temperature sensor Internal FI Soft joint External OT…
-
Heating Mode Working Principle
On heating mode a. When SF04:enable compensation=NO, When the Inlet water temperature ≤ RTc-ST04 (RTc is the actual Inlet water temperature of the last stop) ,the compressor will start to heat. After outlet water temp. B2≥ST02, compressor will stop. The Compressor will start again when Inlet water…
-
System Overview Heating, Cooling with Hot Water Production
with Boiler back up Name Description Included Name Description Included P1 Circulation pump Internal (optional) RT Inlet water temperature sensor Internal VXV 3 way valve External ST Outlet water temperature sensor Internal VVB Hot water tank External OT Outdoor temperature sensor Internal FI Soft…
-
1. Heating Mode Working Principle
On heating mode, Three way valve (VXV) will open AB-A. 1.) When SF04 enable compensation=NO: a. When the inlet water temp. B1 ≤ RTc-ST04, (RTc is the actual measured inlet water temp. of last stop) the compressor will start to heat .After outlet water temp. B2≥ST02, compressor will stop. The…
-
System Overview Multiple Units in Series Cascade Connection
RT Buffer tank AIV SAK OT PT ST ET FI NRV EXP FI P1 FL HEAT PUMP 1 F2 SAK OT ET PT ST AIV FI NRV A HT AB B VXV EXP FI F2 P1 FL HEAT PUMP 2 FS VVB Name Description Included ? Name Description Included ? P1 Circulation pump Internal(Option) RT Inlet water temperature sensor Internal VXV 3 way Valve…
-
Multiple Units in Series Connection
(1) Heating working principle To set two or more units in parallel operation, set the primary unit to the required parameters, other units could have 2~5°C difference of ST01,ST02 and ST05 to allow for energy stage control. 1. When SF04:ENABLE COMPENSATION=NO: a). if there is a heating demand, then…
-
Installation
Installation 1. The pipe installation must adhere to the local Building Code, standards and any local council requirements. 2. Ensure that the water flow and returns are correct and not reversed. Reversing the water flow will reduce the output of the unit; refer to the labels on the unit for the…
-
Electrical connection
Electrical Connections Power Connection Before connecting the power supply, please confirm the unit suits the power supply. Breaker protection must be installed according to the max value stated in the nameplate attached to the unit inside of the front panel. The equipment must be installed via…
-
Outdoor Ambient Temperature Sensor
The outdoor temperature sensor (B3) is a standard component and is prewired and positioned in the unit. The probe is located at the back of the unit in a protective casing. The outdoor sensor is terminated on the PC board B3 and GND. Temperature sensor for hot water: The hot water sensor (B4) is…
-
The unit has two ways to turn ON/OFF heating functions
SF14: A/C On/Off way 1.) remote 2.) keyboard A/C Switch: SF14 set to “keyboard”(factory default setting). Then the A/C switch could not control the unit any more, wired remote control will take over control the unit . If SF14 set = “remote”. Keyboard can not be used to turn On/Off the heating and no…
-
The unit has two ways to turn ON/OFF domestic hot water functions
SF13: HW On/Off way 1.) remote 2.) keyboard Hot Water Switch: When SF13 set= “remote”, Keyboard can not be used to turn On/Off the DHW and no DHW timezone On/Off function. A1-A2 switch is activated to turn On/Off the hot water function. hot water switch A1-A2 is bridged, the unit’s hot water…
-
External Water Pump Connection (N02)
There is a connection port (1-2) at the terminal block for connecting circulation water pump.. If PWM pump is adopted, PWM signal is connected to D1-D2 Three Way Valve Connection (NO7 NC7) A 3 way valve could be connected to terminal (7-8-9) for domestic hot water production. 22
-
Auxiliary Heating Electric Heater or Boiler (NO4)
There is a connection port (10-11) which can be used to activate and de-activate an auxiliary electric heater or a boiler. The max current is 1 Amps therefore a contactor must be applied to control auxiliary electric heater or boiler. L1 L2 L3 N PE KM2 ELK Hot Water Electric Heater (NO8) There is a…
-
User interface
Find the user interface and connection cable from compressor room . Standard factory delivered connection cable is 10m. User interface should be installed indoor. It could be installed about 1.5m up from the floor ,out of reach of children. Connect the user interface with the control board via the…
-
Symbol explanation
Heating mode Cooling mode Domestic hot water mode Domestic hot water mode + Heating mode Domestic hot water mode + Cooling mode Water pump Compressor Fan Menu Tree Code CM CN EV SF Indication Compressor settings Condenser settings Evaporator settings Special functions Code ST UI AR DF 25 Indication…
-
Access Rights
Three groups of users with different privilege levels are described below. Privilege Level Main Activities Special Manufacturer Service User All Password required Configure and commission applications by setting/adjusting parameter values Password required Configure and commission…
-
Press
On/Off button, it display the unit current air conditioning (AC) and domestic hot water (HW) status. If the pre-set mode is heating, it display AC status(heat). Black cursor flashes on “OFF” on AC status(heat) , press button, it display Press button to enter. It displays: Press button, black cursor…
-
This menu display the unit measured temperature sensors value , digital switch on/off state, components on/off state. B1 RT AC inlet temp B2 ST AC outlet temp. B3 OT Ambient temp. B4 HT Hot water temp. B5 PT Discharge temp. B6 ET Suction temp. B11 LPS Suction pressure and temp. B12 HPS Discharge…
-
Change System mode
Button Operation: Prg User System mode System mode only could be changed on heating/cooling unit (SF01 unit type setting cooling + heating). When unit is off state, press “Prg” to main menu, button to enter , it display press up or down button to User, press Enter Press Enter button, Heating will…
-
User Parameters
-
Heating compensation curve setting
The control temperature for heating mode has two methods: fixed and changeable temperature. The fixed temperature is a fixed value and directly set by the user from the set area. The changeable temperature is determined by values of ST05, ST06 and the actual outdoor temperature measured by the OT…
-
With the drop of the outdoor temperature, the control temperature become higher and
higher to meet the large heating requirement. With the increase of the outdoor temperature, the control temperature become lower and lower, so that the heat pump works under low pressure to keep low energy consumption. Changing ST05 or ST06 could change the heating curve . Increase ST05 will lift up…
-
The calculated control water temperature will not be over ST14 Maximum heating
temperature and will not be lower than ST13 Minimum heating temperature Cold weather conditions When the room temperature is too low, You could increase ST06 . When the room temperature is too high, you could decrease ST06. Warm weather conditions If the room temperature is too low, You…
-
Three curves of different ST05 setting
-
If SF04: Enable compensation =Yes,
S10 menu is popped up : Press to change ST05 and ST06, OT is actual measured ambient temp. control temp. ST will be displayed. Press Actual to menu S11: You could input any OT value ,press and relative heating control temp. will be calculated. If OT=-15.0℃, actual control temp. is 49.0℃ If you have…
-
Timezone on/off
Timezone activates the pre-set timer programs. Timezone function is only valid when unit ON/OFF method is “by keyboard”. TR09:AC timerzone is for space heating When TR09 is set YES, two different time periods is available to set in every day from Sunday to Saturday. After finishing timer setting for…
-
Compressor Operating hours
Display compressor operating hours. Night mode Outdoor fan could be set to run in lower speed at night to reduce noise level . Default setting of night mode is activated from 22:00 to 6:00. The night mode time could be adjusted by the user. Insert User default This function is to store user setting…
-
Access Service Level Parameter data
Display Procedures press <Prg> to main menu, press Down button to Parameter, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are inputted, It will enter Service level…
-
Service Parameters
Service Parameters: Para- Descriptions meter De- Min. Max. Unit Res fault EV01 Water pump control mode Continuous work EV03 Water pump set temp. difference on cooling ℃ 0.1 EV04 Water pump set temp. difference on heating ℃ 0.1 SF01 Unit type SF05 Enable domestic hot water function SF13 Continuous…
-
Cooling demand
-
Control process
Turn on process at heating mode 1.) Start water pump , check water flow switch 2.) 5 seconds after water flow switch closes, if there is heating demand, start fan and compressor Turn off process at heating mode 1.) Switch off compressor 2.) After 5 second’s delay, switch off fan motor 3.) After 30…
-
Auxiliary Electric heater or boiler control (NO4)
Auxiliary heater or boiler only could be switched on when all of conditions below are met. 1.) Heating mode running; 2.) Compressor has run over 300s 3.) OT≤ST07; 4.) ST ≤ST02-ST04-1; Auxiliary heater or boiler only could be switched off when any of conditions below is met. 1.) A/C flow switch cut…
-
The EC fan running control (Y1)
-
The pump PWM running control (Y3)
On cooling mode, when compressor is on, pump PWM runs as EV05 for 3 minutes, then runs with (Inlet temperature-Outlet temperature)=EV03 as target via PID control . when compressor is off, pump PWM runs as EV06. On heating mode, when compressor is on, pump PWM runs as EV05 for 3 minutes, then runs…
-
Manufacturer parameters
Access Manufacturer Level Parameter data Display Procedures press <Prg> to main menu, press Down button to Parameter, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are…
-
Manufacturer parameters
Para meter Descriptions Default Min. Max. Unit Res CM01 Compressor minimum ON time Sec. 1 CM02 Compressor minimum OFF time 300 90 1000 Sec. 1 CN01 EC fan Max. speed (cooling) V 0.1 CN02 EC fan Max. speed (heating) V 0.1 CN03 EC fan Min.. speed V 0.1 CN04 EC fan Max speed (night mode) V 0.1 CN05 EC…
-
Commissioning
and Adjusting Commissioning and Adjusting Preparations- Filling and Flushing 1. Before commissioning, ensure the whole system has been properly flushed and filled with water. 2. Check the pipe work system for leaks. 3. The heating system is filled with water and inhibitor to the required pressure…
-
Commissioning and Adjusting
Air in the System after Startup Air will initially be released from the water as its heated and further venting may be required. If a bubbling sound can be heard from the heat pump, the circulation pump, underfloor and or radiators then the entire system will require further venting. When the…
-
Commissioning Form
Commissioning Form Commissioning Form Client / Installation address: Telephone Number Installer: Commissioned by Heat pump Model: Heat pump serial number: Commissioning date: The heating system has been filled and pressure tested YES ( ) Expansion vessel for heating is sized, fitted & charged in…
-
The alarms are divided into two groups: auto reset alarms and manual reset alarms
1. Auto reset alarm, the user is not required to acknowledge and reset it. 2. The corresponding device will be automatically restarted once the alarm status disappears. 3. Once a manual reset alarm is detected, the system will be stopped automatically. The user needs to record and contact the…
-
Auto Reset Alarms
The following are codes for auto reset alarms with their meanings. Codes Meaning AL03 Low outlet water temperature (ST<AR01) AL05 High outlet water temperature (ST>AR03) AL17 Water flow switch AL26 Antifreeze AL35 Low suction pressure ,lower than 1.5bar AL36 High discharge pressure ,higher than…
-
Viewing Alarm history
Display Procedures Press <Prg> button , then then press down button to Alarm History, press <Enter> to confirm. Press <up> or <down> to view other alarms If no alarm is generated, the word “No alarm!” will be displayed. Acknowledging and Resetting Manual Reset Alarms Any alarm detected by the…
-
Low outlet water temperature protection
(Code: AL03) At any mode, if ST≤AR01, the compressor is off ,after 5 seconds delay, the fan motor will be stopped, PWM water pump will run as EV05, other parts will keep its original state. A continuous blink warning code AL03 will appear on the LCD, it will record the instant inlet water…
-
High pressure protection
(Code: AL36) It does not scan high pressure on defrosting period and within 10 seconds after defrosting stop. At other time if B12(HPS)≥AR15 , the compressor is off ,after 5 seconds delay, the fan motor will be stopped, PWM water pump will run as EV06, other parts will keep its original state. A…
-
Temperature Sensor trouble (auto reset)
If the temperature sensor is below -35C or higher 150C in 4.5 seconds, it will display sensor trouble. sensor B1 code AL71 B2 B3 AL72 AL73 B4 AL74 B5 B6 B7 B11 B12 AL75 AL76 AL77 AL37 AL38 Program trouble dealing action Unit will continue to run until it reaches preset temperature. later, it will…
-
To ensure the optimal performance of the unit regular maintenance is essential
Failure to undertake regular maintenance can reduce the unit performance and of the system shorten the life of the unit . Exterior Maintenance 1. Make regular checks throughout the year that the inlet grill is not blocked or clogged by leaves, snow or anything else. 2. Ensure during the colder times…
-
If there is not enough refrigerant in the system, this is indicated by gas bubbles in the
moisture sight glass .the unit will have poor performance. If the low refrigerant charge is significant, large bubbles appear in the moisture sight glass and the suction pressure drops, then the compressor suction superheat will also be high. Find the leak and completely drain the system with a…
-
Mechanical Maintenance
1. Check the tension of the fan motor, fan wheel, compressor and control box fixing bolts. 2. Check that no water has penetrated into the control box. Evaporator Coil It is recommended that the finned coils are inspected regularly to check the degree of fouling. This depends on the environment where…
-
Dimensions
-
Water PressureWater
-
Water Pressure Plots
-
таблицы и схемы — в просмотре
-
Temperature and sensor resistance table
Temperature and sensor resistance table 63
-
таблицы и схемы — в просмотре
-
Components
Components AS10S/L AS13S/L 15 14 1. 2. 3. 4. 5. 6. 7. 8. 9. Finned coil heat exchanger EC Fan motor Fan blade De-icing heater(option package 1) Liquid receiver Plate heat exchanger Filter Compressor Differential pressure flow switch(option package 1) 10. Phase relay 11. Circuit breaker 12. Terminal…
-
Technical Specifications
Technical Specifications AIR TO WATER HEAT PUMP AS10S/L Heat output/Power consumption/COP at 7/35℃ kW Heat output/Power consumption/COP at 7/45℃* Heat output/Power consumption/COP at 7/55℃* AS13S/L 10.7/2.48 COP 4.31 kW 11.0/3.28 kW 11.15/3.85 Heat output/Power consumption/COP at 2/35℃ kW Heat…