Инструкции на Инверторные тепловые насосы воздух-вода Hiseer серии AS15V/LF
Инверторные тепловые насосы воздух-вода Hiseer серии AS15V/LF. Руководство по эксплуатации, установке и техническому обслуживанию.
Смотрите также: Коды ошибок: 9 кодов →
Загружаем документ…
Текст инструкции
-
AIR TO WATER HEAT PUMP
Inverter Split series AS15V/LF Operation, installation &maintenance manual V.201704 The installation of this unit is to adhere to all local Building Codes and Standards 0
-
Nomenclature
-
Working principle
② ① ⑤ ④ Outdoor unit ⑥ ③ Indoor unit 1. The low pressure and low temperature liquid refrigerant coming out of expansion valve exacts heat energy from the air through finned coil heat exchanger ① and evaporates into gas state. 2. The gas state refrigerant is sucked into compressor ② and compressed to…
-
Specialist Tools
Specialist Tools Specialist tools that might be used on installation, commissioning and maintenance. The tools as exclusive tools for R410A refrigerant. 1 Gauge manifold ·Only for R410A ·Use the existing fitting specifications.(G1/4”) ·Use high-tension side pressure of 5.3MPa·G or over. 2 Charge…
-
Pre-installation
Pre-Installation Movement and Storage The unit must not be transported, moved or stored at greater than a 30° angle from the upright position. Store the unit in a dry area until required. The unit must be installed by a suitably qualified tradesperson and all electrical wiring must be completed by a…
-
Pre-Installation
Do not un-weld or flame cut the refrigerant lines including any refrigerant circuit components until the entire refrigerant (liquid and vapour) has been removed from unit. Traces of vapour should be displaced with dry nitrogen. Refrigerant in contact with an open flame will produces toxic gases.…
-
Installation Location
Installation Location The unit must be installed on a solid level surface on a concrete pad foundation not connected to the house foundation. Rubber cushions can be added to reduce vibration and noise if required. The unit should be place so that it is well away from bedrooms or noise sensitive…
-
Positioning
-
Frost Protection
Frost Protection The plate heat exchanger, the piping and the hydraulic pump can be damaged by frost, despite the built-in anti-freeze protection of the unit. In frost prone areas refer to installation location instructions. To avoid freezing-up of the water contained in the system, one of the…
-
System Overview 1: Floor heating
② ⑤ ① ④ ⑥ ③ Outdoor unit Indoor unit Name Description Included Name Description Included P1 Circulation pump Internal RT Inlet water temperature sensor Internal AIV Air vent valve External ST Outlet water temperature sensor Internal FI Soft joint External OT Ambient temperature sensor Internal SAK…
-
System Overview 1: Floor heating
Heating Mode Working Principle: On heating mode Unit On : when RT<T(heating)-ST04(T(heating) is the control water temperature on heating mode) Unit Off: RT>T(heating) + 2℃ and running frequency of the compressor has reduced to Minimum and lasts for 120s. T(heating) calculation: Default…
-
System Overview 2: Heating ,Cooling with DHW Production with Boiler
back up Name Description Included Name Description Included P1 Circulation pump Internal RT Inlet water temperature sensor Internal VXV 3 way valve External ST Outlet water temperature sensor Internal VVB Hot water tank OT Ambient temperature sensor Internal FI Soft joint HT Domestic hot water…
-
System Overview 2: Heating ,Cooling with DHW Production with
Boiler back up 1. Heating Mode Working Principle: On heating mode, Three way valve (VXV) will open AB-A. Unit On : when RT<T(heating)-ST04(T(heating) is the control water temperature on heating mode) Unit Off: RT>T(heating) + 2℃ and running frequency of the compressor has reduced to Minimum and…
-
Installation
Installation 1. The pipe installation must adhere to the local Building Code, standards and any local council requirements. 2. Ensure that the water flow and returns are correct and not reversed. Reversing the water flow will reduce the output of the unit; refer to the labels on the unit for the…
-
Pipe connections
Connecting refrigerant pipe (not supplied) Install the refrigerant pipes between the outdoor unit and indoor unit. Installation must be carried out in accordance with current norms and directives. If indoor unit is higher than outdoor unit more than 5m, an oil return curve must be made in each…
-
Pipe connections
Pressure test and leak test If the system has remaining moisture or a leak, the vacuum pressure will rise after completed evacuation. Filling refrigerant: After finishing pipe connections, pressure test ,leak test and vacuuming, the service valves can be opened. The gas inside the indoor unit is…
-
Electrical connection
Electrical Connections Power Connection Before connecting the power supply, please confirm the unit suits the power supply. Breaker protection must be installed according to the max value stated in the nameplate attached to the unit inside of the front panel. The equipment must be installed via…
-
Connecting indoor and outdoor unit
Use cable (not supplied) to connect indoor and outdoor unit via control board terminal connection . L N Outdoor unit Indoor unit Note: Outdoor unit must be earthed before the wiring before the unit is connected. The wiring must be attached so that the terminal block is not under stress Connect…
-
DHW circulation Pump Connection (N01)
If water in the domestic hot water pipe needs to be re-heated , a DHW circulation pump could be installed in the domestic hot water pipe that is connected to domestic hot water tank heated by the heat pump. The DHW circulation pump power supply should be connected to port (1-2) at the terminal…
-
There are two ways to turn ON/OFF heating functions
SF14: A/C On/Off way 1.) remote 2.) keyboard A/C Switch: SF14 set to “keyboard”(factory default setting). Then the A/C switch could not control the unit any more, user interface will take over control the unit . If SF14 set = “remote”. Keyboard can not be used to turn On/Off the heating and no…
-
There are two ways to turn ON/OFF domestic hot water functions
SF13: HW On/Off way 1.) remote 2.) keyboard Hot Water Switch: When SF13 set= “remote”, Keyboard can not be used to turn On/Off the DHW and no DHW timezone On/Off function. A1-A2 switch is activated to turn On/Off the hot water function. hot water switch A1-A2 is bridged via a cable, the unit’s hot…
-
Auxiliary Electric Heater or Boiler backup and DHW heater
There is a connection port (6-7) and (8-9)which can be used to activate and de-activate an auxiliary electric heater or a boiler JQ1 for heating backup and domestic hot water heater JQ2. The max current is 1 Amps therefore a contactor must be applied to control auxiliary electric heater or boiler.…
-
SG READY -Smart Grid
1.) D1-D2 (DI7) and D3-D4 (DI6) is connected to SG1 SG2 on the electric meter SG signal . 2.) TR12 parameter in Service menu are used to turn on / off unit SG function. When TR12 is disable, SG function is invalid. When TR12 is enable, SG function is valid. "SG mode" display on user interface. SG1…
-
User interface
Find the user interface and connection cable from compressor room . Standard factory delivered connection cable is 10m. User interface should be installed indoor. It could be installed about 1.5m up from the floor ,out of reach of children. Connect the user interface with the control board via the…
-
Symbol explanation
Heating mode Cooling mode Domestic hot water mode Domestic hot water mode + Heating mode Domestic hot water mode + Cooling mode Water pump Compressor Fan Menu Tree Code CM CN EV SF Indication Compressor settings Condenser settings Evaporator settings Special functions Code ST UI AR DF 25 Indication…
-
Access Rights
Three groups of users with different privilege levels are described below. Privilege Level Main Activities Special All Password required Configure and commission applications by setting/adjusting parameter values Password required Configure and commission applications by setting/adjusting…
-
If the pre-set mode is heating, it display AC status(heat)
Black cursor flashes on “OFF” on AC status(heat) , press button, it display Press button to enter. It displays: Press button, black cursor flashes on “OFF” on HW status , press press button to enter, it will display button, it display Unit A/C and DHW are successfully switched on. “Starting “…
-
This menu display the unit measured temperature sensors value , digital switch on/off state, components on/off state. B1 B2 B3 B4 B5 B6 B7 B8 B9 DI4 DI5 DI6 DI7 NO1 NO2 NO3 NO4 NO5 NO6 NO7 N08 N09 Y1 Y3 RT ST OT HT PT LPS HPS ET PWM AC inlet temp AC outlet temp. Ambient temp. Hot water temp.…
-
Changing Set points (for user)
Display Procedures press <Prg> to main menu, press Down button to User, Press Enter button, Press Down button to the desired parameter. Press Enter button, when cursor is flashing by 13.0℃, press Up or Down button to change the value. Press Enter to confirm. Cursor will move to next parameter data…
-
Heating compensation curve setting
The control temperature for heating mode has two methods: fixed and changeable temperature. The fixed temperature is a fixed value and directly set by the user from the set area. The changeable temperature is determined by values of ST02, ST06 and the actual outdoor temperature measured by the OT…
-
Changing ST02 or ST06 could change the heating curve
Increase ST02 will lift up the curve Increase ST06 will increase the grade of the curve The calculated control water temperature will not be over ST14,will not be lower than ST13. Cold weather conditions ●When the room temperature is too low, You could increase ST06 . ●When the room temperature is…
-
Heating curve setup Press to change ST06, OT is actual measured ambient temp. Actual control temp. RT will be displayed. Press to menu : You could input any OT value ,press and relative heating control temp. will be calculated. If OT=-1.0℃, actual control temp. is 47.6℃ If you have your own curve…
-
The calculated control water temperature will be be limited by ST11. 33
-
Timezone on/off
Timezone activates the pre-set timer programs. Timezone function is only valid when unit Disable/Enable method is “by keyboard”. TR09:AC timerzone is for space heating When TR09 is set Enable, two different time periods is available to set in every day from Sunday to Saturday. After finishing timer…
-
Compressor Operating hours
Display compressor operating hours. Insert User default This function is to restore user setting to factory default setting . Change “NO” to “YES”, press <Enter> , it will display “Operation succeed” . Important safety information for end users Installation and service works of the heat pump should…
-
Steps to open the cabinets
The panels must be removed as the order : front panel – left panel – right panel – back panel 1. Unscrew the two screws at the bottom of front panel as below indication and then Front panel could be removed by pressing the panel downward. 2. Unscrews the screws as below indication to remove left…
-
3. The right panel could be removed as the same way of removing the left panel
4. Unscrew the screws as below and then back panel could be removed. 37
-
Access Service Level Parameter data
Display Procedures press <Prg> to main menu, press Down button to Parameter, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are inputted, It will enter Service level…
-
Service Parameters
Service Parameters: Para- Descriptions meter informati on EV03 EV04 De- Min. Max. Unit Res ℃ 0.1 ℃ 0.1 fault Software version Inlet/outlet water temperature difference setting on cooling mode Inlet/outlet water temperature difference setting on heating mode SF01 Unit type SF05 Enable domestic hot…
-
Cooling demand
-
Control process
Turn on process on heating mode 1.) Start water pump , check water flow 2.) if water flow meet requirement and there is heating demand, start fan and compressor Turn off process on heating mode 1.) Switch off compressor 2.) After 5 second’s delay, switch off fan motor 3.) After 30 seconds’ delay…
-
During defrosting period and 3 minutes after the end of defrosting , circulation pump PWM signal output is 100%. After circulation pump stops running over 24 hours ,circulation pump is switched on and runs 3 minutes .The PWM signal output is 60% . This is to prevent the pump from seizing. If…
-
7.) Reduce running frequency to protect the compressor
A.) pressure protection When system pressure is higher than 36Bar in continual 5 seconds, compressor running frequency reduces 10Hz , 10 seconds later: a.) if system pressure is still higher than 36Bar in continual 5 seconds, compressor running frequency reduces 10Hz more and so on until the system…
-
Auxiliary Electric backup heater or boiler control
Auxiliary backup heater or boiler only could be switched on when all of conditions below are met. 1.) Heating mode running and compressor has been running with the maximum workable frequency.; 2.) Compressor has run over 300s 3.) OT≤ST07; 4.) RT ≤T(heating)-ST04-2; Auxiliary backup heater or boiler…
-
The EC fan running control
-
The pump PWM running control (Y3)
1.) On cooling mode, when compressor is on, pump PWM runs as EV05 for 3 minutes, then runs with (Inlet temperature-Outlet temperature)=EV03 as target via PID control . when compressor is off, pump PWM runs as EV06. 2.) On heating mode, when compressor on, pump PWM runs as EV05 for 3 minutes, then…
-
Optimization solution two ( if the last defrosting is activated by condition two mentioned above)
1.) if previous defrosting time is less than 3 minutes and defrosting is terminated by above condition A or B. It means that there is little frost on the evaporator when unit starts defrosting. Then on the next time defrosting, DF16 will add 10 minutes. After this optimization, next time defrosting…
-
Access manufacturer Parameter
Display Procedures press <Prg> to main menu, press Down button to Manufacture, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are inputted, It will enter Manufacturer.…
-
Para-
De- Descriptions meter fault Min. Max. Unit Res CM02 Compressor minimum OFF time 180 1 1000 Sec. 1 CM11 Rated cooling speed 80 CM13 CM12 HZ 1 CM12 Max cooling speed HZ 1 CM13 Min cooling speed HZ 1 CM14 Rated heating speed 80 CM16 CM15 HZ 1 CM15 Max heating speed HZ 1 CM16 Min heating speed HZ 1…
-
SF34
EEV defrost steps step 1 Kp EEV PID 5.5 Ti EEV PID 120 Td EEV PID 1 AR01 Low outlet water temperature protection ℃ 0.1 AR03 High outlet water temperature protection ℃ 0.1 AR06 Low pressure alarm times in 24 hours - 1 AR07 High pressure alarm times in 24 hours - 1 AR08 low evaporation temperature…
-
Reset compressor Operating hours
This function is to restore compressor operating time to 0 . Change “NO” to “YES”, press <Enter> . Insert manufacturer default This function is to restore manufacturer setting to factory default setting . Change “NO” to “YES”, press <Enter> , it will display “Operation succeed” Initialization…
-
Commissioning
and Adjusting Commissioning and Adjusting Preparations- Filling and Flushing 1. Before commissioning, ensure the whole system has been properly flushed and filled with water. 2. Check the pipe work system for leaks. 3. The heating system is filled with water and inhibitor to the required pressure…
-
Commissioning and Adjusting
Air in the System after Start-up Air will initially be released from the water as its heated and further venting may be required. If a bubbling sound can be heard from the heat pump, the circulation pump, under-floor and or radiators then the entire system will require further venting. When…
-
Commissioning Form
Commissioning Form Commissioning Form Client / Installation address: Telephone Number Installer: Commissioned by Heat pump Model: Heat pump serial number: Commissioning date: The heating system has been filled and pressure tested YES ( ) Expansion vessel for heating is sized, fitted & charged in…
-
The alarms
Alarms are divided into two groups: auto reset alarms and manual reset alarms. 1. Auto reset alarm, the user is not required to acknowledge and reset it. 2. The corresponding device will be automatically restarted once the alarm status disappears. 3. Once a manual reset alarm is detected, the system…
-
Auto Reset Alarms
The following are codes for auto reset alarms with their meanings. Codes Meaning AL01 Low pressure AL02 High pressure AL03 Low outlet water temperature (ST<AR01) AL05 High outlet water temperature (ST>AR03) AL17 Water flow is short WN01 Antifreeze AL20 Low evaporation temperature (only cooling mode)…
-
Viewing Alarm history
Display Procedures Press <Prg> button , then then press down button to Alarm Logs, press <Enter> to confirm. Press <up> or <down> to view other alarms If no alarm is generated, the word “No alarm!” will be displayed. Acknowledging and Resetting Manual Reset Alarms Any alarm detected by the system…
-
1.) Low pressure protection
(Code: AL01) After starting the compressor, it check the low pressure after AR09 delay. If LPS≤AR31 in continual 120 seconds, then compressor is switched off, 5 seconds later, fan motor is switched off, other parts keep their original state. Alarm code AL01 display on the user interface. After…
-
9.) Low evaporation temperature protection (serious) (Code: AL31)
In 24 hours time, if AL20 is trigger over AR16 times, manual reset alarm AL31 is triggered, the compressor is switched off, 5 seconds later, fan motor is switched off, other parts keep their original state. Alarm code AL31 displays on the user interface. 10.) Low outlet water temperature protection…
-
Maintenance
Maintenance To ensure the optimal performance of the unit regular maintenance is essential. Failure to undertake regular maintenance can reduce the unit performance and of the system shorten the life of the unit . Exterior Maintenance 1. Make regular checks throughout the year that the inlet grill…
-
Maintenance
Verify the Alarm Status 1. Check the alarm menu when the unit is in the standby mode to see if any alarms or warning have occurred. Electrical Maintenance 1. Check for correct termination tension of the electrical connections, contactors, isolation switch and transformer. 2. Check the condition of…
-
Dimensions
Dimensions Outdoor unit Indoor unit 62
-
Water Pressure PlotsWater Pressure Plots
-
Pump Curve
Internal circulation pump curve 64
-
Temperature and sensor resistance table
-
таблицы и схемы — в просмотре
-
2. 3. 4. 5. 6. Fan blade EC Fan motor EC fan motor board Grill De-icing heater Finned coil heat exchanger 7. EMC filter 8. Transformer 9. A/C contactor 10. Modbus communication adaption board 11. Inverter board 71
-
12. Terminal block
13. Circulation pump flow feedback 14. Controller 15. Aux. backup electric heater 16. Circulation pump 17. Harmonic filter 18. Accumulator 19. Drain valve 20. LP transducer 21. 4 way valve 22. HP transducer 23. LP service connection 24. HP service connection 25. Compressor
-
26. Solenoid valve 27. EEV 28. Separator 29. EVI expansion valve 30. Plate heat exchanger 31. Economizer 32. Adjustable feet
-
Technical Specifications
Model Number AS15V/LF Heating performance Min. Nominal Max. Heat output/Power consumption/COP at A7/W35℃ kW 4.63/1.04/4.45 15.73/3.64/4.32 18.1/4.62/3.90 Heat output/Power consumption/COP at A2/W35℃ kW 3.93/1.09/3.60 12.86/3.52/3.65 16.04/4.62/3.47 Heat output/Power consumption/COP at A-7/W35℃ kW…
-
F-gas Information
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.