GEOTHERMAL HEAT PUMP
-
Working principle
② ① ③ ④ 1. The low pressure and low temperature liquid refrigerant coming out of expansion valve ④ exacts heat energy from the ground which is drawn by circulation water pump P2 in vertical ground loop and evaporates into gas state in plate type heat exchanger evaporator ① . 2. The gas state…
-
Specialist Tools
Specialist Tools Specialist tools that might be used on installation, commissioning and maintenance. The tools as exclusive tools for R410A refrigerant. 1 Gauge manifold ·Only for R410A ·Use the existing fitting specifications.(G1/4”) ·Use high-tension side pressure of 5.3MPa·G or over. 2 Charge…
-
Pre-Installation
Pre-Installation Important Site Instructions The installation, commissioning, inspection, maintenance and repairs must only be carried out by a qualified person. All electrical wiring must be completed by a licensed electrical contractor in accordance with the appropriate standards. The…
-
Pre-Installation
Note: ensure the correct refrigerant gas is used to recharge the unit as an incorrect gas can cause damage beyond repair to the compressor. Do not use oxygen to purge lines or to pressurize a unit for any purpose. Oxygen gas reacts violently with oil, grease and other common substances. Use only…
-
Installation Location and Positioning
Installation Location and Positioning The unit must be installed in a protected area that is free from rain and water penetration. The unit must be installed on a solid level surface, preferably on a concrete pad not connected to the main house slab foundation. Allowances for good ventilation…
-
Buffer Tank
Buffer Tank A buffer tank is recommended to ensure a trouble free heat pump operation. A suitable buffer tank can avoid excessive heat pump cycling (switching on and off). The buffer tank provides a hydraulic separation from the volume flow in the heat pump and heating circuits. The volume flow in…
-
System Overview 1: Vertical Ground Loop System
Name Description Location Name Description Location P2 Outdoor side water pump External OT Outdoor temperature sensor Internal SAK Safety valve External FL Particle filter External BK Brine tank/expansion tank External 9
-
System Overview 2: Horizontal Ground Loop System
Name Description Location Name Description Location P2 Outdoor side water pump External OT Outdoor temperature sensor Internal SAK Safety valve External FL Particle filter External BK Brine tank/expansion tank External 10
-
System Overview 3: Ground Water with Intermediate Heat
Exchanger System Name Description Location Name Description Location P2 Outdoor side water pump External OT Outdoor temperature sensor Internal P3 Ground water pump External FL Particle filter External BK Brine tank/expansion tank External SAK Safety valve External FW Water flow switch External FI…
-
System Overview 1: Floor Heating Only
Name Description Location Name P1 Indoor side water pump External RT EXP Expansion tank External ST AIV Air vent valve External STo SAK Safety valve External ET Suction temp. Internal FS Automatic water supplement valve External Description Location Indoor side inlet water temperature sensor Indoor…
-
System Overview 1: Floor Heating Only
1. Heating Mode Working Principle: a. When SF04:enable compensation=NO, When the Inlet water temperature ≤ RTc-ST04 (RTc is the actual Inlet water temperature of the last stop) ,the compressor will start to heat. After outlet water temp. B2≥ST02, compressor will stop. The Compressor will start again…
-
System Overview 2: Heating ,Cooling& Hot Water
(External water pump, three way valve and electric heater) Name Description Location Name P1 Indoor side water pump External RT ELK Electric heater/boiler External ST EXP Expansion tank External STo VXV Three way valve External HT Hot water temperature sensor Internal FS Automatic water supplement…
-
System Overview Heating Cooling & Hot Water
(External water pump, three way valve and electric heater) 1. Heating Mode Working Principle: On heating mode, Three way valve (VXV) will open AB-A. 1.) When SF04 enable compensation=NO: a. When the Inlet water temperature ≤ RTc-ST04 (RTc is the actual Inlet water temperature of the last stop) ,the…
-
System Overview 3: Floor Heating with Hot Water
(Internal water pump, electric heater and three way valve) Name Description Location Name Description Location P1 Indoor side water pump Internal(Option) RT Indoor side inlet water temperature sensor Internal EXP Expansion tank External ST Indoor side outlet water temperature sensor Internal VXV…
-
System Overview 3: Floor Heating with Hot Water
(Internal water pump ,electric heater and three way valve) 1. Heating Mode Working Principle: On heating mode, Three way valve (VXV) will open AB-A. 1.) When SF04 enable compensation=NO: a. When the RT ≤ RTc-ST04, (RTc is the actual RT value of unit’s last stop) the compressor will start to heat…
-
System Overview 4: Multiple Units in Series Cascade
Connection Name Description Location Name P1 Indoor side water pump Internal (option) RT EXP Expansion tank External ST SAK Safety valve External HT Hot water temperature sensor Internal FS Automatic water supplement valve External STo Outdoor side outlet water temperature sensor Internal CV…
-
System Overview 4: Multiple Units in Series
Cascade Connection (1) Heating working principle To set two or more units in parallel operation, set the primary unit to the required parameters, other units could have 2~5°C difference of ST01,ST02 and ST05 to allow for energy stage control. 1. When SF04:ENABLE COMPENSATION=NO: a). if the RT (inlet…
-
Installation
Installation Installation must be carried out in accordance with current Standards and Building Codes.The heat pump does not come fitted with shutoff valves and these must be fitted outside of the heat pump to facilitate future service. Important The pipe work must be flushed before the heat pump is…
-
Installation
9. Where there is more than one ground loop these must be connected in parallel with a means of adjusting the flow. For surface soil heat, the pipe should be buried at a depth of about 1.8 meters and the distance between the hoses should be at least 1 meter. 10. For bore holes the distance between…
-
Warning
Electrical connections and servicing must be carried out under the supervision of a qualified electrician.Electrical installation and wiring must be carried out in accordance with Local Standards. Power Connection: Before connecting the power supply please confirm the unit suits the power supply as…
-
Mains Connection Diagram
Triple phase: 380-415V/3/50Hz Single phase: Phase relay: There is a phase relay for three phase units. If there is phase relay alarm AL23 ,check the indication lights on the device. “Normal” green light on means that phase connection is correct “Phase reverse” red light on means that phase…
-
Outdoor Ambient Temperature Sensor
The outdoor temperature sensor (OT) is a standard part placed inside the electric box. One terminal is connected with the PC board B3 and GND, its probe must be installed outdoors. It should be mounted on a wall that has the mean outdoor temperature which can accurately measure the outdoor…
-
Indoor Side Inlet Water Temperature Sensor
The indoor side inlet water sensor (RT) from factory is placed in the submerged tube of pipe near the plate heat exchanger. If a buffer tank is installed, the RT sensor can be moved to the buffer tank temperature sensor inlet pocket and EV01 parameter value can be set to “work by regulation”. This…
-
Outdoor Side Water Pump
Outdoor side water pump is connected to terminal port (1-2). Indoor Side Water Pump: Indoor side water pump is connected to terminal port (3-4). 3 4 If a PWM pump is used, PWM is connected to D1-D2 26
-
Three Way Valve
If the unit has no a 3 way valve fitted in factory, an external 3 way valve could be connected to terminal (7-8-9) for domestic hot water production. Outdoor flow Indoor flow switch switch Water flow switch The indoor side and outdoor side water flow switch is connected across C1-C2 and C3-C4. It is…
-
The unit has two ways to turn ON/OFF heating functions
SF14: A/C On/Off way 1.) remote 2.) keyboard A/C Switch: If SF14 set = “remote”. Keyboard can not be used to turn On/Off the heating and no heating timezone On/Off function. B1-B2 switch is activated to turn On/Off the unit. When the A/C switch B1-B2 is bridged, the unit’s heating function is…
-
The unit has two ways to turn ON/OFF domestic hot water functions
SF13: HW On/Off way 1.) remote 2.) keyboard Hot Water Switch: When SF13 set= “remote”, Keyboard can not be used to turn On/Off the DHW and no DHW timezone On/Off function. A1-A2 switch is activated to turn On/Off the hot water function. hot water switch A1-A2 is bridged, the unit’s hot water…
-
Controller Display (Display window & button area)
Operating buttons Button Name Operation <Alarm> It will flash to indicate when any alarm happens. Press it to re-set manual re-set alarms after the fault is removed. <Program> Press it to enter main menu <Esc> In Menu /parameter setting mode, press it to return to the previous menu level. <Enter> In…
-
Menu Tree
Code CM CN EV SF Indication Compressor settings Condenser settings Evaporator settings Special functions Code ST UI AR Indication Setpoints User interface Alarm settings Access Rights Three groups of users with different privilege levels are described below. Privilege Level Manufacturer Service User…
-
Main menu
Press button to enter main menus: Unit on/off I/O input/output User Parameter Clock Alarm history Unit on/off Press button, it display Press button, it display the unit current air conditioning (AC) and domestic hot water (HW) On/Off status. If the pre-set mode is heating, it display AC…
-
Press
button to enter. It displays Press button, black cursor flashes on “OFF” on HW status , press press button to enter, it will display button, it display Unit A/C and DHW are successfully switched on. “Starting “ displays on screen ,water pump turns on and display pump symbol on screen, with some…
-
Change System mode
Button Operation: Prg User System mode System mode only could be changed on heating/cooling unit (SF01 unit type setting cooling + heating). When unit is off state, press “Prg” to main menu, button to enter , it display press up or down button to User, press Enter Press Enter button, Heating will…
-
User Parameters
-
Heating compensation curve setting
The control temperature for heating mode has two methods: fixed and changeable temperature. The fixed temperature is a fixed value and directly set by the user from the set area. The changeable temperature is determined by values of ST05, ST06 and the actual outdoor temperature measured by the OT…
-
With the drop of the outdoor temperature, the control temperature become higher and
higher to meet the large heating requirement. With the increase of the outdoor temperature, the control temperature become lower and lower, so that the heat pump works under low pressure to keep low energy consumption. Changing ST05 or ST06 could change the heating curve . Increase ST05 will lift up…
-
The calculated control water temperature will not be over ST14 Maximum heating
temperature and will not be lower than ST13 Minimum heating temperature Cold weather conditions When the room temperature is too low, You could increase ST06 . When the room temperature is too high, you could decrease ST06. Warm weather conditions If the room temperature is too low, You…
-
Three curves of different ST05 setting
-
If SF04: Enable compensation =Yes,
S10 menu is popped up : Press to change ST05 and ST06, OT is actual measured ambient temp. control temp. ST will be displayed. Press Actual to menu S11: You could input any OT value ,press and relative heating control temp. will be calculated. If OT=-15.0℃, actual control temp. is 49.0℃ If you have…
-
Timezone on/off
Timezone activates the pre-set timer programs. Timezone function is only valid when unit ON/OFF method is “by keyboard”. TR09:AC timerzone is for space heating When TR09 is set YES, two different time periods is available to set in every day from Sunday to Saturday. After finishing timer setting for…
-
Access Service Level Parameter data
Display Procedures press <Prg> to main menu, press Down button to Parameter, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are inputted, It will enter Service level…
-
Service setup
Outdoor Side Anti-Freezing Setting Ground water with immediate heat exchanger system AR02 (outdoor side low outlet water temperature protection), factory default setting is 5 ℃. Ground loop system If brine is adopted as an outdoor side heating medium, AR02 needs to be changed according to brine…
-
Service Parameters
Service Parameters: Para- Descriptions meter De- Min. Max. Unit Res fault SF01 Unit type Only heating or Cooling + Heating EV01 Indoor pump control mode Continuous work EV03 Water pump set temp. difference on cooling ℃ 0.1 EV04 Indoor side pump set temp. difference on heating ℃ 0.1 SF05 Enable…
-
Steps to open the cabinets
The panels must be removed as the order : front panel – left panel – right panel – back panel 1. Unscrew the two screws at the bottom of front panel as below indication and then Front panel could be removed by pressing the panel downward. 2. Unscrews the screws as below indication to remove left…
-
3. The right panel could be removed as the same way of removing the left panel
4. Unscrew the screws as below and then back panel could be removed. 5. The RT ( inlet water temperature ) and ST (outlet water temperature ) sensor location 48
-
Cooling demand
-
Off: B4>ST09
Service Guide Control process Turn on process at heating mode 1.) Start water pumps , check water flow switch 2.) 5 seconds after water flow switch closes, if there is heating demand, start compressor Turn off process at heating mode 1.) Switch off compressor 2.) After 5 second’s delay, switch off…
-
2.) Producing hot water on cooling + hot water mode
Service Guide Auxiliary Electric heater or boiler control (NO4) Auxiliary heater or boiler only could be switched on when all of conditions below are met. 1.) Heating mode running; 2.) Compressor has run over 300s 3.) OT≤ST07; 4.) ST ≤ST02-ST04-1; Auxiliary heater or boiler could be switched off…
-
The indoor side pump PWM running control (Y3)
On cooling mode, after compressor is on, indoor side pump PWM runs as EV05 for 3 minutes, then runs with (Inlet temperature-Outlet temperature)=EV03 as target via PID control . when compressor is off, indoor side pump PWM runs as EV06. On heating mode, after compressor is on, indoor side pump PWM…
-
Manufacturer parameters
Access Manufacturer Level Parameter data Display Procedures press <Prg> to main menu, press Down button to Parameter, Press Enter button, Press Enter and 0 will flash, press Down button to the correct figure, press Enter to confirm. Likewise, change the other 3 figure .After 4 correct figure are…
-
Manufacturer parameters
Manufacturer parameters Para- DeDescriptions meter Min. Max. Unit Res fault CM01 Compressor minimum ON time Sec. 1 CM02 Compressor minimum OFF time 300 90 1000 Sec. 1 EV05 Indoor side PWM pump Max. speed - 1 EV06 Indoor side PWM pump Min. speed - 1 EV07 Pump integral time Sec. 1 EV08 Pump derivative…
-
1. Switch Off /Disconnect the Mains Fuse
2. Check Refrigerant Circuit for Leaks. a. Check heat pump gas pressure gauge reading for any leak. b. Open the front door with the key. Check the heat pump interior with a refrigerant leak detector or leak detection spray for refrigerant leaks. 3. Filling the Heating System a. Open any installed…
-
8. Checking the Tightness of Electrical Connections
9. Checking the Input Terminals and Contactors a. Check the voltage and cycle at the mains connection, at the inlet terminals and at the contactors. Interchange phases L1 and L3, if the phase sequence protector red light illuminates. 10. Checking the Sensor Connections a. Check whether all sensors…
-
speed of indoor side water pump and heating circuit pump
Commissioning and Adjusting 15. Checking the Refrigerant Circuit a. Observe the sight glass in refrigerant circuit. Bubbles >5 mm should not be visible, when heating flow has stabilized at 35°C. If large bubbles are visible, search and repair the leak in respective stage and refill with refrigerant.…
-
Commissioning Form
Commissioning Form Commissioning Form Client / Installation address: Telephone Number Installer: Commissioned by Heat pump Model: Heat pump serial number: Commissioning date: The heating system has been filled and pressure tested YES ( ) Expansion vessel for heating is sized, fitted & charged in…
-
Alarm Management
The alarms are divided into two groups: auto reset alarms and manual reset alarms. 1. Auto reset alarm, the user is not required to acknowledge and reset it. 2. The corresponding device will be automatically restarted once the alarm status disappears. 3. Once a manual reset alarm is detected, the…
-
Auto Reset Alarms
The following are codes for auto reset alarms with their meanings. Codes Meaning AL01 Low pressure AL02 High pressure AL03 Low indoor side outlet water temperature (ST<AR01) AL04 Low outdoor side outlet water temperature (STO<AR02) AL05 High indoor side outlet water temperature (ST>AR03) AL17 Indoor…
-
Viewing Alarm history
Display Procedures Press <Prg> button , then then press down button to Alarm History, press <Enter> to confirm. Press <up> or <down> to view other alarms If no alarm is generated, the word “No alarm!” will be displayed. Acknowledging and Resetting Manual Reset Alarms Any alarm detected by the…
-
Low pressure protection
(Code: AL01) After starting the compressor, it will check the low pressure after AR09 delay. If DI2=OFF, the compressor is off, 5 seconds later, outdoor side pump will be stopped, PWM water pump will run as EV06, other parts will keep its original state. A continuous blink code AL01 will appear on…
-
Indoor side Water flow switch protection (Code: AL17)
At starting process, if indoor side water flow switch does not close after AR04 time (DI1=OFF) after starting the indoor side water pump, a continuous blink warning code AL17 will appear on the LCD. If DI1=ON and last 5 seconds, it will return back to work. During unit working, if DI1=OFF and lasts…
-
When outdoor side water pump is off and ambient temperature≤SF06, outdoor side water pump will be switched on in every AR11 interval , 180 seconds later, If outdoor side outlet water temperature>SF08, switch off outdoor side water pump. If outdoor side outlet water temperature≤SF08 and unit is off…
-
Temperature Sensor trouble (auto reset)
If the temperature sensor is below -35C or higher 150C in 4.5 seconds, it will display sensor trouble. sensor code Trouble fixing B1 AL71 Unit will continue to run until it reaches preset temperature. later, it will start again. B2 AL72 Switch off the unit and display alarm code B3 AL73 Unit will…
-
Trouble Shooting
Trouble shooting Description Power failure Compressor has no sound, no action Compressor make a sound but no action Compressor can not stop Unit heating efficiency is low Possible cause Check faulty or disconnected fuse Check the mains supply phases and active/replace fuse Mains fault, voltage…
-
Maintenance
Maintenance To prevent faults due to sediment in the heat exchangers, care must be taken to ensure that no impurities can enter either the heat source system or the heating system. In the event that operating malfunctions due to contamination occur nevertheless the system should be cleaned as…
-
Dimension
GS04- GS20 Dimension outdoor inlet DHW outlet 80 indoor inlet indoor outlet outdoor outlet 100 power cable outlet Sensor outlet 1023 600 68
-
Dimension
GS26- GS30 Dimension 69
-
GS04 indoor pressure drop
GS04 Outdoor pressure drop 70
-
GS07 to GS30 are with same type condenser and evaporator
-
KPa
-
таблицы и схемы — в просмотре
-
Optional pump curve
GS04-GS10 Optional high efficiency pump curve GS12-GS15 Optional high efficiency pump curve 74
-
Triple phase units control board
1. 3. 4. 5. 6. 6 7 Interface Connection terminal strip A/C contactor Thermal overload relay Phase relay 2. 7. 8. 9. Circuit breaker Carel PCB 30A relay (only for units ≤20KW) Transformer 230V/24V
-
Heating only units
1. 2. 3. 4. 5. 6. Low Pressure Gauge Low Pressure Switch Compressor Service Connection, Low Pressure Indoor Side Heat Exchanger Refrigerant Liquid Indicator 76 7. Filter Dryer 8. Indoor Side Drain Valve 9. Indoor Side Differential Pressure Flow Switch (option) 10. Service Connection, High Pressure…
-
Heating only units
13. Outdoor Side Differential Pressure Flow Switch (option) 14. Outdoor Side Drain Valve 15. Expansion Valve 77
-
Heating and cooling units
1. 2. 3. 4. 5. 6. 7. Indoor Plate Heat Exchanger 8.. Filter Dryer 9. Indoor Side Drain Valve 10. Outdoor Side Heat Exchanger 11. Indoor Side Differential Pressure Flow Switch (option) Service Connection, High Pressure Low Pressure Gauge Compressor High Pressure Switch 4 way valve Refrigerant Liquid…
-
Heating and cooling units
12. Service Connection, Low Pressure. 13. Low Pressure Switch 14. Expansion Valve 15. Outdoor Side Differential Pressure Flow Switch (option) 16. Outdoor Side Drain Valve 79
-
Temperature and sensor resistance table
Temperature and sensor resistance table 80
-
таблицы и схемы — в просмотре
-
Technical
specifications Technical specifications: Heating only models: Heat pump Type GS07 GS09 GS12 GS10 GS13 GS15 GS20 GS26 GS30 Dimensions,weights,connection dimensions Dimensions HxWxD 1040x640X600 1040x640X800 Weight kg 140 150 Refrigerant Type Filling weight kg 1.30 1.60 1.70 1.60 1.70 2.10 2.15 2.80…
-
Technical specifications
Heating and cooling models: Heat pump Type GS07/B GS09/B GS12/B GS10/B GS13/B GS15/B GS20/B GS26/B GS30/B Dimensions,weights,connection dimensions Dimensions HxWxD 1040x640X600 Weight kg Refrigerant Type Filling weight kg 1.60 1.75 1.90 1.80 Permissible operating pressure Mpa 4.2 4.2 4.2 G11/4”…
-
On the side cabinet of the unit, there is a pressure gauge indicating the evaporation pressure R410A saturated pressure vs temperature table 84