Installation and maintenance manual
403 C – 02/06 C Date: June 2002 Supersedes: 403 C- 01/06 B Air to water heat pumps MHZ “B” 011.1 ÷ 038.2 Cooling capacity from 40 to 140 kW Heating capacity from 45 to 170 kW 50Hz – Refrigerant: HFC 407C Scroll Compressors
-
Introduction
Purpose of the manual The manual allows the installer and the operator to perform correctly all the operations referred to the installation and maintenance of the chiller without provoking any damages to the unit or to the qualified personnel. Therefore the manual is a great help for the qualified…
-
Electrical data MHZ “B”
Unit size Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) 011.1 013.1 017.1 020.1 022.2 025.2 029.2 033.2 036.2 038.2 400 V - 3f – 50 Hz + NEUTRAL A 32,3 37,8 45,4 54,8 64,1…
-
Physical data MHZ “B” HFC 407C units
Unit size 011.1 013.1 017.1 020.1 022.2 40,6 46,9 57,5 68,1 80,0 Cooling capacity (1) kW 14,1 17,2 22,4 27,8 29,9 Power input (1) kW 46,0 54,0 67,4 80,0 91,4 Heating capacity (2) kW 15,8 18,4 22,8 27,3 31,6 Power input (2) kW 10,2 11,9 14,4 17,3 20,5 Desuperheaters heating capacity (3) kW…
-
Safety measures
The unit must be suitably clamped to ground. It is necessary to follow these cautions and warnings: - The unit must be lifted only by using the proper tools able to support the weight of the unit. - No admittance to unauthorized or unqualified personnel. - No operation on electrical components is…
-
Space requirements
The MHZ units are air-cooled, hence it is important to observe the minimum distances which guarantee the best ventilation of the condenser coils. Limitations of space reducing the air flow could cause significant reductions in cooling capacity, and increase in electricity consumption. The fans do…
-
table on page 3) to protect the installation down to a temperature of 10 K below the lowest temperature likely to occur at the installation site (for example if the minimum forecast temperature is –13°C, must be considered a temperature of –23°C). If the unit is switched off and if the…
-
• • • the buzzer turns off the alarm relay disenergizes the temperature value blinks no longer the alarm code disappears from the LCD If the alarm condition persists, the actions described above will be performed again. Alarm table Display H1 L1 t1 FL E1,E2,E3 n1 EE EL d1 r1 A1 LO EU EO EP Cn Ht…
-
On this board you can locate clockwise the following connection “areas”
• • • • • • • • G and G0 terminals for power source connection (24Vac) analog inputs (from B1 to B3) for probe connection 24V terminal (with D.C.) for the supply of any pressure probes digital inputs (from ID1 to ID7) for alarm connection jumper connector for expansion board connection digital relay…
-
• • • • • • analog inputs (B4 and B5) for the probes connection (relative to the second circuit) 24V terminal (with D.C.) for the supply of any pressure probe digital inputs (from ID8 to ID11) for safety connections (relative to the second circuit) digital relay outputs to manage any controlled…
-
Meaning of LED indicators in single-compressor units
LED Flashing Tandem 1 Request for tandem 1 Request for tandem 2 Tandem 2 Request for tandem 1 at 100% Cooling Heating Χ100 - Steady Tandem 1 actuated Tandem 2 actuated Tandem 1 actuated at 100% Cooling Heating Value Χ100 Yellow and green LED indicators on the main board - The yellow LED indicator…
-
Buttons and relative messages on display Microprocessor MHZ 011.1÷038.2
Setting and displaying the set point and the main control parameters (DIRECT parameters). The DIRECT parameters are set-points (Cooling and Heating) and main control parameters of the unit (Cooling and Heating differentials, 1 and 2 circuit water temperature, 1 and 2 circuit condensation…
-
Copying the KEY in the unit's eeprom
Press PRG and t at µchiller start-up to copy the removable hardware key into the eeprom of the unit. When the procedure is over, the display will show 'CE' to confirm the operation. Copying the unit's eeprom in the key Press PRG and u at µchiller start-up to copy the unit's eeprom into the removable…
-
Verify that adeguate power supply and capacity is available to handle load. Start-up Start-up must be performed by specialized personnel: 1. Open the compressor suction and discharge shut-off valves; always replace seal caps. 2. Open the manual liquid line shut-off valve. 3. Check to see that the…
-
MHZ “B” Unit dimensions
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay Italia S.P.A. S.S. Nettunense, km 12+300 – 00040 Cecchina (Roma) Italia – Tel. (06) 937311 – Fax (06) 9374014 – E-mail: mcquay@mcquayitalia.com