Product Manual
Date: November 2004 Supersedes: 403 B- 02/03 D $LUWRZDWHUKHDWSXPSV 0+=³%´· &RROLQJFDSDFLW\IURPWRN: +HDWLQJFDSDFLW\IURPWRN: +]±5HIULJHUDQW+)&& 6FUROO&RPSUHVVRUV 403 B – 04/11 E McQuay is participating in the Eurovent Certification Programme. Product are as listed in the Eurovent Directory of…
-
New McQuay Air to water heat pumps unit MHZ
McQuay International introduces their newest air to water heat pumps MHZ equipped with scroll compressors and electronic control system. McQuay have once again succeded in developing a high quality product with extraordinary performance which is able to satisfy HVAC applications. McQuay units are…
-
Factory testing
Each unit is pressure tested, vacuum tested, evacuated and charged with refrigerant requested. It is then tested at the factory’s test bench under the design conditions specified by the customer. Upon request, a second series of tests can be carried out witnessed by the customer. Before shipment…
-
water temperature control
regulation of temperature set points start-up sequence delay device compressor on-off control fan on-off control antifreeze control antifreeze heater functioning general alarm differential pressure switch or pump failure alarm On request, remote programming infrared-control and remote PC board are…
-
Open Cage packing - Protection with polythene and wooden cage for transport and protection before the installation. Rubber type antivibration mounts - Supplied separately, these will be positioned under the base of the unit during installation. Ideal to reduce the vibrations when the unit is floor…
-
Table 6 - Fouling factor
Fouling factor m2 °C / kW Cooling capacity correction factor 0,044 0,132 0,308 1,000 0,986 0,939 Water content in cooling circuits The cooled water distribution circuits should have a minimum water content to avoid excessive compressors start and stop. In fact, each time the compressor starts up, an…
-
When two or more units are positioned side by side it is recommended that the condenser coils are at least 2500 mm distance from one another (fig. 2). Smaller distances could cause the recirculation of hot air. If the units are positioned in places surrounded by walls or obstacles of the same height…
-
Physical data MHZ “B” HFC 407C units
Unit size 011.1 013.1 017.1 020.1 022.2 40,6 46,9 57,5 68,1 80,0 Cooling capacity (1) kW 14,1 17,2 22,4 27,8 29,9 Power input (1) kW 44,9 52,6 65,8 78,1 89,2 Heating capacity (2) kW 15,4 18,0 22,2 26,6 30,8 Power input (2) kW 10,2 11,9 14,4 17,3 20,5 Desuperheaters heating capacity (3) kW…
-
Electrical data MHZ “B”
Unit size Standard voltage (1) Nominal unit current (2) Max compressor current (3) Fans current Max unit current (3) Max unit inrush current (4) Max unit current for wires sizing (5) 011.1 013.1 017.1 020.1 022.2 025.2 029.2 033.2 036.2 038.2 400 V - 3f – 50 Hz + NEUTRAL A 32,3 37,8 45,4 54,8 64,1…
-
Unità
MHZ HFC 407C 011.1 013.1 017.1 020.1 022.2 Notes: Temperatura uscita acqua evap. (°C) Standard ratings MHZ “B” 011.1÷022.2 HFC 407C TEMPERATURA AMBIENTE & Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza Potenza assorbit frigorif. assorbita frigorif. frigorif. assorbita…
-
Unit
size HFC 407C 025.2 029.2 033.2 036.2 038.2 Notes: Evaporator leaving temp.(°C) Standard ratings MHZ “B” 025.2÷038.2 HFC 407C AMBIENT TEMPERATURE - °C Cooling capacity (kW) Power input (kW) Cooling capacity (kW) Power input (kW) Cooling capacity (kW) Power input (kW) Cooling capacity (kW) Power…
-
Unit
size HFC 407C 011.1 013.1 017.1 020.1 022.2 025.2 029.2 033.2 036.2 038.2 Notes: Leaving water temperature (°C) Heating capacity ratings MHZ “B” 011.1÷038.2 HFC 407C AMBIENT TEMPERATURE - °C -5 Heating capacity (kW) Power input (kW) Heating capacity (kW) Power input (kW) Heating capacity (kW) Power…
-
Evaporator pressure drops
403 B – 04/11 E – page 13/16
-
Water pump diagrams
Type “A” water pump Standard voltage 400/3/50 – Motor power 0,75 kW – Absorbed current 2,3 A – IP 55 200 Hydraulic lift (kPa) 0,50 1,00 1,50 2,00 2,50 3,00 3,50 4,00 4,50 Water flow (l/s) Type “B” water pump Hydraulic lift (kPa) Standard voltage 400/3/50 – Motor power 1,5 kW – Absorbed current 4,3 A…
-
MHZ “B” Unit dimensions
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay partecipa al programma di Certificazione Eurovent. I prodotti interessati figurano nella Guida Eurovent dei Prodotti Certificati. McQuay is participating in the…