Package Air Conditioner
-
1. PREFACE
This service manual provides various service information, containing the mechanical and electrical parts and etc. This package air conditioner was manufactured and assembled under the strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions…
-
1.3 Product Specifications
-
1.4 Functions
Indoor Unit Power Switch ON/OFF Operation Mode Control • Cooling, Fan, Soft dry, Auto operation ⇒ "CL" series Model • Cooling, Heater, Fan, Soft dry, Auto operation ⇒ "XL" series Model Sensing the room temperature • Room temperature sensor (Thermistor) Sensing the pipe temperature • Pipe temperature…
-
Outdoor Unit
Outdoor Fan Speed Control • One speed Sensing Discharge Pressure For Compressor • Discharge pressure sensor (High Pressure Switch) Sensing Suchion Pressure for Compressor • Suction pressure sensor (Low Pressure Switch) –6–
-
2. DIMENSIONS
-
3. REFRIGERANT CYCLE DIAGRAM
• Cooling Cycle INDOOR UNIT OUTDOOR UNIT LIQUID SIDE CAPILLARY TUBE 3-WAY VALVE HEAT EXCHANGER HEAT EXCHANGER GAS SIDE 3-WAY VALVE ACCUMULATOR MUFFLER COMPRESSOR –8–
-
4. WIRING DIAGRAM
-
4.2 LP-10091XL
-
4.3 LP-15091CL
-
4.4 LP-15091XL
-
2(V)
-
X
-
4.6 LP-20091XL
-
• OUTDOOR UNIT
-
5. OPERATION DETAILS
(1) The function of main control 1. Time Delay Safety Control • 3min... The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) • 3sec... The indoor fan is ceased for 3 seconds to prevent relay noise. (Protection of fan relay and micro…
-
3. Soft Dry Operation Mode
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°C, the compressor OFF temperature is the setting temperature minus 1°C. • When the room temperature rises over the compressor ON temperature, the operation mode is switched to the Cooling mode. • When the…
-
6. Alarm mode display / only displayed while operating. (10K, 15K)
CH 0 : The sensor for sensing room temperature is open or short. CH 2 : Some keys of the display are out of order or short. 7. Function for Air-Circulation Air-Flow • If you press Fan operation button, indoor Fan is only operating without compressor working. • On Air-flow mode, temperature setting…
-
6. Installation
6.1 Installation of Indoor, Outdoor unit 1) Selection of the best location ① Indoor unit • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where…
-
2) Indoor Unit installation
3) Outdoor unit Installation The mounting floor should be strong and solid enough to prevent it from vibration. Install the outdoor unit on the concrete or any solid base securely and horizontally. Drill the piping hole with 70mm diameter hole-core drill at either the right or the left of indoor…
-
6.2 Installation Method
1) Procedure No. Installation works Descriptions 1 Preparation of tools and installation parts Preparation of installation 2 Flaring the pipes To insert the flare nuts, mounted on the connection parts of both indoor and outdoor unit, onto the copper pipes. 3 Pipe bending To reduce the flow…
-
2) Preparation of installation parts and tools
No. Installation Parts, Tools 1 Pipe cutter (MAX 35mm Copper pipe) Cutting the pipings 2 Remear Remove burrs from cut edges of pipes. 3 Wrench (H5, H4 hexagonal wrench) To open the service valve 4 Pipe bender Bending the pipings 5 Leak detector Check a gas-leakage of connecting part of the pipings 6…
-
6.3 Piping of Indoor Unit
Pipe cutter 1) Preparation of piping ① Cut the pipes and the cable • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than measured distance. • Cut the cable 1.5m longer than the pipe length.…
-
3) Precautions in bending
① If it is necessary to bend or stretch the tubing, use the spring which is attached to the tubing in stead of pipe bender. Spring R70mm • Please make a careful notice to make a smooth line. • Hold the tubing with your two hands closely and then bend or stretch it slowly not to make any crack. (Fig.…
-
6.6 Power Supply and Wiring
MODEL The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with. 1) Power Supply Power source must fulfill the following conditions: ① The working voltage should be higher than 90% and…
-
6.7 Wiring
-
6.8 Checking the Drainage and Form the Piping
1) Checking the Drainage ① Remove the inlet grille. ② Check the drainage. • Pour a glass of water into the drain pan. • Ensure if water flows drain hose of indoor unit. – 28 –
-
2) Form the Piping
① Wrap the connecting portion of indoor unit with the insulation material and secure it with two Plastic Bands. (for the right piping) • If you connect an additional drain hose, the end of the drain-outlet should be kept distance from the ground. (Do not dip it into water, and fix it on the wall to…
-
6.9 Final Check and Test Run
After installing the unit, perform the final check and running test as follows: Final check points ① Is the unit securely mounted? ② Is the installation location adequate? ③ Is the water piping work adequately and without leakage? ④ Are trapped drain lines installed at condensate drain connections?…
-
6.10 Indoor Unit Controls and Indicators
(LP-10091CL/XL, LP-15091CL/XL) • Display Heater ON/OFF Button(XL MODEL ONLY) Timer Setting Button (Operation stops at ON) Fan Operation Lamp Cooling Operation Lamp Timer Operation Lamp Duct Airflow Lamp (LP-10091CL/XL MODEL ONLY) Heating Operation Lamp (XL MODEL ONLY) Outdoor Unit Operation Lamp…
-
6.11 Indoor Unit Controls and Indicators(LP-20091CL/XL)
• Controls Cooling model LOW COOL/HIGH COOL Lamp • When the unit sets cooling operation condition, the Lamp is lighted. LOW COOL HIGH COOL FAN OFF LOW HIGH COOL COOL HIGH MODE LOW TEMP Heating and Cooling model Heating Lamp • When the unit sets heating operation condition, the Lamp is lighted. FAN…
-
7. 3-WAY VALVE
3-Way Valve (Liquid Side) Valve cap Open position Flare nut Closed position 3-Way Valve (Gas Side) Valve cap Open position Flare nut Closed position Pin To piping connection Service Service port cap port To outdoor unit Pin To piping connection Service Service port cap port To outdoor unit Works…
-
7.1 Air purging
Required tools: hexagonal wrench, adjustable wrench, torque wrench, and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed.…
-
7.2 Pumping down
Liquid side Indoor unit 3-Way valve Closed Outdoor unit Gas side Open 3-Way valve Lo CLOSE CLOSE Purge the air • Procedure ① Confirm that both 3-way(liquid side) and 3-way(gas side) valves are set to the open position. • Remove the valve stem caps and confirm that the valve stems are in the raised…
-
1) Re-air purging
(Re-installation) Indoor unit Liquid side 3-Way Closed valve Outdoor unit Gas side 3-Way valve Closed Gas cylinder R22 OPEN CLOSE • Procedure ① Confirm that both the 3-way (liquid side) valve and the 3-way(gas side) valve are set to the closed position. ② Connect the charge set and a gas cylinder to…
-
2) Balance refrigerant of the 3-way(liquid side), 3-way(gas side) valves
(Gas leakage) Indoor unit Liquid side Outdoor unit 3-Way valve Open 3-Way valve Open Gas side OPEN CLOSE • Procedure ① Confirm that both the liquid side and gas side valves are set to the back seat. ② Connect the charge set to the 3-way(gas side) valve's port. • Leave the valve on the charge set…
-
7.3 Evacuation
(All amount of refrigerant leaked) Liquid side Indoor unit Outdoor unit 3-Way valve Open 3-Way valve Open Gas side Vacuum pump Lo OPEN CLOSE • Procedure ① Connect the vacuum pump to the center hose of charge set. ② Evacuation for approximately one hour. - Confirm that the gauge needle has moved…
-
7.4 Gas Charging
1) Cooling mode (After Evacuation) Liquid side Indoor unit Open Outdoor unit 3-Way valve Gas side Open 3-Way valve Check valve Charging cylinder Lo (1) OPEN CLOSE • Procedure ① Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from the vacuum pump to…
-
8. TROUBLESHOOTING GUIDE
In general, possible trouble is classified as two causes. The one is so called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling…
-
Failures to Start
Check power source. Check of circuit breaker and fuse. Check control switch setting. Check control switch. Compressor only fails to start Fan only fails to start Electric heater is not energized Improper wiring Drop of power voltage Defect of compressor capacitor Loose terminal connection. Improper…
-
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM MAXIMUM 220 V 198 V 242 V 380 V 342 V 418 V 8.1 No cooling and heating operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts than the unit Electric supply interrupted Defective power wiring Cut of…
-
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Motor Over-heated Layer short Check how it is insulated. Repair or replace it. Electric Wiring Open wire on operation Check it with a tester. Rewiring or repair. Short circuited operation on 4) Only compressor does not work WHAT TROUBLED COMPLAINTS HOW TO…
-
8.2 The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts than the unit Improper opening of the service valves in the refrigerant line Checking Open it properly Outdoor coil Coil is dirty *1 Checking Wash it by means of something like chemical washing. In-condensable gas blended. Air intruded into…
-
8.3 The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much heat load Heat load increased. Window or door has many cracks or gaps. Do necessary disposal respectively. Air flow Obstacle disturbs Intake of uniform wind. Checking Correct it. Short air volume Reverse…
-
COMPLAINTS
HOW TO CHECK REMEDY Electric troubles (Magnetic contactor) Defective contact. Defective contact point. Rusting and faults in the iron core contact face. Defective contact of the operating switch. Checking Repair and clean or replace it. Others Improper installation Checking Correct it. 8.5 Trouble…
-
Fault
Internal Thermostat Cut-Off Overcurrent Relay for Compressor Cut-Off Overcurrent Relay for Fan Motor Cut-Off Cause Check/Correcitve Action Discharge pressure is lower than standard. See "Low Discharge Pressure". Single or three phases running. Check the power supply line and the contactor. High or…
-
8.6 Electronic Parts Troubleshooting Guide
1) No cooling operation performed. Is the AC220V (AC 240 V) between Connector(CNoutunit) Pin 1 and Pin 3 of Main P.C.B YES Is the input power AC220V (AC240V) at COMP Magnetic coil? NO NO NO YES Is the unit operating? Check the magnetic contactor of outdoor unit. YES Reset the power ON/OFF S/W ON Is…
-
2) Indoor fan does not operate (LP-10091CL/XL)
-
3) Indoor fan does not operate (LP-15091CL/XL)
-
4) The unit does not operate
Is the AC220V (240V) at Trans input terminal? NO 1. Check the electric connections 2. Check the fuse of Main PCB ASM YES Is the AC12-18V at Trans (2nd)? NO Replacement Trans YES Is the connector of Main/Display correct? NO Check the connector of Main/Display YES Is the DC5V between PIN64 and PIN 32…
-
5) No heater operation works
-
9. ELECTRONIC CONTROL DEVICE
-
10. SCHEMATIC DIAGRAM
-
11. EXPLODED VIEW & REPLACEMENT PARTS LIST
-
Top cover Bimetal(2nd) Bimetal(1st) Thermal Fuse(3rd) 54 Fixing screw Diffuser assy Electric heater 52 Barrier blower hole Front panel Heater bracket Barrier blower Control box 53 Inlet grille Electric heater connector Electric heater connector for the control box Thermal Fuse Type Bimetal Type…
-
DESCRIPTION
-
таблицы и схемы — в просмотре
-
1) Exploded View 52-1 30-1 30-2 31 – 61 –
-
Top cover Bimetal(2nd) Thermal fuse(3rd) Bimetal(1st) Thermal fuse(3rd) 62 Fixing screw Diffuser assy Electric heater 60 Barrier blower hole Front panel Heater bracket Barrier blower Control box 61 (for Electric heater) Inlet grille Electric heater connector Heater cable Electric heater connector…
-
DESCRIPTION
-
таблицы и схемы — в просмотре
-
1) Exploded View 30-1 30-2 31 – 66 –
-
Top cover Bimetal(2nd) Bimetal(1st) Thermal fuse(3rd) 66 Fixing screw Diffuser assy Electric heater 65 Barrier blower hole Front panel Heater bracket Barrier blower Inlet grille Connected to No.1, No.3 of the control box terminal block Electric heater connector for the control box Thermal Fuse Type…
-
DESCRIPTION
-
таблицы и схемы — в просмотре
-
DESCRIPTION
-
таблицы и схемы — в просмотре
-
– 74 – 24-1 25-1 1) Exploded View
-
DESCRIPTION
-
1) Exploded View – 76 –
-
DESCRIPTION
-
таблицы и схемы — в просмотре
-
May, 2000 Printed in Korea
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Кондиционеры серии LP-K3020HL/HA, LP-K3061HL/HA, LP-K3061ZL/ZA. Инструкция по монтажу и эксплуатации.PDF · 1.16 Mb
- Кондиционеры серии LP-K2060CL/CA, LP-K3061CL/CA, LP-K3020CL/CA, LP-K4020CL/CA. Инструкция по монтажу и эксплуатации.PDF · 1.08 Mb
- Кондиционеры серии LP-K3020HL/HA, LP-K3060HL/HA, LP-K3060ZL/ZA. Инструкция по монтажу и эксплуатации.PDF · 953.65 Kb
- Кондиционеры модели LP-K2060CL/CA, LP-K3060CL/CA, LP-K3020CL/CA, LP-K4020CL/CA. Инструкция по монтажу и эксплуатации.PDF · 873.70 Kb
- Кондиционеры серии LP-F8081CL/HL/ZL. Инструкция по монтажу и эксплуатации.PDF · 1.49 Mb
- Кондиционеры серии LP-E5020CL, LP-E5022CL/CA/HL/HA, LP-E5082CL/CA/HL/HA/ZL/ZA, LP-E5092CL/CA/HL/HA, LP-E50B0CL/CA/HL/HA. Инструкция по монтажу и экс…PDF · 1.96 Mb
- Кондиционеры серии LP-8091PC. Инструкция по монтажу и эксплуатации.PDF · 1.11 Mb