Air Conditioner SERVICE MANUAL MODEL: LP-8091PC
-
1. Preface
This service manual provides various service information, containing the mechanical and electrical parts and etc. This package air conditioner was manufactured and assembled under the strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions…
-
1.3 Product Specifications
MODEL LP-8091PC POWER SOURCE (ø, V, Hz) 3, 220, 60 COOLING Btu/h 71,400 W 20,927 INPUT W 9,500 CURRENT A 27.6 CAPACITY COMPRESSOR MAKER COPELAND TYPE RECIPRO MODEL QR90K2-ES8 INPUT W 9,500 LRA A 110 CAPACITY Kcal/h 91,000 NOISE INDOOR dB(A) 64 LEVEL(1m) OUTDOOR AIR INDOOR VOLUME OUTDOOR 66 50 CMM…
-
1.4 Functions
Indoor Unit Power Switch ON/OFF Operation Mode Control • Cooling, Fan ➔ Cooling Model Sensing the room temperature • Room temperature sensor (Thermistor) Controlling the room temperature • Maintains the room temperature in accordance with the setting temperature. Starting Current Control • Indoor…
-
Outdoor Unit
Outdoor Fan Speed Control • One speed Sensing discharge pressure for compressor • Discharge pressure sensor(High Pressure Switch) –6–
-
2. Wiring Diagram
-
3. Dimensions
Indoor Unit Air outlet vent 728 Window display 725 1800 Liquid side piping hole 780 Air inlet vent 134 Connecting cable and liquid/gas side piping hole 210 305 Earth screw Outdoor Unit Air Outlet Vent Air Inlet Vent 1245 –8– Drain hole
-
4. Operation details
■ The function of main control 1. Time Delay Safety Control • 3min... • 3sec... The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) The indoor fan is ceased for 1~3 seconds to prevent relay noise. (Protection of fan relay and micro…
-
5. Off Timer Function
This function is to set the time of stopping the unit operation. The procedure is as the following. 1st: Press the timer set button on the Remocon. 2nd: The buzzer sounds and then the display window shows the Off-Time to be set as 1:00→ → 7:00 →0:00. - The Off-Time is shifted as the following by…
-
5. Installation
5-1. Installation of Indoor, Outdoor unit 1) Selection of the best location ➀ Indoor unit 100cm • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • A place where air circulation in the room will be good. • A place where…
-
2) Indoor Unit installation
3) Outdoor unit Installation ➀ The mounting floor should be strong and solid enough to prevent it from vibration. ➁ Drill the piping hole with 70mm diameter holecore drill at either the right or the left of indoor unit. The hole should be sightly slant to the outdoor side. ➀ Install the outdoor unit…
-
5-2. Installation Method
1) Procedure No. Installation works Descriptions 1 Preparation of tools and installation parts Preparation of installation 2 Flaring the pipes To insert the flare nuts, mounted on the connection parts of both indoor and outdoor unit, onto the copper pipes. 3 Pipe bending To reduce the flow…
-
2) Preparation of installation parts and tools
No. Installation Parts, Tools Use 1 Pipe cutter (MAX 35mm Copper pipe) Cutting the pipings 2 Remear Remove burrs from cut edges of pipes. 3 Wrench (H5, H4 hexagonal wrench) To open the service valve 4 Pipe bender Bending the pipings 5 Leak detector Check a gas-leakage of connecting part of the…
-
5-3. Piping of Indoor Unit
1) Preparation of piping ➀ Cut the pipes and the cable • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • Cut the pipes a little longer than measured distance. • Cut the cable 1.5m longer than the pipe length. Pipe cutter…
-
3) Precautions in bending
➀ If it is necessary to bend or stretch the tubing, use the spring which is attached to the tubing in stead of pipe bender. Spring • Please make a careful notice to make a smooth line. • Hold the tubing with your two hands closely and then bend or stretch it slowly not to make any crack. • Remember…
-
5-6. Power Supply and Wiring
The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with. 1) Power Supply Power source must fulfill the following conditions: ① The working voltage should be higher than 90% and lower…
-
5-7. Air Purging of the Piping and Indoor Unit
The air which contains moisture and which remains in the Refrigeration cycle may cause a malfunction on the compressor. Outdoor unit ① Remove the caps from the 4-way(liquid side) and 4-way(gas side) valves. Service port cap Hexagonal wrench ② Remove the service-port cap from the 3-way (gas side)…
-
⑦ Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the Hexagonal
wrench for the unit operation. ⑧ Checking a gas leakage for the left piping • Connect the manifold gauge to the service port of 3-way(gas side) valve. Measure the pressure. • Keep it for 5 - 10 minutes. Ensure if the pressure indicated on the gauge is as same as that of measured at first time.…
-
5-8. Checking the Drainage and Form the Piping
1) Checking the Drainage ① Remove the inlet grille. ② Check the drainage. • Pour a glass of water into the drain pan. • Ensure if water flows drain hose of indoor unit. –20–
-
2) Form the Piping
① Wrap the connecting portion of indoor unit with the insulation material and secure it with two Plastic Bands. (for the right piping) • If you connect an additional drain hose, the end of the drain-outlet should be kept distance from the ground. (Do not dip it into water, and fix it on the wall to…
-
5-9. Final Check and Test Run
After installing the unit, perform the final check and running test as follows: Final check points Running test should be accomplished as follows: ① Set operation switch at "FAN" and the fan will start. Check to ensure that the fan sounds normal. ① Is the unit securely mounted? ② Is the installation…
-
6. Operation
Display ■ Auto Airflow Direction Cpntrol Button and Lamp ■ Timer Setting Button and Lamps (Oeration stops at ON) Start/Stop Button ■ (Operation will start when this button is pressed, and stop when the button is pressed again) ■ Temperature/Time Display Window ■ Temperature Setting Buttons ■ Indoor…
-
7. 3-Way Valve
3-Way Valve (Liquid Side) 3-Way Valve (Gas Side) Valve cap Open position Flare nut Closed position Valve cap Open position Flare nut Closed position Pin Pin To piping connection Service Service port cap port To outdoor unit To piping connection Service Service port cap port To outdoor unit Works…
-
7-1. Air purging
Required tools: hexagonal wrench, adjustable wrench, torque wrench, and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed.…
-
7-2. Pump down
Liquid side Indoor unit 3-Way valve Closed Outdoor unit Gas side Open 3-Way valve Lo CLOSE CLOSE Purge the air • Procedure ⑤ Set the 3-way(liquid side) valve to the closed position. ① Confirm that both 3-way(liquid side) and 3way(gas side) valves are set to the open position. • Remove the valve stem…
-
1) Re-airpurging
(Re-installation) Indoor unit Liquid side 3-Way Closed valve Outdoor unit Gas side 3-Way valve Closed Gas cylinder R22 OPEN CLOSE • Procedure ① Confirm that both the 3-way (liquid side) valve and the 3-way(gas side) valve are set to the closed position. ⑤ Discharge the refrigerant. • Close the valve…
-
2) Balance refrigerant of the 3-way(liquid side), 3-way(gas side) valves
(Gas leakage) Indoor unit Liquid side Outdoor unit 3-Way valve Open 3-Way valve Open Gas side OPEN CLOSE • Procedure ① Confirm that both the liquid side and gas side valves are set to the back seat. ② Connect the charge set to the 3-way(gas side) valve's port. • Leave the valve on the charge set…
-
7-3. Evacuation
(All amount of refrigerant leaked) Liquid side Indoor unit Outdoor unit 3-Way valve Open 3-Way valve Open Gas side Vacuum pump Lo OPEN CLOSE • Procedure ① Connect the vacuum pump to the center hose of charge set. ② Evacuation for approximately one hour. - Confirm that the gauge needle has moved…
-
7-4. Gas Charging
1) Cooling mode (After Evacuation) Liquid side Indoor unit Open Outdoor unit 3-Way valve Gas side Open 3-Way valve Check valve Charging cylinder Lo (1) OPEN CLOSE • Procedure ① Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from the vacuum pump to…
-
8. Troubleshooting Guide
In general, possible trouble is classified as two causes. The one is so called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling…
-
Failures to Start
Check power source. Check of circuit breaker and fuse. Check control switch setting. Check control switch. Compressor only fails to start Fan only fails to start Electric heater is not energized Improper wiring Drop of power voltage Defect of compressor capacitor Loose terminal connection. Improper…
-
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM MAXIMUM 220V 198V 242V 8-1. No cooling operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED Other parts than the unit COMPLAINTS HOW TO CHECK Electric supply interrupted Measure it with a tester in Defective power wiring Cut case that the same…
-
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Motor Over-heated Layer short Check how it is insulated. Repair or replace it. Electric Wiring Open wire on operation Check it with a tester. Rewiring or repair. Short circuited on operation 4) Only compressor does not work WHAT TROUBLED COMPLAINTS HOW TO…
-
8-2. The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts than the unit Improper opening of the service valves in the refrigerant line Checking Open it properly Outdoor coil Coil is dirty *1 Checking Wash it by means of something like chemical washing. In-condensable gas blended. Air intruded into…
-
8-3. The unit is working, but not cooling sufficiently
(Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much heat load Heat load increased. Window or door has many cracks or gaps. Do necessary disposal respectively. Air flow Obstacle disturbs Intake of uniform wind. Checking Correct it. Short air volume Reverse…
-
COMPLAINTS
HOW TO CHECK REMEDY Electric troubles (Magnetic contactor) Defective contact. Defective contact point. Rusting and faults in the iron core contact face. Defective contact of the operating switch. Checking Repair and clean or replace it. Others Improper installation Checking Correct it. 8-5. Trouble…
-
Fault
Internal Thermostat Cut-Off Overcurrent Relay for Compressor Cut-Off Overcurrent Relay for Fan Motor Cut-Off Cause Check/Correcitve Action Discharge pressure is lower than standard. See "Low Discharge Pressure". Single or three phases running. Check the power supply line and the contactor. High or…
-
8-6. Electronic Parts Troubleshooting Guide
1) No cooling operation performed. Is the AC220V (AC 240 V) between Connector(CNoutunit) and of Main P.C.B YES Is the input power AC220V (AC240V) at COMP Magnetic coil? NO NO NO YES Is the unit operating? Check the magnetic contactor of outdoor unit. YES ON/OFF S/W ON Is it Cooling mode? NO YES Room…
-
2) Indoor fan does not operate
-
3) The unit does not operate
Is the AC220V (240V) at Trans input terminal? NO 1. Check the electric connections 2. Check the fuse of Main PCB ASM YES Is the AC12-18V at Trans (2nd)? NO Replacement Trans YES Is the connector of Main/Display correct? NO Check the connector of Main/Display YES Is the DC5V between PIN64 and PIN 32…
-
9. Electronic Control Device
-
10. Schematic Diagram
Circuit and Troubleshooting –44–
-
11. Exploped View and Replacement Parts List
Indoor Unit 18-2 18-1 –45–
-