Package
-
1. PREFACE
This service manual provides various service information, containing the mechanical and electrical parts and etc. This package air conditioner was manufactured and assembled under the strict quality control system. The refrigerant is charged at the factory. Be sure to read the safety precautions…
-
1.3 Product Specifications
MODEL LP-E5082CL/CA LP-E5082HL/HA LP-E5082ZL/ZA LP-E5020CL LP-E5022CA LP-E5022HL/HA POWER SOURCE (ø, V, Hz) 3.380 - 415,50 3,380 - 415,50 1,200,60 1,220,60 Btu/h 44,000 44,000 44,000 44,000 W 12,896 12,896 12896 12,896 INPUT W 3,600 3,600 3,600 5500 CURRENT A CAPACITY Btu/h (W) – 48,000 +(3,000)…
-
MODEL
-
1.4 Functions
Indoor Unit Power Switch ON/OFF Operation Mode Control • Cooling, Soft Dry, Auto, Fan ¢¡Cooling Model • Cooling, Heating, Soft Dry, Fan ¢¡Heat Pump Model Sensing the room temperature • Room temperature sensor (Thermistor) Controlling the room temperature • Maintains the room temperature in…
-
Remote Control
Operation ON/OFF Operation Mode Selection • Cooling, Soft Dry, Auto, Fan ¤I Cooling Only Model • Cooling, Heating, Soft Dry, Fan, ¤I E/heater Heat Pump Model Fan Speed Selection • High, Medium, Low Setting the temperature • Up or Down Timer Control • Off Timer(1, 2, 3...7 hour) Airflow Direction…
-
2. DIMENSIONS
1) Indoor Unit 1513 58.2 37.3 605.5 80 ¤ Air Outlet Vent ¤ØWindow display ¤ŁAir Inlet Vent ¤ŒEarth Screw 2) Outdoor Unit 1220 ¤ Air Outlet Vent ¤ŒControl Box ¤ŁLiquid Side SVC Valve ¤ºEarth Screw ¤ØGas Side SVC Valve –8–
-
3. REFRIGERANT CYCLE DIAGRAM
3.1 Cooling Cycle INDOOR UNIT OUTDOOR UNIT LIQUID SIDE CAPILLARY TUBE 3-WAY VALVE HEAT EXCHANGER HEAT EXCHANGER GAS SIDE 3-WAY VALVE ACCUMULATOR MUFFLER COMPRESSOR 3.2 Cooling and Heating Cycle INDOOR UNIT OUTDOOR UNIT LIQUID SIDE CHECK VALVE 3-WAY VALVE CAPILLARY TUBE CAPILLARY TUBE HEAT EXCHANGER…
-
4. WIRING DIAGRAM
-
WIRING DIAGRAM – 12 –
-
5. OPERATION DETAILS
(1) The function of main control 1. Time Delay Safety Control • 3min... • 3sec... • 1min... The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) The indoor fan is ceased for 1~3 seconds to prevent relay noise. (Protection of fan relay…
-
4. Auto Operation (Cooling Model only)
ƒUThe operation procedure is as following. Press Start/Stop Button Select Auto Operation Mode Check the Room temperature ƒUAuto Operation for Cooling Operation Condition When Switch to Auto Operation Intake-air Temperature Setting temperature Over 26°C 25°C Over 24°C~below 25.5°C Intake air -1.0°C…
-
5. Heating Mode Operation
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Intake Air Temp. Setting Temp. +1°C (Compressor OFF) A A Setting Temp. (Compressor ON) Setting Temp. -1°C Hot Start minimum minimum minimum 10sec. 10sec. 1min Indoor Fan Speed…
-
6. Hot-Start Control
• The indoor fan stops until the evaporator piping temperature will be reached to 28°C. • During heating operation, if piping temperatures fall below 26°C fan stops. • The operation diagram is as following. Maximum 1min INDOOR PIPE TEMP. 28°C 26°C INDOOR FAN SPEED OFF Selecting fan speed LOW…
-
8. Soft Dry Operation Mode
• During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 2°C, the compressor OFF temperature is the setting temperature minus 1°C. • When the room temperature rises over the compressor ON temperature, the operation mode is switched to the Cooling mode. • When the…
-
12. Off Timer Function
This function is to set the time of stopping the unit operation. The procedure is as the following. 1st: Press the timer set button on the Remocon. 2nd: The buzzer sounds and then the display window shows the Off-Time to be set as 1:00¡ ¡ 7:00 ¡ 0:00. - The Off-Time is shifted as the following by…
-
6. INSTALLATION
6.1 Installation of indoor, Outdoor Unit 1) Select the best location 5cm ¥LIndoor unit • There should not be any heat source or steam near the unit. • There should not be any obstacles to prevent the air circulation. • The place where air circulation in the room will be good. • The place where…
-
2) Indoor Unit installation
3) Outdoor unit Installation ¥LThe mounting floor should be strong and solid enough to prevent it from vibration. ¥LInstall the outdoor unit on the concrete or any solid base securely and horizontally by securing it with bolts (Ø12mm) and nuts. ¥MDrill the piping hole with 70mm diameter hole-core…
-
6.2 Installation Method
1) Procedure No. Installation works Descriptions 1 Preparation of tools and installation parts Preparation of installation 2 Flaring the pipes To insert the flare nuts, mounted on the connection parts of both indoor and outdoor unit, onto the copper pipes. 3 Pipe bending To reduce the flow…
-
2) Preparation of installation parts and tools
No. Installation Parts, Tools Use 1 Flaring tool (Ø 6,35 - Ø 19,05) Flaring the pipes 2 Reamer Remove burrs from cut edges of pipes. 3 Pipe cutter (Max 35mm Copper pipe) Cutting the pipings 4 Wrench (H5, H4 hexagonal wrench) To open the service valve 5 Pipe bender Bending the pipings 6 Leak detector…
-
6.3 Piping of indoor unit
Pipe cutter 1) Preparation of pipings ¤ Cut the pipes and the cable Slanted 90° • Use the accessory piping kit or the pipes purchased locally. • Measure the distance between the indoor and the outdoor unit. • cut the pipes a little longer than measured distance. • Cut the cable 1.5m longer than the…
-
2) Connection of pipings
¤ Move the indoor tubing and drain hose to the hole • Remove tubing holder and pull the tubing out of the chassis. ¤ŁReplace the tubing holder into original position ¤ØRoute the tubing and the drain hose staight backwards. ¤ŒInsert the connecting cable into the indoor unit through the hole. • Do not…
-
6.4 Connecting the cable to indoor unit
The inside and outside connecting cable can be connected after opening the inlet grille. ¤ Open the inlet grille manually. ¤ŁOpen the control cover with Driver ( ) ¤ØConnect the wire to the housing on the control board. ¤ŒSecure the cable onto the control board with clamp. ¤ºSecure the control cover…
-
6.5 Connecting Pipings and the cable to Outdoor unit
1) Connecting the pipings to the outdoor unit . ¥LAlign the center of the pipings and sufficiently tighten the flare nut with fingers. ¥MFinally tighten the flare nut with torque wrench until the wrench clicks. Gas side piping • When tightening the flare nut with torque wrench, ensure the direction…
-
and thickness.)
6.6 Power Supply and Wiring The unit is completely wired internally at the factory according to general rule of electrical technology, but local rules, if they are required, should be complied with. 1) Power supply Power source must fulfill the following conditions: ¤ Never fail to equip a leakage…
-
6.7 Air Purging of the Piping and
Indoor Unit 1) Air purging The air which contains moisture and remains in the Refrigeration cycle may cause a malfunction on the compressor. Outdoor unit To indoor unit ¤ Remove the caps from the 3-way(liquid side) and 3-way(gas side) valves. Hexagonal wrench ¤Ł Remove the service-port cap from the…
-
¤ Set the both 3-way(liquid side) and 3-way(gas side) valves to open position with the hexagonal wrench for the unit operation. ¤ Checking the gas leakage for the left piping. • Connect the manifold gauge to the service port of 3-way(gas side) valve. Measure the pressure. • Keep it for 5 - 10…
-
6.8 Checking the Drainage and Form the Piping
1) Checking the Drainage ¤ Remove the inlet grille with your hands as shown (right and left) and pull in the direction indicated by the arrow. ¤ŁCheck the drainage • Pour a glass of water into the Drain pan. • Ensure if water flows drain hose of indoor unit. – 35 –
-
2) Form the Piping
¤ Wrap the connecting port of indoor unit with the insulation material and secure it with two Plastic Bands. (for the right Piping) Gas side piping • If you connect an additional drain hose, the end of the drain-outlet should be water, and fix it on the wall to avoid swinging in the wind.) Main…
-
6.9 Final Check and Test Run
After installing the unit, perform the final check and running test as follows: Running test should be accomplished as follows: ¤ Is the unit securely mounted? ¤Ł Next, set it at "COOL" and the compressor will start. Check to ensure that the compressor sounds normal. ¤ŁIs the installation location…
-
6.10 Installation Check List
1. Is the unit securely mounted and levelled? Space for Evaporator Air Flow Space for Condenser Air Flow Space for Maintenance Work Noise and Vibration Appearance 2. Is electrical wiring system adequate? Wire Size Tightened Connection Switch Size Operation Control Devices Fuse Size Safety Devices…
-
6.11 Running Test and Maintenance Record
JOB NUMBER: POWER SUPPLY : Main Power_______ V, Hz Indoor Unit Model ( V, Outdoor Unit Hz) ( V, Hz) Production No. Accessory Attached : CUSTOMER'S NAME AND ADDRESS : INSTALLED BY: START UP BY: (PHONE NO.: DATE: DATE: ❐ 1. Does the operation switch function properly? ❐ 2. Is the rotating direction of…
-
7. OPERATING
7.1 Display (Heat Pump Model) (Cooling only Model) ROOM TEMP. SET TEMP. ROOM TEMP. SET TEMP. A/CL A/CL L M A/CL A/CL H L M OUT DOOR OUT DOOR MODE H MODE ¤ START/STOP BUTTON Operation starts when this button is pressed and stops when the button is pressed again. ¤ HEATING OPERATION LAMP ¤ŁOPERATION…
-
7.2 Control
1 ¤ Signal Transmitter • Transmits the signals to the package air conditioner ¤Ł Operation Display of the Remote Control 2 10 ¤Ø Indoor Fan Speed Selection Button • To select the desired fan speed in three steps [Low, Med, High] 9 ¤Œ Cooling ON Button A/CL (Cooling Model) A/CL ¤º Temperature Setting…
-
7.3 Remote Control Preparation
1 How to mount onto a wall Use the screws to secure the holder to the wall or attach the holder side of indoor unit. 2 To insert the remote control to the holder. Insert Pull How to insert batteries 1 Remove the cover from the back of the remote controller. • Slide the cover according to the arrow…
-
8. 3-WAY VALVE
3-Way Valve (Liquid Side) Valve cap Open position Flare nut Closed position 3-Way Valve (Gas Side) Valve cap Open position Flare nut Closed position Pin To piping connection Service Service port cap port To outdoor unit Pin To piping connection Service Service port cap port To outdoor unit Works…
-
8.1 Air purging
Required tools: hexagonal wrench, adjustable wrench, torque wrench, and gas leak detector. The additional gas for air purging has been charged in the outdoor unit. However, if the flare connections have not been done correctly and there gas leaks, a gas cylinder and the charge set will be needed.…
-
8.2 Pumping down
Liquid side Indoor unit 3-Way valve Closed Outdoor unit Gas side Open 3-Way valve Lo CLOSE CLOSE Purge the air • Procedure ¤ Confirm that both 3-way(liquid side) and 3-way(gas side) valves are set to the open position. • Remove the valve stem caps and confirm that the valve stems are in the raised…
-
1) Re-air purging
(Re-installation) Indoor unit Liquid side 3-Way Closed valve Outdoor unit Gas side 3-Way valve Closed Gas cylinder R22 OPEN CLOSE • Procedure ¤ Confirm that both the 3-way (liquid side) valve and the 3-way(gas side) valve are set to the closed position. ¤ŁConnect the charge set and a gas cylinder to…
-
2) Balance refrigerant of the 3-way(liquid side), 3-way(gas side) valves
(Gas leakage) Indoor unit Liquid side Outdoor unit 3-Way valve Open 3-Way valve Open Gas side OPEN CLOSE • Procedure ¤ Confirm that both the liquid side and gas side valves are set to the back seat. ¤ŁConnect the charge set to the 3-way(gas side) valve's port. • Leave the valve on the charge set…
-
8.3 Evacuation
(All amount of refrigerant leaked) Liquid side Indoor unit Outdoor unit 3-Way valve Open 3-Way valve Open Gas side Vacuum pump Lo OPEN CLOSE • Procedure ¤ Connect the vacuum pump to the center hose of charge set. ¤ŁEvacuation for approximately one hour. - Confirm that the gauge needle has moved…
-
8.4 Gas Charging
1) Cooling mode (After Evacuation) Liquid side Indoor unit Open Outdoor unit 3-Way valve Gas side Open 3-Way valve Check valve Charging cylinder Lo (1) OPEN CLOSE • Procedure ¤ Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from the vacuum pump to…
-
2) Heating Mode
(After Evacuation) Charging cylinder Lo (1) OPEN CLOSE Check valve Indoor unit Liquid side Open 3-Way valve Outdoor unit Gas side Open 3-Way valve • Procedure ¤ Connect the charge hose to the charge cylinder. • Connect the charge hose which you disconnected from the vacuum pump to the valve at the…
-
9. TROUBLESHOOTING GUIDE
In general, possible trouble is classified as two causes. The one is so called Starting Failure which is caused from an electrical defect, and the other is Ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application. Unit runs but ineffective cooling…
-
Failures to Start
Check power source. Check of circuit breaker and fuse. Check control switch setting. Check control switch. Compressor only fails to start Fan only fails to start Electric heater is not energized Improper wiring Drop of power voltage Defect of compressor capacitor Loose terminal connection. Improper…
-
PACKAGE AIR CONDITIONER VOLTAGE LIMITS
NAME PLATE RATING MINIMUM MAXIMUM 380 V 342 V 418 V 220 V 198 V 242 V 380 - 415 V 342 V 456 V 9.1 No cooling and heating operation performed 1) Both the blower and the compressor do not work WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts than the unit Electric supply interrupted Defective…
-
3) Only outdoor fan does not work
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Motor Over-heated Layer short Check how it is insulated. Repair or replace it. Electric Wiring Open wire on operation Check it with a tester. Rewiring or repair. Short circuited operation on 4) Only compressor does not work WHAT TROUBLED COMPLAINTS HOW TO…
-
9.2 The Units discontinue after the operation started
WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Other parts than the unit Improper opening of the service valves in the refrigerant line Checking Open it properly Outdoor coil Coil is dirty *1 Checking Wash it by means of something like chemical washing. In-condensable gas blended. Air intruded into…
-
9.3 The unit is working, but not cooling and heating sufficiently
(Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much heat load Heat load increased. Window or door has many cracks or gaps. Do necessary disposal respectively. Air flow Obstacle disturbs Intake of uniform wind. Checking Correct it. Short air volume Reverse…
-
COMPLAINTS
HOW TO CHECK REMEDY Electric troubles (Magnetic contactor) Defective contact. Defective contact point. Rusting and faults in the iron core contact face. Defective contact of the operating switch. Checking Repair and clean or replace it. Others Improper installation Checking Correct it. 9.5 Trouble…
-
Fault
Internal Thermostat Cut-Off Overcurrent Relay for Compressor Cut-Off Overcurrent Relay for Fan Motor Cut-Off Cause Check/Correcitve Action Discharge pressure is lower than standard. See "Low Discharge Pressure". Single or three phases running. Check the power supply line and the contactor. High or…
-
9.6 Electronic Parts Troubleshooting Guide
1) No cooling operation performed. Is the AC220V (AC 240 V) between Connector(CNoutunit) Pin 1 and Pin 3 of Main P.C.B YES Is the input power AC220V (AC240V) at COMP Magnetic coil? NO NO NO YES Is the unit operating? Check the magnetic contactor of outdoor unit. YES ON/OFF S/W ON Is it Cooling mode?…
-
2-1) Indoor fan does not operate
-
3) Airflow Direction does not operate
Is the unit operating? NO The power ON/OFF S/W ON YES Is the Auto Swing S/W "ON"? NO Press the Auto Swing S/W YES Is the DC5V at 16 terminal? (MICOM) NO Replacement MICOM YES Is the DC12V at each terminal? (RY-Sync COIL) NO Replacement ICO2M YES Is the AC220V(240V) at each terminal (SYN. MOTOR…
-
4) Remote control does not operate
Is the battery of remote controller normal? NO Replacement battery YES Is the CN-Disp1 connector normal? NO Check the connector. CN-Disp1 YES Does the operation of remote controller properly? NO Replacement remote-controller YES Is the Pre-amp of display normal? NO Replacement preamp assy YES…
-
5) The unit does not operate
Is the AC220V (240V) at Trans input terminal? NO 1. Check the electric connections 2. Check the fuse of Main PCB ASM YES Is the AC12-18V at Trans (2nd)? NO Replacement Trans YES Is the connector of Main/Display correct? NO Check the connector of Main/Display YES Is the DC5V between PIN64 and PIN 32…
-
7) No heating operation works
-
8) No heater operation works
-
10. ELECTRONIC CONTROL DEVICE
-
11. SCHEMATIC DIAGRAM
11.1 Circuit and Troubleshooting – 68 –
-
11.2 Remote Controller
FUNCTION DATA CODE(HEX) FUNCTION DATA CODE(HEX) 9D 81 89 8F 8C 9F * CUSTOM CODE : 8656 (HEX) 1000011001010110(BINARY) – 69 –
-
12. EXPLODED VIEW AND REPLACEMENT PARTS LIST
12.1 Indoor Unit 1) Exploded View 40-1 20-1 20-1 – 70 – 55
-
2) Replacement Parts List
-
12.2 Outdoor Unit 1) Exploded View
-
2) Replacement Parts List
-
Printed in Korea
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.