Systemair SyScrew 300-1400 Air: 91 код
Инструкция, стр. 23 →| Код | Что означает |
|---|---|
| 10 | Main board - High pressure sys 2 sensor fault |
| 11 | Main board - Discharge temperature sys 1 sensor fault |
| 12 | Main board - Discharge temperature sys 2 sensor fault |
| 13 | Main board - Coil Temperature sys 1 sensor fault |
| 14 | Main board - Coil Temperature sys 2 sensor fault |
| 15 | Flow switch / Interlock / Serious alarm (SQZ) |
| 16 | Serious alarm (SQZ) |
| 17 | Flow switch / Interlock |
| 18 | Oil Safety Sys 1 manual reset |
| 19 | Oil Safety Sys 2 manual reset |
| 20 | High pressure switch Sys 1 |
| 21 | High pressure switch Sys 2 |
| 22 | Low pressure Sys 1 switch manual reset |
| 23 | Low pressure Sys 2 switch manual reset |
| 24 | Thermal protection compressor 1 Sys 1 manual reset |
| 27 | Thermal protection compressor 1 Sys 2 manual reset |
| 30 | Fan Thermal protection manual reset |
| 31 | Fan Thermal protection Group 1 Sys 1 manual reset |
| 32 | Fan Thermal protection Group 2 Sys 1 manual reset |
| 33 | Fan Thermal protection Group 1 Sys 2 manual reset |
| 34 | Fan Thermal protection Group 2 Sys 2 manual reset |
| 35 | Low refrigerant cutout Sys 1 manual reset |
| 36 | Low refrigerant cutout Sys 2 manual reset |
| 37 | Low pressure alarm Sys 1 manual reset |
| 38 | Low pressure alarm Sys 2 manual reset |
| 39 | Out of envelope Sys 1 manual reset |
| 40 | Out of envelope Sys 2 manual reset |
| 41 | High pressure Sys 1 manual reset |
| 42 | High pressure Sys 2 manual reset |
| 43 | High limit discharge temperature Sys1 manual reset |
| 44 | High limit discharge temperature Sys2 manual reset |
| 45 | ∆T Water Too High |
| 47 | Wrong Water Trend |
| 49 | Antifreeze alarm manual reset |
| 51 | Antifreeze alarm Recovery manual reset |
| 52 | Pump maintenance |
| 53 | Compressor 1 Sys 1 maintenance |
| 56 | Compressor 1 Sys 2 maintenance |
| 59 | Driver 1 LAN disconneted |
| 60 | Driver 2 LAN disconneted |
| 61 | EPROM Error Driver 1 |
| 62 | EPROM Error Driver 2 |
| 63 | Driver 1 S1 Sensor fault |
| 64 | Driver 1 S3 Sensor fault |
| 65 | Driver 1 S2 Sensor fault |
| 66 | Driver 1 S4 Sensor fault |
| 67 | Driver 2 S1 Sensor fault |
| 68 | Driver 2 S3 Sensor fault |
| 69 | EEV motor Error (Check viring) Sys 1 |
| 70 | EEV motor Error (Check viring) Sys 2 |
| 71 | Driver 1 Battery alarm |
| 72 | Driver 2 Battery alarm |
| 73 | Autotune alarm Sys 1 |
| 74 | Autotune alarm Sys 2 |
| 75 | Low suction alarm Sys 1 |
| 76 | Low suction alarm Sys 2 |
| 77 | Driver 1 Regulation Alarm |
| 78 | Driver 2 Regulation Alarm |
| 79 | Expansion board 1 OFF LINE |
| 80 | Expansion board 2 OFF LINE |
| 81 | Expansion board 1 - Sensor 1 fault |
| 82 | Expansion board 1 - Sensor 2 fault |
| 83 | Expansion board 1 - Sensor 3 fault |
| 84 | Expansion board 1 - Sensor 4 fault |
| 85 | Safety Extra Heater |
| 86 | Recovery Flow switch |
| 87 | Low delta pressure Sys 1 manual reset |
| 88 | Low delta pressure Sys 2 manual reset |
| 118 | Oil Safety Sys 1 auto reset |
| 119 | Oil Safety Sys 2 manual reset |
| 122 | Low pressure Sys 1 switch auto reset |
| 123 | Low pressure Sys 2 switch auto reset |
| 124 | Thermal protection compressor 1 Sys 1 auto reset |
| 127 | Thermal protection compressor 1 Sys 2 auto reset |
| 130 | Fan Thermal protection auto reset |
| 131 | Fan Thermal protection Group 1 Sys 1 auto reset |
| 132 | Fan Thermal protection Group 2 Sys 1 auto reset |
| 133 | Fan Thermal protection Group 1 Sys 2 auto reset |
| 134 | Fan Thermal protection Group 2 Sys 2 auto reset |
| 135 | Low refrigerant cutout Sys 1 auto reset |
| 136 | Low refrigerant cutout Sys 2 auto reset |
| 137 | Low pressure alarm Sys 1 auto reset |
| 138 | Low pressure alarm Sys 2 auto reset |
| 139 | Out of envelope Sys 1 auto reset |
| 140 | Out of envelope Sys 2 auto reset |
| 141 | High pressure Sys 1 auto reset |
| 142 | High pressure Sys 2 auto reset |
| 143 | High limit discharge temperature Sys1 auto reset |
| 144 | High limit discharge temperature Sys2 auto reset |
| 187 | Low delta pressure Sys 1 auto reset |
| 188 | Low delta pressure Sys 2 auto reset |
Источник: «Водяные чиллеры с воздушным охлаждением Systemair серии SyScrew 300-1400 Air», стр. 23. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.