Ошибки кондиционеров Lennox: коды и расшифровка
Расшифровка кодов на дисплее кондиционеров Lennox и что делать — по инструкциям производителя. Один и тот же код в разных сериях может означать разное: найдите свою серию.
Серии Lennox
Lennox BALTIC: 104 кода
Инструкция, стр. 117 →| Код | Что означает | Что делать |
|---|---|---|
| 001 | "Airflow" | |
| 004 | Filters, Clogged up | |
| 005 | Filters, Missing | |
| 006 | Recovery Module, Filters, Clogged up | |
| 11 | Electrical Heater | Faulty |
| 011 | Electric heating elements | |
| 12 | Outlet or Supply T. | Over Temp. |
| 012 | High Temperature, Blowing | |
| 13 | Inlet or Room T. | Temp. Too Low |
| 013 | Low Temperature, Ambient | |
| 14 | Gas Burner, 1 | Faulty |
| 014 | Gas burner, 1 | |
| 15 | Gas Burner, 2 | Faulty |
| 015 | Gas burner, 2 | |
| 22 | Outlet or Supply T. | Temp. To Below |
| 022 | Low Temperature, Blowing | |
| 23 | Inlet or Room T. | Temp. Too High |
| 023 | High Temperature, Ambient | |
| 31 | Humidifier | Faulty |
| 031 | Humidifier | |
| 32 | Room Humidity | Humidity Too Low |
| 032 | Low Humidity, Ambient | |
| 33 | Room Humidity | Humidity Too High |
| 033 | High Humidity, Ambient | |
| 40 | Flow, Pump | Failure |
| 41 | Pump, 1 | Faulty |
| 041 | Pump | |
| 42 | Pump, 2 | Faulty |
| 051 | Recovery Module, Motor failure | |
| 052 | Recovery Module, Wheel failure | |
| 70 | Real Time Clock | Faulty |
| 070 | Clock card | |
| 80 | Remote S.Point | Faulty |
| 81 | Inlet or Room T. | Faulty Sensor |
| 081 | Temperature sensor, Ambient | |
| 82 | Room Humidity | Faulty Sensor |
| 082 | Humidity sensor, Ambient | |
| 83 | Outside Temperature | Faulty Sensor |
| 083 | Temperature probe, Outside | |
| 84 | Outside Humidity | Faulty Sensor |
| 084 | Humidity sensor, Outside | |
| 85 | Outlet or Supply T. | Faulty Sensor |
| 085 | Temperature probe, Blower | |
| 86 | Inlet, Recovery | Faulty Sensor |
| 086 | Circuit 1, Temperature sensor, Water condenser Outlet | |
| 87 | Outlet, Recovery | Faulty Sensor |
| 087 | Circuit 2, Temperature sensor, Water condenser Outlet | |
| 88 | Return or Mixing T. | Faulty Sensor |
| 088 | Temperature sensor, return or Mixing air | |
| 90 | Air, Condenser | Faulty |
| 91 | Blower, Fan | Faulty |
| 091 | Blower | |
| 92 | Air, Condenser | Faulty, System 1 |
| 092 | Circuit 1, Condenser fan | |
| 93 | Air, Condenser | Faulty, System 2 |
| 093 | Circuit 2, Condenser fan | |
| 94 | Air, Condenser | Faulty, System 3 |
| 094 | Circuit 3, Condenser fan | |
| 95 | Air, Condenser | Faulty, System 4 |
| 095 | Circuit 4, Condenser fan | |
| 96 | Water, Condenser | Temp. To Below |
| 096 | Low temperature, Water Condenser | |
| 97 | Water, Condenser | Temp. Too High |
| 097 | High temperature, Water Condenser | |
| 98 | Water, Condenser | Faulty, Flow |
| 098 | Flow rate, water condenser | |
| 99 | Fire / Smoke | Faulty |
| 099 | Smoke detector | |
| 111 | Condenser | Faulty Sensor, 1 |
| 112 | Suction | Faulty Sensor, 1 |
| 114 | Circuit 1 | Elec. power |
| 115 | Circuit 1 | Cut High Pressure |
| 117 | Circuit 1 | Cut Low Pressure |
| 118 | Circuit 1 | Risk of Frosting |
| 121 | Condenser | Faulty Sensor, 2 |
| 122 | Suction | Faulty Sensor, 2 |
| 124 | Circuit 2 | Elec. power |
| 125 | Circuit 2 | Cut High Pressure |
| 127 | Circuit 2 | Cut Low Pressure |
| 128 | Circuit 2 | Risk of Frosting |
| 131 | Condenser | Faulty Sensor, 3 |
| 134 | Circuit 3 | Elec. power |
| 135 | Circuit 3 | Cut High Pressure |
| 137 | Circuit 3 | Cut Low Pressure |
| 141 | Condenser | Faulty Sensor, 4 |
| 144 | Circuit 4 | Elec. power |
| 145 | Circuit 4 | Cut High Pressure |
| 147 | Circuit 4 | Cut Low Pressure |
| 210 | P.Lan | EEV 1, Error |
| 211 | Low Superheat | EEV 1, Error |
| 212 | High Suction T. | EEV 1, Error |
| 215 | Valve Not Closed | EEV 1, Error |
| 216 | Probe | EEV 1, Error |
| 217 | Motor | EEV 1, Error |
| 218 | EEPROM | EEV 1, Error |
| 219 | Battery | EEV 1, Error |
| 220 | P.Lan | EEV 2, Error |
| 221 | Low Superheat | EEV 2, Error |
| 222 | High Suction T. | EEV 2, Error |
| 225 | Valve Not Closed | EEV 2, Error |
| 226 | Probe | EEV 2, Error |
| 227 | Motor | EEV 2, Error |
| 228 | EEPROM | EEV 2, Error |
| 229 | Battery | EEV 2, Error |
Источник: «Rooftops (крышные кондиционеры) Lennox серии BALTIC», стр. 117. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
Lennox FLEXY: 161 код
Инструкция, стр. 41 →| Код | Что означает |
|---|---|
| 000 | No fault |
| 001 | Failure air flow |
| 004 | Dirty filters |
| 005 | Missing filters |
| 10 | Temperature, compressor, no. 4 |
| 11 | Temperature, condenser, no. 1 |
| 011 | If the CLIMATIC™ gives the order to the heater to operate and if 5 seconds later the auxiliary contact is still open, the heat safety system is activated and stops the electrical heater assembly. This safety system is automatically locked-out. In this case a manual reset is obligatory. Note: This fault is also displayed in the event of a contact "shunt". Faulty Gas Burners |
| 12 | Temperature, condenser, no. 2 |
| 012 | Supply air overtemperature |
| 13 | Temperature, condenser, no. 3 |
| 013 | If the room temperature is less than or equal to the setpoint [C39], the safety system is activate Faulty Electrical Heater Batteries The electrical heater battery safety thermostats act directly on the heater stage contactors. This information is fed to the CLIMATIC™ via auxiliary contacts. |
| 14 | Temperature, condenser, no. 4 |
| 014 | If there is a fault with the gas control boxes the heat safety system is activated and stops the respective burner. |
| 15 | Temperature, air/water cooled heat exchanger, water outlet |
| 015 | This safety system automatically cuts out on the CLIMATIC™ and the control unit must be manually reset. |
| 16 | Pressure, air flow (mb) |
| 17 | Air quality sensor, CO² (ppm) |
| 18 | Pressure, compressor, no. 1 |
| 19 | Pressure, compressor, no. 2 |
| 20 | Pressure, compressor, no. 3 |
| 21 | Pressure, compressor, no. 4 |
| 22 | Volt free contact, remote control, unit Off |
| 022 | Supply temperature too low |
| 23 | Volt free contact, remote control, forced occupied mode |
| 023 | If the room temperature is greater than or equal to the setpoint [C40], the safety system is activated. It automatically cuts out at a temperature lower than 3°C below this setpoint. Lower Room Air Limit |
| 24 | Volt free contact, remote control, forced unoccupied mode |
| 25 | Volt free contact, remote control, 50% load limit |
| 26 | Volt free contact, remote control, heating disable |
| 27 | Volt free contact, remote control, cooling disable |
| 28 | Volt free contact, remote control,low ventilation speed |
| 29 | Auxiliary contact, blower fan |
| 30 | Volt free contact, error, DAD board, detected smoke |
| 031 | Faulty Humidifier (Flexy Only) If there is a fault with the gas control unit for more than a minute, the safety system is activated and stops the humidifier. |
| 31 | Auxiliary contact, compressor, no. 1 |
| 032 | This safety system is automatically locked-out. In this case a manual reset is obligatory. Room Humidity Safety System Lower Room Limit If the room humidity is less than or equal to the setpoint [C41] or [C42], the safety system is activated. It automatically cuts out at a humidity of 3% above this setpoint. Upper Room Limit |
| 32 | Auxiliary contact, compressor, no. 2 |
| 033 | If the room humidity is greater than or equal to the setpoint [C43] or [C44], the safety system is activated. It automatically cuts out at a humidity of 3% below this setpoint. Faulty Pump The internal protection of the water pump motor acts directly on the pump contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact of the contactor. |
| 33 | Auxiliary contact, compressor, no. 3 |
| 34 | Auxiliary contact, compressor, no. 4 |
| 35 | Pressure switch, compressor, no. 1, low pressure |
| 36 | Pressure switch, compressor, no. 2, low pressure |
| 37 | Pressure switch, compressor, no. 3, low pressure |
| 38 | Pressure switch, compressor, no. 4, low pressure |
| 39 | Auxiliary contact, condenser fan, no. 1 |
| 40 | Auxiliary contact, condenser fan, no. 2 |
| 041 | If the CLIMATIC™ gives the pump the order to operate and if 5 seconds later the auxiliary contact remains open, the safety system is activated and stops the pump. The safety system is immediately automatically locked out. In this case, manual resetting is obligatory. Note: This error is also displayed in the event of a "shunt" of the auxiliary contact of the contactor. |
| 41 | Auxiliary contact, condenser fan, no. 3 |
| 42 | Auxiliary contact, condenser fan, no. 4 |
| 43 | Volt free contact, air/water cooled heat exchanger, water flow regulator |
| 44 | Auxiliary contact, pump (hot water coil - frost protection pump) |
| 45 | Auxiliary contact, electrical heater, no. 1 |
| 46 | Auxiliary contact, electrical heater, no. 2 |
| 47 | Auxiliary contact, gas grade, no. 1 |
| 48 | Auxiliary contact, gas grade, no. 2 |
| 49 | Volt free contact, humidifier, error, control & setting board |
| 50 | Volt free contact, leak water |
| 51 | Volt free contact, information, miscellaneous source |
| 52 | Output, supply fan |
| 081 | Room temperature sensor missing or faulty. Room relative humidity sensor missing or faulty Outside air temperature sensor faulty |
| 82 | Battery Temperature, setpoint, Authorised defrosting |
| 082 | Faulty return air or room relative humidity sensor |
| 83 | Coefficient, Icing time |
| 083 | Faulty outside temperature sensor |
| 84 | Number, Condensor restart |
| 084 | Outside relative humidity sensor faulty |
| 85 | Low Temperature, setpoint, GOLD heat exchanger |
| 085 | Supply Air temperature sensor faulty |
| 86 | High Temperature, setpoint, GOLD heat exchanger |
| 086 | Temperature sensor on cold water loop faulty |
| 87 | Outside Temperature, setpoint, 100% Elec. res. discharge |
| 087 | Temperature sensor on condenser water outlet faulty. |
| 88 | Sensing setpoint, Air flow cutout |
| 088 | Faulty mixing air temperature sensor |
| 89 | Sensing setpoint, Clogged filters |
| 089 | The inter card link is faulty or missing. |
| 90 | Sensing setpoint, Missing filters |
| 91 | Unit type |
| 091 | Faulty blower fan |
| 92 | On = ‘L’ Series, Off = ‘F’ Series |
| 092 | Faulty condenser: system 1 |
| 93 | On = Advanced Control Pack Option Fitted |
| 093 | Faulty condenser: system 2 |
| 94 | All setpoint values forced to factory values |
| 094 | Faulty condenser: system 3 |
| 95 | Test stages |
| 095 | Faulty condenser: system 4 |
| 096 | Condenser water temperature too low |
| 097 | Condenser water overtemperature |
| 098 | Faulty condenser water flow |
| 099 | Error: smoke |
| 111 | Faulty condenser temperature sensor, compressor no. 1 |
| 112 | Faulty pressure transmitter, compressor no. 1 |
| 113 | Faulty frost power temperature sensor no. 1 |
| 115 | - The high pressure pressostat is open. |
| 117 | Faulty low pressure compressor no. 1 |
| 121 | Faulty condenser temperature sensor Faulty pressure transmitter sensor, refrigeration system |
| 122 | Faulty pressure transmitter, compressor no. 2 |
| 123 | Faulty refrigeration system, frost temperature sensor High pressure switch safety or compressor electrical safety The compressor contactor is not connected although the CLIMATIC™ requests it. |
| 125 | - The internal protection of the compressor motor is open. The high pressure pressostat and the compressor motor thermal protection act directly on the compressor contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact of the contactor. |
| 127 | Faulty low pressure compressor If the low pressure pressostat is open and the compressor has been operating for more than 2 minutes, the low pressure safety system is activated and stops the compressor. This safety system is not taken into account during the defrost cycle for the heat pump units. |
| 131 | Faulty condenser temperature sensor, compressor no. 3 |
| 132 | Faulty pressure transmitter, compressor no. 3 |
| 133 | Faulty frost temperature sensor no. 3 |
| 135 | If the CLIMATIC™ gives the order to operate to the compressor and if the auxiliary contact is still open 5 seconds later, the fan safety system is activated and stops the compressor.The safety system automatically cuts out after 4 minutes. |
| 137 | The compressor is engaged when the pressostat contact closes. It is also automatically locked out after 3 failures within a day. In this case, manual resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3 failures. |
| 141 | Faulty condenser temperature sensor, compressor no. 4 |
| 142 | Faulty pressure transmitter, compressor no. 4 |
| 143 | Faulty frost temperature sensor no. 4 |
| 145 | It is also automatically locked out after 3 failures within a day. In this case, manual resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3 failures. |
| 147 | Faulty low pressure compressor no. 4 |
| V000 | [Defects] error codes |
| V001 | [Value] Temperature (in °c), Room, Reference value |
| V002 | [Value] Relative humidity (in %), Room, Reference value |
| V003 | [Value] Absolute humidity (in g/kg), Room, Reference value |
| V004 | [Value] Temperature (in °c), Outdoor, Reference value |
| V005 | [Value] Relative humidity (in %), Outdoor, Reference value |
| V006 | [Value] Absolute humidity (in g/kg), Outdoor, Reference value |
| V007 | [Input] Temperature (in °c), Supply |
| V008 | [Input] Temperature (in °c), Mixing |
| V009 | [Input] Temperature (in °c), Free |
| V010 | [Input] Temperature (in °c), Chilled water |
| V011 | [Input] Temperature (in °c), Compressor, n°1 |
| V012 | [Input] Temperature (in °c), Compressor, n°2 |
| V013 | [Input] Temperature (in °c), Compressor, n°3 |
| V014 | [Input] Temperature (in °c), Compressor, n°4 |
| V015 | [Input] Temperature (in °c), Condenser, n°1 |
| V016 | [Input] Temperature (in °c), Condenser, n°2 |
| V017 | [Input] Temperature (in °c), Condenser, n°3 |
| V018 | [Input] Temperature (in °c), Condenser, n°4 |
| V019 | [Input] Temperature (in °c), Water condenser, Output exchanger |
| V020 | [Input] Signal, Shift of the set point |
| V021 | [Input] Pressure (in pa), Air flow, Supply fan |
| V022 | [Input] Signal (in ppm), Air quality sensor, Co² |
| V023 | [Input] Pressure (in b), Compressor, n°1 |
| V024 | [Input] Pressure (in b), Compressor, n°2 |
| V025 | [Input] Pressure (in b), Compressor, n°3 |
| V026 | [Input] Pressure (in b), Compressor, n°4 |
| V027 | [Output] Supply fan |
| V028 | [Output] Supply fan, Command low speed |
| V029 | [Output] Extraction fan |
| V030 | [Output] Compressor, n°1 |
| V031 | [Output] Compressor, n°2 |
| V032 | [Output] Compressor, n°3 |
| V033 | [Output] Compressor, n°4 |
| V034 | [Output] Compressor, Cycle reversing valve, Heat pump, n°1 |
| V035 | [Output] Compressor, Cycle reversing valve, Heat pump, n°2 |
| V036 | [Output] Compressor, Cycle reversing valve, Heat pump, n°3 |
| V037 | [Output] Compressor, Cycle reversing valve, Heat pump, n°4 |
| V038 | [Output] Compressor, Hot gas injection valve |
| V039 | [Output] Condenser fan, Command low speed |
| V040 | [Output] Condenser fan, n°1 |
| V041 | [Output] Condenser fan, n°2 |
| V042 | [Output] Condenser fan, n°3 |
| V043 | [Output] Condenser fan, n°4 |
| V044 | [Output] Pump |
| V045 | [Output] Electrical heater, n°1, 1st level |
| V046 | [Output] Electrical heater, n°1, 2nd level |
| V047 | [Output] Electrical heater, n°2 |
| V048 | [Output] Gas grade, n°1, 1st level |
| V049 | [Output] Gas grade, n°1, 2nd level |
| V050 | [Output] Gas grade, n°2 |
Источник: «Rooftops (крышные кондиционеры) Lennox серии FLEXY», стр. 41. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
Lennox FLEXY, FLEXY II: 147 кодов
Инструкция, стр. 46 →| Код | Что означает |
|---|---|
| 000 | No fault |
| 001 | Failure air flow |
| 004 | Dirty filters |
| 005 | Missing filters |
| 10 | Temperature, compressor, no. 4 |
| 11 | Temperature, condenser, no. 1 |
| 011 | If the CLIMATIC™ gives the order to the heater to operate and if 5 seconds later the auxiliary contact is still open, the heat safety system is activated and stops the electrical heater assembly. This safety system is automatically locked-out. In this case a manual reset is obligatory. Note: This fault is also displayed in the event of a contact "shunt". Faulty Gas Burners |
| 12 | Temperature, condenser, no. 2 |
| 012 | Supply air overtemperature |
| 13 | Temperature, condenser, no. 3 |
| 013 | If the room temperature is less than or equal to the setpoint [C39], the safety system is activate Faulty Electrical Heater Batteries The electrical heater battery safety thermostats act directly on the heater stage contactors. This information is fed to the CLIMATIC™ via auxiliary contacts. |
| 14 | Temperature, condenser, no. 4 |
| 014 | If there is a fault with the gas control boxes the heat safety system is activated and stops the respective burner. |
| 15 | Temperature, air/water cooled heat exchanger, water outlet |
| 015 | This safety system automatically cuts out on the CLIMATIC™ and the control unit must be manually reset. |
| 16 | Pressure, air flow (mb) |
| 17 | Air quality sensor, CO² (ppm) |
| 18 | Pressure, compressor, no. 1 |
| 19 | Pressure, compressor, no. 2 |
| 20 | Pressure, compressor, no. 3 |
| 21 | Pressure, compressor, no. 4 |
| 22 | Volt free contact, remote control, unit Off |
| 022 | Supply temperature too low |
| 23 | Volt free contact, remote control, forced occupied mode |
| 023 | If the room temperature is greater than or equal to the setpoint [C40], the safety system is activated. It automatically cuts out at a temperature lower than 3°C below this setpoint. Lower Room Air Limit |
| 24 | Volt free contact, remote control, forced unoccupied mode |
| 25 | Volt free contact, remote control, 50% load limit |
| 26 | Volt free contact, remote control, heating disable |
| 27 | Volt free contact, remote control, cooling disable |
| 28 | Volt free contact, remote control,low ventilation speed |
| 29 | Auxiliary contact, blower fan |
| 30 | Volt free contact, error, DAD board, detected smoke |
| 31 | Auxiliary contact, compressor, no. 1 |
| 031 | Faulty Humidifier (Flexy Only) If there is a fault with the gas control unit for more than a minute, the safety system is activated and stops the humidifier. |
| 32 | Auxiliary contact, compressor, no. 2 |
| 032 | This safety system is automatically locked-out. In this case a manual reset is obligatory. Room Humidity Safety System Lower Room Limit If the room humidity is less than or equal to the setpoint [C41] or [C42], the safety system is activated. It automatically cuts out at a humidity of 3% above this setpoint. Upper Room Limit |
| 33 | Auxiliary contact, compressor, no. 3 |
| 033 | If the room humidity is greater than or equal to the setpoint [C43] or [C44], the safety system is activated. It automatically cuts out at a humidity of 3% below this setpoint. Faulty Pump The internal protection of the water pump motor acts directly on the pump contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact of the contactor. |
| 34 | Auxiliary contact, compressor, no. 4 |
| 35 | Pressure switch, compressor, no. 1, low pressure |
| 36 | Pressure switch, compressor, no. 2, low pressure |
| 37 | Pressure switch, compressor, no. 3, low pressure |
| 38 | Pressure switch, compressor, no. 4, low pressure |
| 39 | Auxiliary contact, condenser fan, no. 1 |
| 40 | Auxiliary contact, condenser fan, no. 2 |
| 41 | Auxiliary contact, condenser fan, no. 3 |
| 041 | If the CLIMATIC™ gives the pump the order to operate and if 5 seconds later the auxiliary contact remains open, the safety system is activated and stops the pump. The safety system is immediately automatically locked out. In this case, manual resetting is obligatory. Note: This error is also displayed in the event of a "shunt" of the auxiliary contact of the contactor. |
| 42 | Auxiliary contact, condenser fan, no. 4 |
| 43 | Volt free contact, air/water cooled heat exchanger, water flow regulator |
| 44 | Auxiliary contact, pump (hot water coil - frost protection pump) |
| 45 | Auxiliary contact, electrical heater, no. 1 |
| 46 | Auxiliary contact, electrical heater, no. 2 |
| 47 | Auxiliary contact, gas grade, no. 1 |
| 48 | Auxiliary contact, gas grade, no. 2 |
| 49 | Volt free contact, humidifier, error, control & setting board |
| 50 | Volt free contact, leak water |
| 51 | Volt free contact, information, miscellaneous source |
| 52 | Output, supply fan |
| 081 | Room temperature sensor missing or faulty. Room relative humidity sensor missing or faulty Outside air temperature sensor faulty |
| 082 | Faulty return air or room relative humidity sensor |
| 083 | Faulty outside temperature sensor |
| 084 | Outside relative humidity sensor faulty |
| 085 | Supply Air temperature sensor faulty |
| 086 | Temperature sensor on cold water loop faulty |
| 087 | Temperature sensor on condenser water outlet faulty. |
| 088 | Faulty mixing air temperature sensor |
| 089 | The inter card link is faulty or missing. |
| 091 | Faulty blower fan |
| 092 | Faulty condenser: system 1 |
| 093 | Faulty condenser: system 2 |
| 094 | Faulty condenser: system 3 |
| 095 | Faulty condenser: system 4 |
| 096 | Condenser water temperature too low |
| 097 | Condenser water overtemperature |
| 098 | Faulty condenser water flow |
| 099 | Error: smoke |
| 111 | Faulty condenser temperature sensor, compressor no. 1 |
| 112 | Faulty pressure transmitter, compressor no. 1 |
| 113 | Faulty frost power temperature sensor no. 1 |
| 115 | - The high pressure pressostat is open. |
| 117 | Faulty low pressure compressor no. 1 |
| 121 | Faulty condenser temperature sensor Faulty pressure transmitter sensor, refrigeration system |
| 122 | Faulty pressure transmitter, compressor no. 2 |
| 123 | Faulty refrigeration system, frost temperature sensor High pressure switch safety or compressor electrical safety The compressor contactor is not connected although the CLIMATIC™ requests it. |
| 125 | - The internal protection of the compressor motor is open. The high pressure pressostat and the compressor motor thermal protection act directly on the compressor contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact of the contactor. |
| 127 | Faulty low pressure compressor If the low pressure pressostat is open and the compressor has been operating for more than 2 minutes, the low pressure safety system is activated and stops the compressor. This safety system is not taken into account during the defrost cycle for the heat pump units. |
| 131 | Faulty condenser temperature sensor, compressor no. 3 |
| 132 | Faulty pressure transmitter, compressor no. 3 |
| 133 | Faulty frost temperature sensor no. 3 |
| 135 | If the CLIMATIC™ gives the order to operate to the compressor and if the auxiliary contact is still open 5 seconds later, the fan safety system is activated and stops the compressor.The safety system automatically cuts out after 4 minutes. |
| 137 | The compressor is engaged when the pressostat contact closes. It is also automatically locked out after 3 failures within a day. In this case, manual resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3 failures. |
| 141 | Faulty condenser temperature sensor, compressor no. 4 |
| 142 | Faulty pressure transmitter, compressor no. 4 |
| 143 | Faulty frost temperature sensor no. 4 |
| 145 | It is also automatically locked out after 3 failures within a day. In this case, manual resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value does not exceed 3 failures. |
| 147 | Faulty low pressure compressor no. 4 |
| V000 | [Defects] error codes |
| V001 | [Value] Temperature (in °c), Room, Reference value |
| V002 | [Value] Relative humidity (in %), Room, Reference value |
| V003 | [Value] Absolute humidity (in g/kg), Room, Reference value |
| V004 | [Value] Temperature (in °c), Outdoor, Reference value |
| V005 | [Value] Relative humidity (in %), Outdoor, Reference value |
| V006 | [Value] Absolute humidity (in g/kg), Outdoor, Reference value |
| V007 | [Input] Temperature (in °c), Supply |
| V008 | [Input] Temperature (in °c), Mixing |
| V009 | [Input] Temperature (in °c), Free |
| V010 | [Input] Temperature (in °c), Chilled water |
| V011 | [Input] Temperature (in °c), Compressor, n°1 |
| V012 | [Input] Temperature (in °c), Compressor, n°2 |
| V013 | [Input] Temperature (in °c), Compressor, n°3 |
| V014 | [Input] Temperature (in °c), Compressor, n°4 |
| V015 | [Input] Temperature (in °c), Condenser, n°1 |
| V016 | [Input] Temperature (in °c), Condenser, n°2 |
| V017 | [Input] Temperature (in °c), Condenser, n°3 |
| V018 | [Input] Temperature (in °c), Condenser, n°4 |
| V019 | [Input] Temperature (in °c), Water condenser, Output exchanger |
| V020 | [Input] Signal, Shift of the set point |
| V021 | [Input] Pressure (in pa), Air flow, Supply fan |
| V022 | [Input] Signal (in ppm), Air quality sensor, Co² |
| V023 | [Input] Pressure (in b), Compressor, n°1 |
| V024 | [Input] Pressure (in b), Compressor, n°2 |
| V025 | [Input] Pressure (in b), Compressor, n°3 |
| V026 | [Input] Pressure (in b), Compressor, n°4 |
| V027 | [Output] Supply fan |
| V028 | [Output] Supply fan, Command low speed |
| V029 | [Output] Extraction fan |
| V030 | [Output] Compressor, n°1 |
| V031 | [Output] Compressor, n°2 |
| V032 | [Output] Compressor, n°3 |
| V033 | [Output] Compressor, n°4 |
| V034 | [Output] Compressor, Cycle reversing valve, Heat pump, n°1 |
| V035 | [Output] Compressor, Cycle reversing valve, Heat pump, n°2 |
| V036 | [Output] Compressor, Cycle reversing valve, Heat pump, n°3 |
| V037 | [Output] Compressor, Cycle reversing valve, Heat pump, n°4 |
| V038 | [Output] Compressor, Hot gas injection valve |
| V039 | [Output] Condenser fan, Command low speed |
| V040 | [Output] Condenser fan, n°1 |
| V041 | [Output] Condenser fan, n°2 |
| V042 | [Output] Condenser fan, n°3 |
| V043 | [Output] Condenser fan, n°4 |
| V044 | [Output] Pump |
| V045 | [Output] Electrical heater, n°1, 1st level |
| V046 | [Output] Electrical heater, n°1, 2nd level |
| V047 | [Output] Electrical heater, n°2 |
| V048 | [Output] Gas grade, n°1, 1st level |
| V049 | [Output] Gas grade, n°1, 2nd level |
| V050 | [Output] Gas grade, n°2 |
Источник: «Rooftops (крышные кондиционеры) Lennox серии FLEXY, FLEXY II », стр. 46. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.
Lennox SMART LINEА: 95 кодов
Инструкция, стр. 76 →| Код | Что означает |
|---|---|
| 000 | No error Communication error |
| 001 | The air flow safety system automatically stops after 1 minute 30 seconds and is automatically locked out after 3 cut-outs in the same day. In this case a manual reset is obligatory. The cut-out counter is reset to zero every evening at 20:00 if the value does not exceed 3 failures. |
| 004 | Dirty Filters If the pressure differential obtained by the analog sensor [V16] is greater than the setpoint value [C94] for more than one minute, the CLIMATIC indicates that the filters are dirty. The unit is not stopped. |
| 005 | Missing Filters If the pressure differential obtained by the analog sensor [V16] is less than the setpoint value [C90] for more than one minute, the CLIMATIC indicates that the filters are missing. |
| 10 | Temperature, compressor, no. 4 |
| 11 | Temperature, condenser, no. 1 |
| 011 | If the CLIMATIC gives the order to the heater to operate and if 5 seconds later the auxiliary contact is still open, the heat safety system is activated and stops the electrical heater assembly. This safety system is automatically locked-out. In this case a manual reset is obligatory. Note: This fault is also displayed in the event of a contact "shunt". |
| 12 | Temperature, condenser, no. 2 |
| 012 | Supply air overtemperature |
| 13 | Temperature, condenser, no. 3 |
| 013 | If the room temperature is less than or equal to the setpoint [C40], the safety system is activate Faulty Electrical Heater Batteries The electrical heater battery safety thermostats act directly on the heater stage contactors. This information is fed to the CLIMATIC via auxiliary contacts. |
| 14 | Temperature, condenser, no. 4 |
| 014 | Faulty Gas Burners If there is a fault with the gas control boxes the heat safety system is activated and stops the respective burner. |
| 15 | Temperature, air/water cooled heat exchanger, water outlet |
| 015 | This safety system automatically cuts out on the CLIMATIC and the control unit must be manually reset. Faulty Pump The internal protection of the water pump motor acts directly on the pump contactor. This information is transmitted to the CLIMATIC™ via an auxiliary contact of the contactor. |
| 16 | Pressure, air flow (mb) |
| 17 | Air quality sensor, CO² (ppm) |
| 18 | Pressure, compressor, no. 1 |
| 19 | Pressure, compressor, no. 2 |
| 20 | Pressure, compressor, no. 3 |
| 21 | Pressure, compressor, no. 4 |
| 22 | Volt free contact, remote control, unit Off |
| 022 | Supply temperature too low |
| 23 | Volt free contact, remote control, forced occupied mode |
| 023 | Upper Room Air Limit If the room temperature is greater than or equal to the setpoint [C41], the safety system is activated. It automatically cuts out at a temperature lower than 3°C below this setpoint. Lower Room Air Limit |
| 24 | Volt free contact, remote control, forced unoccupied mode |
| 25 | Volt free contact, remote control, 50% load limit |
| 26 | Volt free contact, remote control, heating disable |
| 27 | Volt free contact, remote control, cooling disable |
| 28 | Volt free contact, remote control,low ventilation speed |
| 29 | Auxiliary contact, blower fan |
| 30 | Volt free contact, error, DAD board, detected smoke |
| 31 | Auxiliary contact, compressor, no. 1 |
| 031 | Faulty humidifier |
| 32 | Auxiliary contact, compressor, no. 2 |
| 032 | Room humidity too low |
| 33 | Auxiliary contact, compressor, no. 3 |
| 033 | Room overtemperature |
| 34 | Auxiliary contact, compressor, no. 4 |
| 35 | Pressure switch, compressor, no. 1, low pressure |
| 36 | Pressure switch, compressor, no. 2, low pressure |
| 37 | Pressure switch, compressor, no. 3, low pressure |
| 38 | Pressure switch, compressor, no. 4, low pressure |
| 39 | Auxiliary contact, condenser fan, no. 1 |
| 40 | Auxiliary contact, condenser fan, no. 2 |
| 41 | Auxiliary contact, condenser fan, no. 3 |
| 041 | If the CLIMATIC gives the pump the order to operate and if 5 seconds later the auxiliary contact remains open, the safety system is activated and stops the pump. The safety system is immediately automatically locked out. In this case, manual resetting is obligatory. Note: This error is also displayed in the event of a "shunt" of the auxiliary contact of the contactor. |
| 42 | Auxiliary contact, condenser fan, no. 4 |
| 43 | Volt free contact, air/water cooled heat exchanger, water flow regulator |
| 44 | Auxiliary contact, pump (hot water coil - frost protection pump) |
| 45 | Auxiliary contact, electrical heater, no. 1 |
| 46 | Auxiliary contact, electrical heater, no. 2 |
| 47 | Auxiliary contact, gas grade, no. 1 |
| 48 | Auxiliary contact, gas grade, no. 2 |
| 49 | Volt free contact, humidifier, error, control & setting board |
| 50 | Volt free contact, leak water |
| 51 | Volt free contact, information, miscellaneous source |
| 52 | Output, supply fan |
| 53 | Output, low speed supply fan |
| 081 | Room temperature sensor missing or faulty. |
| 082 | Room relative humidity sensor missing or faulty |
| 083 | Outside air temperature sensor faulty |
| 084 | Outside relative humidity sensor faulty |
| 085 | Supply Air temperature sensor faulty |
| 086 | Temperature sensor on cold water loop faulty |
| 087 | Temperature sensor on condenser water outlet faulty. NOTE: Missing or faulty room, supply air or outside air temperature sensors can affect the overall control system. A safety device will be activated and all equipment except for the ventilation will cut out. Failure of the other sensors will only stop the equipment involved. Faulty inter card link |
| 089 | The inter card link is faulty or missing. Faulty blower fan The fan contactor is not connected although the CLIMATIC requests it. - The thermostat fire safety mechanism, or the fire insertion, is open. - The internal protection of the blower fan motor is open. The fire detector and the fan motor internal protection act directly on the fan motor contactor. |
| 091 | This information is transmitted to the CLIMATIC via an auxiliary contact of the contactor. If the CLIMATIC gives the order to operate to the fan and if the auxiliary contact is still open 5 seconds later, the fan safety system is activated and stops the unit. |
| 092 | Faulty condenser: system 1 or 2 |
| 093 | Faulty condenser: system 3 or 4 |
| 094 | Customer error A fault has been detected, external to the unit. WATER HEAT EXCHANGER OUTLET TEMPERATURE SAFETY SYSTEM. Condenser Water Temperature Too Low If the temperature of the water loop is less than or equal to the preset setpoint [C89] during the operation of one of the compressors, the condenser safety mechanism is applied. The compressors are stopped. |
| 096 | This safety mechanism automatically cuts out if the loop temperature is less than 4°C from this setpoint. |
| 097 | Condensor water overtemperature |
| 098 | Faulty water flow |
| 099 | The unit is completely shut down and the fresh air louver is set to the fresh air position. This safety mechanism is automaticallylocked out. In this case, manual resetting is obligatory. |
| 111 | Faulty condenser temperature sensor no. 1 |
| 112 | Faulty pressure transmitter no. 1 |
| 113 | Faulty frost temperature sensor no. 1 |
| 115 | - The high pressure pressostat is open. |
| 117 | Faulty low pressure compressor no. 1 |
| 121 | Faulty condenser temperature sensor no. 2 |
| 122 | Faulty pressure transmitter no. 2 |
| 123 | Faulty frost temperature sensor no. 2 |
| 125 | - The internal protection of the compressor motor is open. The high pressure pressostat and the compressor motor thermal protection act directly on the compressor contactor. This information is transmitted to the CLIMATIC via an auxiliary contact of the contactor. |
| 127 | This safety system is not taken into account during the defrost cycle for the heat pump units. The compressor is engaged when the pressostat contact closes. |
| 131 | Faulty condenser temperature sensor no. 3 |
| 132 | Faulty pressure transmitter no. 3 |
| 133 | Faulty frost temperature sensor no. 3 |
| 135 | If the CLIMATIC gives the order to operate to the compressor and if the auxiliary contact is still open 5 seconds later, the fan safety system is activated and stops the compressor.The safety system automatically cuts out after 4 minutes. |
| 137 | It is also automatically locked out after 3 failures within a day. In this case, manual resetting is obligatory. The counter is reset to zero every evening at 20:00 if its value |
| 141 | Faulty condenser temperature sensor no. 4 |
| 142 | Faulty pressure transmitter no. 4 |
| 143 | Faulty frost temperature sensor no. 4 |
| 145 | Faulty high pressure or faulty electrical power compressor no. 4 |
| 147 | does not exceed 3 failures. |
Источник: «Rooftops (крышные кондиционеры) Lennox серии SMART LINEА», стр. 76. Если кода нет в таблице или ошибка повторяется — обратитесь в сервисный центр.