Rooftops (крышные кондиционеры) Lennox серии FLEXY: FCA 50 - FCA 60 - FCA 70 - FCA 85 - FCA 100 - FCA 120 - FCA 140 - FCA 160 - FCA 190, FCK 50 - FCK 60 - FCK 70 - FCK 85 - FCK 100 - FCK 120 - FCK 140 - FCK 160 - FCK 190, FHA 50 - FHA 60 - FHA 70 - FHA 85 - FHA 100 - FHA 120 - FHA 140 - FHA 160 - FHA 190, FHK 50 - FHK 60 - FHK 70 - FHK 85 - FHK 100 - FHK 120 - FHK 140 - FHK 160 - FHK 190, FDA 50 - FDA 60 - FDA 70 - FDA 85 - FDA 100 - FDA 120 - FDA 140 - FDA 160 - FDA 190, FDK 50 - FDK 60 - FDK 70 - FDK 85 - FDK 100 - FDK 120 - FDK 140 - FDK 160 - FDK 190, FGA 50 - FGA 60 - FGA 70 - FGA 85 - FGA 100 - FGA 120 - FGA 140 - FGA 160 - FGA 190, FGK 50 - FGK 60 - FGK 70 - FGK 85 - FGK 100 - FGK 120 - FGK 140 - FGK 160 - FGK 190, FXA 25 - FXA 30 - FXA 35 - FXA 40 - FXA 55 - FXA 70 - FXA 85 - FXA 100 - FXA 110 - FXA 140 - FXA 170, FXK 25 - FXK 30 - FXK 35 - FXK 40 - FXK 55 - FXK 70 - FXK 85 - FXK 100 - FXK 110 - FXK 140 - FXK 170. Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Смотрите также: Коды ошибок: 57 кодов →
Загружаем документ…
Текст инструкции
-
INSTALLATION
OPERATING & MAINTENANCE MANUAL ROOFTOP FLEXY English Sept 2001
-
CONTENTS
IOM MANUAL Ref. IOM-RT F-0701-E The present manual applies to the following ROOFTOP versions : FCA 50 - FCA 60 - FCA 70 - FCA 85 - FCA 100 - FCA 120 - FCA 140 - FCA 160 - FCA 190 FCK 50 - FCK 60 - FCK 70 - FCK 85 - FCK 100 - FCK 120 - FCK 140 - FCK 160 - FCK 190 FHA 50 - FHA 60 - FHA 70 - FHA 85…
-
DELIVERY CHECKS
STORAGE The equipment is shipped at the customers risk, and whose responsiblity it is to ensure that the products are in good working order on receipt by checking the following : When units are delivered on site they are not always required immediately and are sometimes put into storage. In the…
-
DIMENSIONS AND WEIGHTS
-
Model
Length Ventil. louver mm Width Height Weight mm Side louver mm mm mm kg FX* 25 4070 490 600 1633 1055 950 FX* 30 4070 490 600 1633 1055 980 FX* 35 4750 490 600 2254 1290 1400 FX* 40 4750 490 600 2254 1290 1450 FX* 55 4750 490 600 2254 1290 1600 FX* 70 5050 890 600 2254 1725 1800 FX* 85 5050 890 600…
-
Sling length = 2590 mm for angle = 45°C Sling length = 1855 mm for angle = 45°C FC.../FH.../FD.../FG... 085 & 100 Sling length = 2830 mm for angle = 45°C Sling length = 2330 mm for angle = 64,5°C FC.../FH.../FD.../FG... 085 & 100 with centrifugal fans Sling length = 3230 mm for angle = 45°C Sling…
-
FC.../FH.../FD... 120 & 140
Sling length = 2700 mm for angle = 45°C Sling length = 2080 mm for angle = 45°C FC.../FH.../FD... 120 & 140 with centrifugal fans Sling length = 3000 mm for angle = 45°C Sling length = 2410 mm for angle = 45°C Sling length = 1880 mm for angle = 45°C FG... 120 & 140 with gas burner Sling length =…
-
FG... 120 & 140 with gas burner and centrifugal fans
Sling length = 3300 mm for angle = 45°C Sling length = 2700 mm for angle = 45°C Sling length = 2080 mm for angle = 45°C FC.../FH.../FD... 160 & 190 FC.../FH.../FD... 160 & 190 with centrifugal fans Sling length = 2700 mm for angle = 45°C Sling length = 2090 mm for angle = 45°C FG... 160 & 190 FG...…
-
FX 25 & 30
Sling length = 3000 mm FX 35 - 40 - 55 Sling length = 3700 mm FX 70 - 85 - 100 Sling length = 3900 mm FX 110 - 140 - 170 Sling length = 4300 mm IOM / ROOF-TOP FLEXY™ Series - Page 9
-
INS
TALLA TION INST ALLATION PRELIMINARY CHECK INSTALLATION DEVICE Before installing the equipment, the following items MUST be checked : The surface on which the equipment is to be installed must be clean and free of any obstacles which could hinder the flow of air to the condensers: - Is there…
-
INSTALLATION ON A ROOFMOUNTING FRAME
As levels are adjustable, observe the following recommendations for correct installation of the equipment. Above all, ensure that all the flaps are facing outward (1 - figure 5). They are sometimes stored inside for transport. 1 Figure 5 Place the roof mounting frame on the trimmer beam by first…
-
INSTALLATION ON A ROOFMOUNTING FRAME
When the frame is correctly positioned, it is essential to secure the assembly with a disconnected welding seam (20 to 30 mm for every 200 mm) along the outside, or by using an alternative method (1 - figure 8). 1 Figure 8 1 Assembly joint (1 - figure 9) 3 2 Insulate the frame before installation.…
-
INSTALLATION ON POSTS
The unit can be fitted on corner posts using the frame provided. The minimum height of the posts should be 400mm. Figure 10 IOM / ROOF-TOP FLEXY™ Series - Page 13
-
COMMISSIONING
This work must only be carried out by trained refrigeration engineers Before connecting to the power : Safety Test - Ensure that the power supply between the building and the unit meets local authority standards and that the cable specification satisfies the start-up and operating conditions.…
-
The actual resistance of ductwork systems is not always the
same as the calculated theoretical values. To rectify this, it may be necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys. TEST You should already have measured the + ve pressure experienced on fan discharge, as well as the pressure…
-
UNIT/FAN KIT REFERENCE TABLE
Size Fan type 50 FCx or FHx FGx or FDx FCx or FHx Centrifugal condensor FGx or FDx FCx or FHx Centrifugal condensor FGx or FDx FCx or standard FHx FCx or side FHx Centrifugal condensor FGx or FDx FCx or standard FHx FCx or side FHx Centrifugal condensor FGx or FDx FCx or standard FHx FCx or side FHx…
-
EXAMPLE
You may want to adjust a FHK 120 set to 22 000 m3/h with a system resistance of 150Pa: The machine has 2 fans (chart D). For this operating point, the unit supplied is fitted with E kits comprising 112 mm - 131 mm variable pulleys on the motors and 250 mm pulleys on the fans. In this case the pulley…
-
CHART A
Page 18 - IOM / ROOF-TOP FLEXY™ Series
-
CHART B
IOM / ROOF-TOP FLEXY™ Series - Page 19
-
CHART C
Page 20 - IOM / ROOF-TOP FLEXY™ Series
-
CHART D
IOM / ROOF-TOP FLEXY™ Series - Page 21
-
CHART E
Page 22 - IOM / ROOF-TOP FLEXY™ Series
-
CHART F
IOM / ROOF-TOP FLEXY™ Series - Page 23
-
AIRFLOW BALANCING - FXA/FXK
The FX* models are designed to operate with more complex supply and extract ductwork systems. Without balancing there are numerous risks : - Fan motor overvoltage - Significant flow variations depending on the position of the dampers, which affects the building concerned, especially when applied to…
-
fil
ters filters The CLIMATIC™ controls the filters. Two types of problems may occur : 1 - 004 error code (lit LED “filter”) or the following icon (for a graphics screen - KP07) : Item 8 on KP 17 indicates that the filters must be changed. The unit has not stopped but the airflow is likely to be reduced…
-
HO
T W ATER COILS HOT WA HYDRAULIC CONNECTIONS ELECTROLYTIC CORROSION The heating coil is connected to the isolating valves. Two keys must be used to tighten the connections, one of the keys maintains the valve body. Failure to use two keys may damage the pipes and invalidates the warranty. Attention…
-
PRELIMINARY CHECKS ON
COMMISSIONING NOTE : Any work on the gas system must only be carried out by qualified personnel. CAUTION : Smoking is forbidden during any intervention on the gas components. Make sure that the gas supply line installation conforms to the latest technology and the local safety regulations. Check…
-
PRESSURE REDUCING VALVE SETTING
- Connect the tube of the manometer to the power pressure inlet of a solenoid valve (5-figure 24) after loosening the screw. - Remove the safety plug of the expansion valve setting. - Use a screwdriver to pre-set by placing the screw at a depth of 34 mm. - Place the burner(s) in operation at maximum…
-
IGNITION ELECTRODE
The following two checks can be made : - Ensure that the electrode tip (1 – figure 25) is always sharp and oxide-free. Use some sand paper to clean it, if necessary. - The space between the tip and the air duct must be 3 mm approx. (2 – figure 26). 2 1 Figure 25 Figure 26 IONISATION SENSOR - The…
-
GAS BURNERS
BURNER DISASSEMBLY FOR SERVICE AND MAINTENANCE PURPOSES TROUBLESHOOTING Please refer to the enlarged diagrams at the end of the section (figures 29 to 31) for further help. - Check the electrical supply as well as the CLIMATIC™ which should show a heat demand. - Make sure that B17/18 minigas…
-
GAS BURNERS
60 KW BURNER FOR FGX 60 AND 70 MODELS 1 2 Figure 30 IOM / ROOF-TOP FLEXY™ Series - Page 31
-
120 KW BURNER FOR FGX 60, 70 AND 100 MODELS
Figure 31 Page 32 - IOM / ROOF-TOP FLEXY™ Series
-
180 KW BURNER FOR FGX 120 AND 140 MODELS
Figure 32 IOM / ROOF-TOP FLEXY™ Series - Page 33
-
BEL
T TENSION BELT On delivery, the drive belts are new and correctly tensioned. After the first 50 operating hours check and adjust the tension. 80% of the total elongation of belts is generally produced during the first 15 hours of operation. Before adjusting the tension, make sure that the pulleys…
-
PULLEYS
FAN PULLEY REMOVAL Remove the 2 screws and put one of them in the extraction threaded screw. Screw in fully. The hub and the pulley will separate from each other. Remove the hub and the pulley by hand without damaging the machine. Figure 35 FAN PULLEY INSTALLATION Clean and de-grease the shaft, hub…
-
USING THE KP 17 COMFORT CONTROL DISPLAY
The CLIMATIC™ 'Comfort' control Display allows an untrained person to easily operate a Lennox Roof-Top. This display connects to a single Rooftop and, through the use of the control keys, LED's and display the user can see how the connected Rooftop is operating, wether there are any faults, modify…
-
This display unit allows you to read and modify all the values
of the variables or setpoints of the rooftop to which it is connected. The dialogue with the controller is initiated by the CLIMATIC™. If, after 3 attempts, no communication is established, a message will be displayed signalling the problem. The unit will then try to re-connect at regular intervals.…
-
Variable or setpoint value
Digital Values 1 <--> ON 0 <--> OFF Temperatures Temperatures are displayed in °C, to an accuracy of 0.1 °C <--> -21.6 °C <--> + 105.8 °C Pressures Pressure is given in bars, to an accuracy of 0.1 bar. <--> 18.3 bars Other analog values Valeurs displayed Values non displayed Specific Displays…
-
If the password code is correct, the following message will
appear when key [V] is released : 2 - OPERATING MODES The maintenance display allows for 4 modes of operation. Key [M] allows you to move successively and in a loop from one mode to the next. The current mode is indicated by the status of LEDs [V] and [C] : Status of LEDs associated with current…
-
For different types of data, the setting ranges are as follows
Item Minimum value Maximum value Hours and minutes 00-00H 23-59 H Day of the month 1 31 Day of the week 1 7 Month 1 12 Year 0 99 Changes are only incorporated when key [A] is pressed. NOTE : The compatibility of the value for the day of the month is not checked when it is entered. You might…
-
LIST OF SETPOINTS
1st Level Min. Factory Maxi. 0 Password to access level 2 setpoints and variables 0 # 255 1 Temperature, required setpoint for room, day mode 8.0 21.0 35.0 2 (Used by KP17 only) KP17 Remote control, overide, occupied mode Off Off On (Used by KP17 only) KP17 Remote control, overide, automatic mode…
-
Factory
Maxi. (FLEXY™ only) Mode, Fan low speed, dead zone Off # On (FLEXY™ only) Mode, Fan low speed automation Off # On (on = unit runs at maximum 50% during "night mode") Mode, Low noise Off # On (J-BUS only) Remote control, overide, Mode Off Off On (J-BUS only) Remote control, Overide, Low fan speed Off…
-
Factory
Maxi. 55 Differential temperature, heating setting between 2 steps 0.1 1.0 10.0 56 Differential temperature, engaged cooling setting 0.0 1.0 10.0 57 Differential temperature, cold setting between 2 steps 0.1 1.0 10.0 58 (Not used - special option only) On = Compressors then chilled water coil, room…
-
Factory
Maxi. 87 Coefficient, icing time, condenser coil Number, condenser restart, condenser coil Low temperature, setpoint, air/water cooled heat exchanger (non standard) 4.0 5.0 20.0 High temperature, setpoint, air/water cooled heat exchanger (non standard) 20.0 45.0 46.0 Outside temperature, setpoint…
-
VARIABLE LIST (june 2001)
1st Level Error code Temperature, room Relative humidity (%),room Temperature, outside air Relative humidity (%), outside, air Temperature, supply Air Temperature, chilled water battery Temperature, compressor, no. 1 Temperature, compressor, no. 2 Temperature, compressor, no. 3 Temperature…
-
Output, low speed supply fan Output, Extract fan Output, compressor, no. 1 Output, compressor, no. 2 Output, compressor, no. 3 Output, compressor, no. 4 Output, compressor, no. 1, hot gas injection valve Output, compressor, no. 1, cycle reversing valve Output, compressor, no. 2, cycle reversing…
-
This display unit allows you to operate 1 to 8 machines. The
icon and schematic display provides a vivid and user-friendly interface.It uses a liquid crystal monochrome display, with background lighting, consisting of 240 x 128 pixels. It has 2 LEDs and 12 keys. The remote console must be connected to the unit using a 4 x 0.5 mm² braid-screened cable (maxi…
-
2 - FIXED KEYS (FIGURE 41)
5 - "MODIFICATION" MODE The functions of these 5 keys are fixed : This mode allows you to change the values of all the variables displayed on the active screen. It uses the 4 keys "1", "2", "3" and "4" by attributing preset functions to them : PAGE DOWN : KEY / ASSOCIATED ICON Moves to the next page…
-
GENERAL SCREEN LAYOUT
Summary Measurements : Temperatures Chart : Ambient temperature Measurements : Humidity Chart : Ambient humidity Operational status : Ventilation History : Safety & Errors Hourmeters : Ventilation, customer... Operational status : Frost History : Safety & Errors Operational status : Compressor n° 1…
-
Password
Level 1 Settings : On/Off Settings : Condition ; Day Settings : On ; Ventilation Settings : Condition ; Weekend Settings : On ; Ventilation Settings : Time Settings : Condition ; Night Settings : On ; Ventilation Settings: Time Settings : Condition ; Morning Settings : On ; Ventilation Settings…
-
Settings
Condition ; BMS Settings : On ; Ventilation Settings : Control ; Cold Settings : Control ; Hot Settings : Control. ; Dehumidification Settings : Control ; Humidification Settings : Control ; Misc. Settings : Limits ; Ambient Settings : Remote controls Settings : Limits ; Outside Settings : Remote…
-
INDEX OF ICONS
Keys Select variable to change Select digit to change. Increase value Enter current change. Go to temperature and humidity values and charts. Go to the machine component status. Go to various notices. Go to room temperature chart. Go to room humidity chart (Flexy only) Reset errors and error meters.…
-
Sensors
Temperature sensor Humidity sensor Pressure sensor Return or room data Supply data Outside data Operating conditions Operating condition: Day Operating condition: Weekend Operating condition: Night Operating condition: Morning Operating condition: Noon Operating condition: Evening Operating…
-
Compressor defrosting
Compressor stopped in anti-short cycle. / (On / Off) Condenser / (On / Off) Gas grade. Half flow gas. / (On / Off) Hot proportional valve, hot water valve. / (On / Off) Electrical heaters. / (On / Off) Humidifier / (On / Off) Dehumidification / (On / Off) Pump Errors General alarm / (Start / End)…
-
(Start / End) [091] Faulty processing fan. / (Start / End) [001] Wrong air flow. / (Start / End) [099] Error smoke. / (Start / End) [004] Dirty filters. / (Start / End) [005] Missing filters. / (Start / End) [115][125][135][145] Faulty high pressure or faulty electrical compressor. / (Start / End)…
-
BMS VOLT FREE CONTACTS KIT
-
The five available time slots are
ON - OFF The unit is declared On if setpoint 6 (C06) is ON. The unit can be stopped by a remote control command by hard contact. On KP12 extension card - see chapter on BMS contact kit. WEEK-END NIGHT For certain configurations a CLIMATIC™ system actuator can be used to control an external function…
-
DESCRIPTION OF PARAMETERS
Parameters are defined for the time slot. Select by instruction 08 setting. 0 = DAY / 1 = WEEKEND / 2 = NIGHT / 3 = unused / 4 = MORNING / 5 =MIDDAY / 6 = EVENING / 7 = BMS. Instruction Description 09 Day of the week of start of setting . From 1 to 7, 1 = Sunday. 10 Hour of start of setting 11…
-
ADVANCE ACTIVATION OF THE MORNING
SLOT ORDER OF COMPONENTS IN REGULATION Depending on the thermal inertia of the building or the installation and external climatic conditions, it is possible to advance the switch from the NIGHT slot to the MORNING slot. Cooling operation The time advanced, in minutes, is calculated using the…
-
Inversion by
setpoint 58 Inversion by setpoint 60 Inertia 100% zone Cp4 75% Cp4 3-way valve or water coil Cp3 Cp3 Damper 3-way valve 50% Cp2 Cp2 25% Cp1 Cp1 Min. fresh air 0% Heating setpoint 16 Air conditioning setpoint 15 Differential in heating Hysteresis in heating Hysteresis in air cond.…
-
REGULATION OF SUPPLY AIR
REGULATION IN HUMIDITY Supplying air regulation should be activated by setting setpoint 61 to ON. Two power factors, one for dehumidifying (variable 105), the other for humidifying (variable 104), are calculated according to the difference in relative hygrometry between the setpoint and the…
-
REGULATION IN DEHUMIDIFYING
3rd stage 2nd stage 1st stage Dehumidification Hysteresis (setpoint 69) Activation differential (setpoint 70) Hysteresis (setpoint 69) Activation differential (setpoint 70) Hysteresis (setpoint 69) ENTHALPY FUNCTION REGULATION IN HUMIDIFYING This function is used to control the use of the economiser…
-
L13
-
-KM10
-
DIAGRAMS
-
+18V
-
DIAGRAMS
-
таблицы и схемы — в просмотре
-
DIAGRAMS
-
+18V
06 05 12V 12V J3 KP12.2 J1 12V.H 12V.G J2 1 Remote control stop + - Comfort setpoint (4-20mA) 1 200mA Remote control night 2 3 Remote control day + Load limit 50% 4 5 Disable heating + Disable cooling 6 7 + Customer status 8 RL3 RL4 Gas heat alarm or electric heat alarm RL2 Compressor alarm RL1…
-
DIAGRAMS
-
AMS lis
t of itemS DIAGRAMS list +A0 CLIMATIC™ controller +A1/+A2 Condensing unit 1 / Condensing unit 2 +A3/+A4 Condenser 1 / Condenser 2 -A1 Démarreur progressif -B1 External air thermostat -B2 Smoke detection head -B3 RC circuit -B4/B5 Gas manifold ionisation sensor -B6/-B7 Gas manifold ignition electrode…
-
AMS lis
t of itemS DIAGRAMS list -Q1/2 Blower fan motor -MS1/-MS2 protection -Q5 Extraction fan motor -ME1/-ME2 protection -Q9 Condenser -MC1/-MC2 fan motor protection -Q10 Condenser -MC3/-MC4 fan motor protection -Q11/12 Compressor -MG1/-MG2 protection -Q13/14 Compressor -MG3/-MG4 protection -Q15 Condenser…
-
No error 001 Failure air flow 004 Dirty filters 005 Missing filters 011 Faulty electrical heater batteries 012 Supply air overtemperature 013 Temperature too low 014 Faulty gas burner no. Faulty gas burner no. 2 Supply temperature too low 023 Room overtemperature 031 Faulty humidifier 032 Room…
-
The following text includes references such as [C11] and [V25]. They relate to the threshold or variable numbers used with the KP02 unit. Wrong Air Flow 001 If the pressure differential obtained by the analog sensor [V16] is less than the setpoint value [C92] for more than 20 seconds, and if the…
-
register time set to 5 seconds. In addition, if the antifreeze thermostat is opened, the 3rd safety
level is immediately automatically maintained. In this case, manual resetting of the thermostat followed by the CLIMATIC™ is obligatory Room Overtemperature Safety System Upper Room Air Limit 023 013 If the room temperature is greater than or equal to the setpoint [C41], the safety system is…
-
Sensor Status
081 Room temperature sensor missing or faulty. 082 Room relative humidity sensor missing or faulty 083 Outside air temperature sensor faulty 084 Outside relative humidity sensor faulty 085 Supply Air temperature sensor faulty 086 Temperature sensor on cold water loop faulty 087 Temperature sensor on…
-
Customer error A fault has been detected, external to the unit. Water leak 095 If the contact of the water leak detection card is closed for more than 30 seconds, the safety system is activated. WATER HEAT EXCHANGER OUTLET TEMPERATURE SAFETY SYSTEM. Condenser Water Temperature Too Low 096 If the…
-
Refrigeration system faults
111 121 Faulty condenser temperature sensor Faulty pressure transmitter sensor, refrigeration system Faulty refrigeration system, frost temperature sensor 133 143 High pressure switch safety or compressor electrical safety The compressor contactor is not connected although the CLIMATIC™ requests it.…
-
Before Calling for Assistence
- The network voltage should not vary from + or - 10 % of the supply required for the equipment, Fan stops following thermal relay cutout (indicated via an error code) - The supply variation between the phases should never exceed + or - 3 %. Problem : 1. Check that there is current in the electrical…
-
Before Calling for Assistence
The unit no longer works Cause : - No supply voltage. - Ruptured remote control fuses. - Wrong connections. Solution : - Check the supply voltage. - Check the fuses. - Check and tighten the connections. The fan rotates but the compressor does not work Problem : - The air rerun conditions are not…
-
Regular maintenance of your Rooftop will extend its operating
life and reduce operating faults. We recommend that the unit is serviced by a trained refrigeration engineer. A log book kept near the equipment detailing work carried out, by whom and when, is an excellent diagnostic tool. The panel opening key is required for this work (see “TRANSPORT”). MOTOR-FAN…
-
REFRIGERATION CIRCUITS
At least once a year, carry out an in-depth inspection of the refrigerant circuits. In addition, before each season (or every 3 months if used permanently) the tasks listed in the maintenance contract must be performed, i.e. check the refrigerant charge, evaporation and condensing temperatures…
-
GENERAL
MAINTENANCE SCHEDULE At least once a year after winter the equipment casing must be cleaned, inspected and if necessary treated for corrosion. NOTE : 6 monthly maintenance is performed when changing from the heating season to the air-conditioning season and vice-versa. Annual maintenance is…
-
WARRANTY
TERMS AND CONDITIONS competent company. In the absence of any other written agreement, the guarantee shall only apply to design faults which occur within a 12 month period (warranty period). The sole effect of any repair, modification or replacement of an item during the warranty period must be to…
-
ISO 9001 CERTIFICA
TION CERTIFICATION Page 88 - IOM / ROOF-TOP FLEXY™ Series
-
CE CERTIFICA
TION OF CONFORMITY CERTIFICATION IOM / ROOF-TOP FLEXY™ Series - Page 89
-
EU4 FIL
TER FIRE CLASS FILTER Page 90 - IOM / ROOF-TOP FLEXY™ Series
-
33 kW GAS BURNER CE CERTIFICA
TION OF CONFORMITY CERTIFICATION IOM / ROOF-TOP FLEXY™ Series - Page 91
-
60 kW GAS BURNER CE CERTIFICA
TION OF CONFORMITY CERTIFICATION Page 92 - IOM / ROOF-TOP FLEXY™ Series
-
120 kW GAS BURNER CE CERTIFICA
TION OF CONFORMITY CERTIFICATION IOM / ROOF-TOP FLEXY™ Series - Page 93
-
180 kW GAS BURNER CE CERTIFICA
TION OF CONFORMITY CERTIFICATION Page 94 - IOM / ROOF-TOP FLEXY™ Series
-
INSULATION
IOM / ROOF-TOP FLEXY™ Series - Page 95
-
INSULATION
Page 96 - IOM / ROOF-TOP FLEXY™ Series
-
INSULATION
IOM / ROOF-TOP FLEXY™ Series - Page 97
-
INSULATION
Page 98 - IOM / ROOF-TOP FLEXY™ Series
-
GREAT BRITAIN ,
IRELAND : LENNOX INDUSTRIES LTD tél. : + 44 1604 599400 fax : + 44 1604 594200 e-mail : marketing@lennoxind.com BELGIUM : LENNOX BENELUX N.V./S.A. tel. : + fax : + e-mail : info.be@lennoxbenelux.com CZECH REPUBLIC : FRANCE : GERMANY : NETHERLANDS : JANKA RADOTIN AS tel. : + fax : + e-mail…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Rooftops (крышные кондиционеры) Lennox серии FLEXY II: FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100 - FHM 12…PDF · 8.58 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY II: FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100 - FHM 12…PDF · 10.85 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY II: FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100 - FHM 12…PDF · 8.74 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY, FLEXY WSHP FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230,FH M 85 - FHM 100…PDF · 10.05 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY, FLEXY WSHP FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100…PDF · 8.87 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY, FLEXY WSHP (85 - 234 kW). Инструкция по монтажу, эксплуатации и техническому обслуживанию.PDF · 3.93 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY WSHP: FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100 - FHM…PDF · 8.83 Mb
- Rooftops (крышные кондиционеры) Lennox серии FLEXY: FCA 60 - FCA 70 - FCA 85 - FCA 100 - FCA 120 - FCA 140 - FCA 160 - FCA 190, FCK 60 - FCK 70 - FC…PDF · 6.18 Mb