Rooftops (крышные кондиционеры) Lennox серии FLEXY, FLEXY WSHP FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230, FHM 85 - FHM 100 - FHM 120 - FHM 150 - FHM 170 - FHM 200 - FHM 230, FDM 85 - FDM 100 - FDM 120 - FDM 150 - FDM 170 - FDM 200 - FDM 230, FGM 85 - FGM 100 - FGM 120 - FGM 150 - FGM 170 - FGM 200 - FGM 230, FWH 85 - FWH 100 - FWH 120 – FWH150 – FWH170, FWM 85 - FWM 100 - FWM 120 – FWM150 – FWM170, FXK 25 - FXK 30 - FXK 35 - FXK 40 - FXK 55 - FXK 70 - FXK 85 - FXK 100 - FXK 110 - FXK 150 - FXK 170. Инструкция по монтажу, эксплуатации и техническому обслуживанию.
Смотрите также: Основной документ →
Загружаем документ…
Текст инструкции
-
Installation, operating
and maintenance FLEXY & FLEXY WSHP Providing indoor climate comfort FLEXYII-WSHP-IOM-0909-E
-
OPERATION
MAINTENANCE MANUAL Ref. FLEXYII_WSHP-IOM-0909-E The present manual applies to the following ROOFTOP versions: FCM 85 - FCM 100 - FCM 120 - FCM 150 - FCM 170 - FCM 200 - FCM 230 FHM 85 - FHM 100 - FHM 120 - FHM 150 - FHM 170 - FHM 200 - FHM 230 FDM 85 - FDM 100 - FDM 120 - FDM 150 - FDM 170 - FDM 200…
-
IMPORTANT NOTICE – Safety instructions
All FLEXY II Units are compliant with the PED directive 97-23/CE The following note must be followed carefully All work on the unit must be carried out by a qualified and authorised employee. Non-compliance with the following instructions may result in injury or serious accidents. Work on the unit…
-
IMPORTANT NOTICE – Safety instructions
UV LIGHT : - The UV lamp emits shortwave UV-C ultraviolet radiation which is harmful to skin and eyes It can cause serious skin burns and eye inflammation within ONE SECOND of exposure - Do not enter the machine while UV are switched on Make sure the UV light circuit breaker is OFF when opening the…
-
Site details
Site Unit Ref Installer Controller Model Serial No Refrigerant (1) ROOF INSTALLATION Sufficient Access OK Yes Condensate drain fitted Yes No Roofcurb OK No Not OK (2) CONNECTIONS CHECK Phase check Yes Voltage between Phases No 1/2 2/3 1/3 (3)CLIMATIC CONFIGURATION CHECK CLIMATIC 50 Configured…
-
It is recommended that you fill the two tables below before transferring the zone settings to the Climatic 50 controller. Refer to control section page 55 / Se référer à la section régulation page 55 Time Zones / Zones Horaires Hour 012 3 4567 Example 7h15 ZA 11h00 ZB 14h00 19h00 ZC UNO UNO Monday…
-
COMMENTS
FLEXYII_WSHP-IOM-0909-E Page 9
-
TRANSPORT – HANDLING – WARNING
STORAGE DELIVERY CHECKS On receipt of a new equipment please check the following points. It is the customer’s responsibility to ensure that the products are in good working order: - The exterior has not been damaged in any way. - The lifting and handling equipment are suitable for the equipment and…
-
MANDATORY HANDLING DEVICES
Handling slings to guide the unit towards the roofcurb Vacuum lifting beam to position the unit COMPLIANT FLEXYII_WSHP-IOM-0909-E NON-COMPLIANT Page 11
-
DIMENSIONS AND WEIGHTS
-
DIMENSIONS AND WEIGHTS
FXK025 FXK030 FXK035 FXK040 FXK055 FXK070 FXK085 FXK100 FXK110 FXK140 FXK170 FLEXYII_WSHP-IOM-0909-E LENGTH HEIGHT WIDTH mm mm mm 4070 4070 4750 4750 4750 5050 5050 5050 5650 5650 5650 1635 1635 2255 2255 2255 2255 2255 2255 2255 2255 2255 1055 1055 1290 1290 1290 1725 1725 1725 2000 2000 2000 HOOD…
-
LIFTING THE UNIT
As shown on the picture below, a lifting frame is necessary. After lifting, withdraw angle’s feet and lifting lugs. FLEXYII_WSHP-IOM-0909-E Page 14
-
FORKLIFT PROTECTIONS
NEVER LIFT THE UNIT WITHOUT FORKLIFT PROTECTIONS REMOVE THE FORKLIFT PROTECTIONS BEFORE INSTALLATION PRELIMINARY CHECKS Before installing the equipment, the following points MUST be checked: - Have the forklift protections been removed? - Is there sufficient space for the equipment? - Is the surface…
-
MINIMUM CLEARANCE AROUND THE UNIT
Figure 4 shows the required clearances and service access around the unit. NOTE: Ensure the fresh air inlet does not face prevailing wind direction. C B D A FCM/FHM/FGM/FDM/FWH/FWM F BOX G BOX H BOX FX 25 & 30 35Æ55 70Æ100 110Æ170 A B C D 2200 (1) 2700 (1) 2700 (1) 2000 2000 2000 2000 2000 2000 2000…
-
DUCT CONNECTIONS
RECOMMENDATIONS FOR DUCTS CONNECTIONS Some rules must be complied with for the connections between ducts and unit done on site. Whatever the supply configuration is, respect a minimal duct’s length (D) of 2m before any elbow or any duct’s diameter change. These recommendations are imperative in the…
-
WATER CONNECTIONS
WATER SOURCE HEAT PUMP ONLY Water connections The water circulating pump will be preferably installed upstream so that the evaporator/condenser will be subjected to positive pressure. Inlet and Outlet water connections are indicated on the certified drawing sent with the unit or shown in the sales…
-
WATER CONNECTIONS
Antifreeze protection Use glycol/water solution ADDITION OF GLYCOL IS THE ONLY EFFICIENT WAY TO PROTECT AGAINST FREEZING The glycol/water solution must be sufficiently concentrated to ensure proper protection and prevent formation of ice at the lowest outdoor air temperatures expected on an…
-
WATER CONDENSING
WATER LOOP CONFIGURATION (FOR WATER SOURCE HEAT PUMP) Figures below show the 2 water configurations. Figure 1 indicates all components used as standard : • the electronic water flow switch, • the water filter, • the pressure taps and drain valves, • the automatic airvent, The second figure shows…
-
таблицы и схемы — в просмотре
-
INSTALLATION ON A ROOFMOUNTING FRAME
CAUTION: - - An approach ramp must be installed if the unit’s installation requirements tell that it's necessary to reach the main switch. This recommendation is valid for installations in general and in particular for return and curbs. It’s also valid to reach other parts of the unit: filters…
-
INSTALLATION ON A ROOFMOUNTING FRAME
When the frame is correctly positioned, it is essential to secure the assembly with a disconnected stitched welded seam (20 to 30mm every 200mm ) along the outside or by using an alternative method CURBING AND FLASHING Outside of frame must be insulated with rigid type insulation; We recommend a…
-
INSTALLATION ON A ROOF MOUNTING FRAME
NON ADJUSTABLE NON ASSEMBLIED ROOFCURB INSTALLATION FRAME PARTS IDENTIFICATION Figure 8 shows the different parts used in the assembly of this roof mounting frame. INSTALLATION The roof mounting frame provides support when the units are installed in down-flow configurations. The non adjustable, non…
-
NON ADJUSTABLE ROOFCURB – Installation instructions
This roof curb will arrive as a packaged on a pallet and need to be built together. The part will be connected by special corrosion free nails. It is not possible to connect with standard nail equipment because there is a lot of power needed. Therefore, you need a pneumatic or electric device. All…
-
ADJUSTABLE ROOFCURB
-
NON ADJUSTABLE NON ASSEMBLED ROOFCURB
-
MULTIDIRECTIONAL ROOFCURB
-
RETURN ROOFCURB
All units CAUTION: An approach ramp must be installed if the machine installation requirements tell that it's necessary to reach the main switch. This recommendation is valid for installations in general and in particular for return and curbs. It’s also valid to reach other parts of the unit…
-
RETURN HORIZONTAL ROOFCURB
CAUTION: An approach ramp must be installed if the machine installation requirements tell that it's necessary to reach the main switch. This recommendation is valid for installations in general and in particular for return and curbs. It’s also valid to reach other parts of the unit: filters…
-
TRANSITION CURB
-
ENERGY RECOVERY
-
zoom
2 Fig. 25 zoom zoom 1 3 1) The unit being already erected on the roofcurb, remove the lifting lug shown on [A], and the doors of the Recovery module [B]. 2) Fit the support part of the Recovery Module on interior level of the rooftop 3) Fix the Recovery Module at the roof of the rooftop 4) Apply…
-
STEP 1: Rooftop configuration
This picture shows how the rooftop configuration has to be before recovery module assembling No Hood No panel The lifting lug and the corner sheet metal have to be removed. FLEXYII_WSHP-IOM-0909-E The head guard on the left corner of the rooftop has to be flattened. Page 34
-
STEP 2: Lifting
For Recovery module lift, use lifting lugs localised at the top of each corner structures FLEXYII_WSHP-IOM-0909-E Page 35
-
STEP 3: Fitting
During installation phase, fit the support part on the interior level of the rooftop SUPPORT PART INTERIOR LEVEL FLEXYII_WSHP-IOM-0909-E Page 36
-
STEP 4: Check
A good fit can be controled by looking at the junction between the rooftop and the recovery module: The junction has to be at the same level. SAME LEVEL For 150 and 170 sizes, a deviation of 70mm exists between rooftop and recovery module Size 150 & 170 (see picture on the right). 70 mm In the same…
-
STEP 5 : Fixing
When the module is well fitted, fix the corner structures to the rooftop by using selfdrilling screws 32mm Self-drilling screws 32mm D4.8 And fix the top of the module to the rooftop by using self-driling screws 19mm Self-drilling screws 19mm D6.3 FLEXYII_WSHP-IOM-0909-E Page 38
-
STEP 6: Masticate
Apply mastic on side junctions and higher junction FLEXYII_WSHP-IOM-0909-E Page 39
-
STEP 7: Electrical wiring
The Recovery module is sent with a power cable and a T-lan cable T-lan cable Power cable These 2 cables have to be inserted through this hole FLEXYII_WSHP-IOM-0909-E Page 40
-
Then fix the 2 cables on the grid of the extraction roofcurb and insert them in rooftop electrical panel as shown Cables from the module, through the hole, to rooftop electrical panel FLEXYII_WSHP-IOM-0909-E Page 41
-
Then connect the power cable from the module to the rooftop, and the t-lan to the
Climatic50 (or the BE50 if presents in electrical rooftop panel) Recovery Module Connection Exctraction Roofcurb Connection Actuator Roofcurb Connection Be careful: Check connections and connect male connections to good female one. Roofcurb and recovery module connectors are the same. To check the…
-
STEP 8: Roof curb economiser Adjustment
With Heat Recovery module option the extract air goes through the wheel, that’s why the economiser of the roofcurb has to be permanently fully closed. If roofcurb economiser is not fully closed, close it manually And don’t connect the actuator to the rooftop. Actuator Roofcurb not connected…
-
ECONOMISER AND EXTRACTION
ECONOMISER Free cooling can be provided through the use of fresh air which is more appropriate than excessive cooling amounts of return air. The economiser is factory fitted and tested prior to shipment. It includes two dampers operating from a 24V actuator RAIN HOOD It also includes a factory…
-
THIS WORK MUST ONLY BE CARRIED OUT BY TRAINED REFRIGERATION ENGINEERS
FILL THE COMMISSIONNING SHEET AS YOU GO ALONG Don’t forget to open the isolation Valves on the liquid line before starting the unit (see sticker below) ISOLATION VALVES MUST BE OPENED BEFORE RUNNING G1 G2 ELECTRICAL CONNECTIONS - Ensure that the power supply between the building and the unit meets…
-
STARTING THE UNIT
Check and adjust the control settings. At this point the unit circuit breakers should be open You will need a DS50 maintenance controller or Adalink with appropriate Interface. Refer to the control section in this manual to adjust the different parameters. POWERING THE UNIT - Power up the unit by…
-
RUN TEST
Start unit in cooling mode Reverse cycle test This test is designed to check the good operation of the 4way reversing valves on heat pump reversible systems. Start the reverse cycle by adjusting the cold or hot temperature threshold data according to the indoor and outdoor conditions at the time of…
-
VENTILATION : BELT TENSION
BELT TENSION On delivery, the drive belts are new and correctly tensioned. After the first 50 operating hours check and adjust the tension. 80% of the total elongation of belts is generally produced during the first 15 hours of operation. Before adjusting the tension, make sure that the pulleys are…
-
VENTILATION : PULLEYS
MOUNTING AND ADJUSTING PULLEYS FAN PULLEY REMOVAL Remove the 2 screws and put one of them in the extraction threaded screw. Screw in fully. The hub and the pulley will separate from each other. Remove the hub and the pulley by hand without damaging the machine. FAN PULLEY INSTALLATION Clean and…
-
The actual resistance of ductwork systems is not always identical to the calculated theoretical values. To rectify this, it may be necessary to modify the pulley and belt setting. To this effect, the motors are fitted with variable pulleys. SITE TEST AND MAINTENANCE Measure the motor absorbed power.…
-
2nd method when adjusting the pulley
-Close the pulley fully and count the number of turns from fully closed position. Using table_1 determine the motor pulley actual diameter. -Record the fix fan pulley diameter.(DF) -Determine the fan speed using the following formulae: CHECKING AIRFLOW AND ESP Using the fan curves on page 36 to 40…
-
EXAMPLE
The unit used for this example is a FGM170ND with standard supply and return airflow configuration. It is also fitted with an economiser and an electric heater type H. It is fitted with 2 ADH450 L fans which curve is shown on page 36 and 2x 5.5 kW motors.. - Motor rpm: 1447 rpm - cosϕ = 0.83…
-
AT15-15G2L(*)
(*) The performances of twin fan units can be calculated starting from the corresponding operation point for a single fan (see the figure behind) by applying the formulas below. - pressure : PTwin = P x 1 - volume flow rate : Qb = Q x 2 - impeller power: Wb = W x 2,15 - fan speed : Nb = N x 1,05…
-
AT18-18S
FLEXYII_WSHP-IOM-0909-E Page 54
-
ADH355L
FLEXYII_WSHP-IOM-0909-E Page 55
-
ADH450L
FLEXYII_WSHP-IOM-0909-E Page 56
-
ADH500L
FLEXYII_WSHP-IOM-0909-E Page 57
-
FILTERS
FILTER REPLACEMENT After opening the filter access panel, lift the filter retaining log. The filters can then be removed and replaced easily by sliding the dirty filters out and clean ones in. The CLIMATIC controller can monitor the pressure drop across the filter (If option fitted) The following…
-
VENTILATION : AIR SOCK CONTROL
AIR SOCK CONTROL FANSTART OPERATION The use of air socks for space conditioning allows high air volumes to be distributed at low velocity and is becoming a common feature in many applications. To accommodate this trend, Air-sock control is offered which allows the air socks to be progressively…
-
VENTILATION : UV lights
UV LIGHT UV light option allows to kill bacteria living on the fin. The UV lamp emits shortwave UV-C ultraviolet radiation which is harmful to skin and eyes It can cause serious skin burns and eye inflammation within ONE SECOND of exposure Do not enter the machine while UV are switched on Make sure…
-
HEATING : HOT WATER COIL
FREEZE PROTECTION HYDRAULIC CONNECTIONS Hot water coils offer fully modulating control through the use of a 3 way valve. The hot water coil, connections and valves are all tested at pressure of 15 bars. Frost protection is provided by forcing the opening the 3 way valve when supply temperature from…
-
таблицы и схемы — в просмотре
-
HEATING : ELECTRIC HEATER
GENERAL INFORMATIONS The electric heater comprises of shielded resistance heaters, which are smooth stainless steel tubes 6 W/cm2 capacity. High temperature limit control offers overload protection and is set to 90°C and located at less than 150mm after electric heaters. This is provided as a…
-
PRELIMINARY CHECKS BEFORE START-UP
NOTE : ANY WORK ON THE GAS SYSTEM MUST BE CARRIED OUT BY QUALIFIED PERSONNEL. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH LOCAL SAFETY CODES AND REGULATIONS AND CAN ONLY BE USED IN PLANED INSTALLATION CONDITIONS FOR OUTDOOR. PLEASE READ CAREFULLY THE MANUFACTURER’S INSTRUCTIONS BEFORE STARTING A…
-
HEATING : GAS BURNER 60 & 120 kW
PRESSURE ADJUSTMENTS ON HONEYWELL PRESSURE REGULATING VALVE TYPE VK 4125 P Pressure regulator adjustment with 300mbar gas supply: High Heat Injection Pressure Checks Fig.16 Check and adjust if necessary the valve OUTLET pressure to 10.4mbar (G 20) / 13.1mbar for Groningen (G25) & 34.3 mbar for…
-
HEATING : GAS BURNER 60 & 120 kW
Low Heat Injection Pressure Checks - Switch the control to Low Heat - Check and adjust if necessary the Outlet pressure to 3.7 mbar (G20) or 5.1 mbar for Groningue(G25) & 15.3 mbar for propane (G31)(fig.18) - After the adjustment of the low heat, re-verify the high heat - re-position the stoppers…
-
HEATING : GAS BURNER 180 & 240kW
PRESSURE ADJUSTMENTS ON HONEYWELL PRESSURE REGULATING VALVE TYPE VR 4605P Pressure regulator adjustment with 300mbar gas supply: Fig.20 High Heat Injection Pressure Checks Check and adjust if necessary the valve OUTLET pressure to 8.0mbar (G 20) / 10.4mbar for Groningen (G25) & 28.3 mbar for propane…
-
HEATING : GAS BURNER 180 & 240kW
Low Heat Injection Pressure Checks - Switch the control to Low Heat - Check and adjust if necessary the Outlet pressure to 3.1 mbar (G20) or 3.9 mbar for Groningen (G25) & 12.6 mbar for propane (G31) (fig.22) - After the adjustment of the low heat, re-verify the high heat - re-position the stoppers…
-
Ionisation Probe test
BURNER SAFETY CHECKS Smoke extractor pressure switch Test. - With the gas burner running, disconnect the terminal plug coming from the ionisation probe to the gas ignition control box. - With the gas burner running, disconnect the flexible tube fitted to the pressure taping on the pressure switch…
-
GAS BURNER FIRE-UP SEQUENCE
Operation from control thermostat GAZ =Closed Supply Thermostat Limit? (Auto Reset) NO YES NO Gas Low Pressure switch? YES Gas Ignition Control Block Signal Extraction Fan ON AIR Pressure Switch ON Backfire Thermostat ON? NO YES Pre-Ventilation 30 seconds Gas Control Valve Closes BURNER STOPS…
-
GAS BURNER TROUBLESHOUTING
If faults reported on CLIMATIC -Reset the CLIMATIC. -Check voltage: 230V after circuit breaker. -Check GAS isolation shut-off valves are open. -Check GAS pressure at the inlet of the GAS valves. It must be >20 mbar when the Burners shut down. -Adjust the set points to priorities the burner. Increase…
-
DISASSEMBLING THE GAS BURNER FOR
MAINTENANCE PURPOSES Preliminary Safety Recommendations - Isolate the unit using the main isolator switch. - Close off the isolating gas valve located before the unit. - Disconnect the Pipe-work. Do not discard the seals. Disassembling the gas «burner support bar» - Disconnect the Electrical…
-
60kW
120kW FLEXYII_WSHP-IOM-0909-E Page 73
-
180kW
240kW FLEXYII_WSHP-IOM-0909-E Page 74
-
Maximum opening
Actuator screw Minimum opening Bearing surface of the actuator’s screw MODULATING GAS (UNDER PATENT INPI May 2004) The actuator The actuator receives an information 0-10V from the regulation for the positioning of the air shutter; then the actuator transmits its position to the printed-board which…
-
PRESSURE ADJUSTMENTS ON HONEYWELL PRESSURE
REGULATING VALVE VK4105MB AND ON ELECTRONIC BOARD High & Low heat injection pressure check: W4115D1024 Electronic board W4115D1024 Pressure regulator adjustment with 300mbars gas supply: There is one board for two valves 230V power supply Potentiometer called « CURRENT » Switches in position 3 for…
-
- Check the 230V supply voltage of electronic board: the
phase on terminal 01 and the neutral conductor on terminal 02 - Bring back the potentiometer towards the position + until obtaining the desired 10.4mbar in high heat for natural gas. - Check the wiring of the signal 0-10V between terminal 64 (polarity 01 of the 24V) and terminal 66 (+ coming from…
-
MODULATING GAS (UNDER PATENT INPI May
2004) Maximum opening Actuator screw The actuator Minimum opening The actuator receives an information 0-10V from the regulation for the positioning of the air shutter; then the actuator transmits its position to the printed-board which will order the valve. Check position and operation of the…
-
PRESSURE ADJUSTMENTS ON HONEYWELL PRESSURE
REGULATING VALVE VR4605MB AND ON ELECTRONIC BOARD High & Low heat injection pressure check: W4115D1024 Electronic board W4115D1024 Pressure regulator adjustment with 300mbars gas supply: There is one board per valve 230V power supply Potentiometer called « CURRENT » Switches in position 3 for an…
-
- Check the 230V supply voltage of electronic boards: the
phase on terminal 01 and the neutral conductor on terminal 02 - Check the wiring of the signal 0-10V between terminal 64 (polarity 01 of the 24V) and terminal 66 (+ coming from the actuator) Adjusting minimum pressure setting: - Disconnect electrical connection to MODUREG (=modulating solenoid…
-
HEATING : MODULATING GAS BURNER
-
таблицы и схемы — в просмотре
-
CO2 SENSOR 16 CO2 SENSOR ANALOG DIRTY FILTER AND FAN PROVEN SWITCH 17 ANALOG DIRTY FILTER AND FAN PROVEN SWITCH COMFORT DISPLAY DC50 18 COMFORT DISPLAY DC50 COMFORT DISPLAY WIRELESS DC50W 19 COMFORT DISPLAY WIRELESS DC50W SERVICE DISPLAY DS50 20 SERVICE DISPLAY DS50 MULTIROOFTOP DISPLAY DM50 21…
-
DIAGRAM REFERENCE LEGEND
A1-2-3-4 AIR SOCK CONTROL BT10 REGULATION TEMPERATURE PROBE MG11/MG12 COMPRESSOR -MG11/MG12 B1 EXTERNAL AIR THERMOSTAT BT11 EXTERNAL TEMPERATURE PROBE MG21/MG22 COMPRESSOR -MG21/MG22 B2 SMOKE DETECTION HEAD BT12 BLOWER TEMPERATURE PROBE MR1 ECONOMISER DAMPER MOTOR B3 RC CIRCUIT BT13 COLD WATER…
-
FCM = Cooling only unit
FHM = Heat pump unit FGM = Cooling only unit with gas fired heating FDM = Heat pump unit with gas fired heating FWH = Heat pump unit with water condensing FWM = Heat pump unit with water condensing and gas fired heating MAIN CURRENT DIAGRAM TRI / 400V / 50Hz + T FLEXYII_WSHP-IOM-0909-E Page 85
-
FLEXYII_WSHP-IOM-0909-E Page 86
-
CLIMATIC 50 CONTROLER
FLEXYII_WSHP-IOM-0909-E Page 87
-
CLIMATIC 50 INPUT FCM / FHM / FGM / FDM / FWH / FWM
FLEXYII_WSHP-IOM-0909-E Page 88
-
CLIMATIC 50 OUTPUT FCM / FHM / FGM / FDM / FWH / FWM
FLEXYII_WSHP-IOM-0909-E Page 89
-
DAD SMOKE DETECTOR
FLEXYII_WSHP-IOM-0909-E Page 90
-
GENERAL CUSTOMER CONNECTION TCB
FLEXYII_WSHP-IOM-0909-E Page 91
-
GENERAL CUSTOMER CONNECTION WITH ADVANCED CONTROL PACK (ADC)
FLEXYII_WSHP-IOM-0909-E Page 92
-
WIRING DIAGRAM GAS BURNER 60 kW and HOT WATER COIL
HOT WATER COIL FLEXYII_WSHP-IOM-0909-E Page 93
-
WIRING DIAGRAM GAS BURNER 120kW
FLEXYII_WSHP-IOM-0909-E Page 94
-
WIRING DIAGRAM GAS BURNER 180 / 240kW
FLEXYII_WSHP-IOM-0909-E Page 95
-
WIRING DIAGRAM ELECTRIC HEATER
FLEXYII_WSHP-IOM-0909-E Page 96
-
GENERAL CUSTOMER CONNECTION DIAGRAM
FLEXYII_WSHP-IOM-0909-E Page 97
-
ELECTRICAL DATA : CONTROL VARIABLES
STANDARD ADVANCED CONTROL PACK OR TCB Logical Output Board (2 outputs: 1 assigned, 1 customized) Logical Output Board (4 outputs: 0 assigned, 4 customized) DO 1 - Alarm, General DO 2 - Customized (choose 1 output between those 7 possibilities) DO 3 to 6 - Customized (choose, for each input (4)…
-
R410A
SATURATION PRESSURE REFRIGERANT DEFINITION R-410A is an HFC, or hydro fluorocarbon, and is made of hydrogen, fluorine, and carbon atoms. Because it has no chlorine, it won’t interact with the ozone layer once it breaks down. It’s non-toxic and non-inflammable. CHEMICAL CHARACTERISTICS OF REFRIGERANT…
-
ADVANCED SCROLL TEMPERATURE PROTECTION (ASTP)
SERVICE A COMPRESSOR OPERATION MODE EXPLANATION Protection is activated when Scroll Discharge Port. Reaches 150°C (+/- 17K) Compressor is protected as « Unloaded » but continues to run • Protection mode balances discharge/suction pressure - Motor heat builds inside compressor - No…
-
BCD1.2
CONDENSER COIL BEC HOT WATER COIL BEV EVAPORATOR COIL CA1.2 CHECK VALVE DT1.2 THERMOSTATIC EXPANSION VALVE FD1.2 FILTER DRIER - B14 - B15 HOT WATER COIL ANTIFREEZE THERMOSTAT - BT12 BLOWER TEMPERATURE PROBE - BT17 RETURN REGULATION TEMPERATURE SENSOR - B41 - B42 COMPRESSOR -MG1 - MG2 HIGH PRESSURE…
-
FCM 150
FHM 150 FLEXYII_WSHP-IOM-0909-E Page 102
-
FCM 170
FHM 170 FLEXYII_WSHP-IOM-0909-E Page 103
-
FCM 200 & 230
FHM 200 & 230 FLEXYII_WSHP-IOM-0909-E Page 104
-
BEV
-
FWH - FWM 150
FWH - FWM 170 FLEXYII_WSHP-IOM-0909-E Page 106
-
HOT WATER COIL DIAGRAM
HOT WATER FLEXYII_WSHP-IOM-0909-E PIPE DIAMETERS 1 ROW 2 ROWS Page 107
-
REFRIGERATION
FAULT POSSIBLE CAUSE AND SYMPTOMS SOLUTION Refrigerant charge too low Measure the superheat and sub-cooling Good if 5°C<SC<10°C and 5°C<SH<10°C Bad if SC>10°C and SH too low Check superheat adjustment and charge unit (a leak check must be carried out) In Heat Pump Mode the temperature difference…
-
REFRIGERATION
FAULT POSSIBLE CAUSE AND SYMPTOMS SOLUTION Incorrect airflow rates Heat pump mode: Check the filter before the indoor coil measure and estimate the airflow rate increase the speed of the fan Cooling mode: Check the condenser fan (Amps) Incorrect water flow rate (Water cooled rooftop only) Check…
-
INDOOR FAN BLOWER
FAULT POSSIBLE CAUSE AND SYMPTOMS SOLUTION High amps on action Fan motor Pressure drop in the ducting installation too low. Reduce the rotation speed of the fan Measure and estimate the airflow and pressure and compare with the specification from customer. High amps on reaction Fan motor Pressure…
-
WATER LEAKS
FAULT POSSIBLE CAUSE AND SYMPTOMS SOLUTION Cooling mode: Water carried away from the coil because of excessive airflow and speed on the coil. Estimate the airflow rate and check the speed is lower than 2.8 m/s Low air pressure in the compartment due to a high airflow rate or a high pressure drop…
-
MAINTENANCE PLAN
Rooftops are generally placed on the roof but can also be installed in technical rooms. These units are very robust but minimum regular maintenance is required. Some moving parts in the units can suffer from wear and tear and must be checked regularly (belts). Other parts can get clogged by dirt…
-
Clean or replace filters
disposable or metal frame Visual check of the oil level Position check of the compressor crankcase heater Belt tension check Centrifugal fan bearings check Check absorbed amps Check smoke detector Check CLIMATIC control, setpoints and variables Check clock settings Check the position and tightness…
-
Install manifold gauges on the circuit to be checked
Shut down the axial fans and wait for the HP switch to shut down the compressor : 29 bar (+1/-0) auto reset 22 bar (+/- 0,7). Check HP/LP safety switches Reconnect fans. Switch off the centrifugal supply fan and wait for the LP switch to cut out : 0,5 bar (+/- 0,5) reset 1,5 bar (+/- 0,5). Check…
-
WARRANTY
TERMS AND CONDITIONS In the absence of any other written agreement, the guarantee shall only apply to design faults which occur within a 12 month period (warranty period). The warranty period starts on the date of commissioning and at the latest six months after the delivery of the Rooftop.…
-
LONGVIC SITE – ISO 9001 (2008) CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 116
-
EC CONFORMITY DECLARATION
FLEXYII_WSHP-IOM-0909-E Page 117
-
SMOKE DETECTOR – NF CONFORMITY CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 118
-
SMOKE DETECTOR - CE CONFORMITY CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 119
-
G4 FILTER INSULATION CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 120
-
F7 FILTER INSULATION CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 121
-
GLASSWOOL INSULATION CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 122
-
GLASSWOOL INSULATION CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 123
-
FLEXY 60-120-180-240 KW GAS BURNER CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 124
-
ROOFTOP PED CONFORMITY CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 125
-
ROOFTOP PED CONFORMITY CERTIFICATE
FLEXYII_WSHP-IOM-0909-E Page 126
-
Direct Sales Offices
BELGIUM AND LUXEMBOURG + 32.3.633.3045 info.be@lennoxeurope.com PORTUGAL +351 info.pt@lennoxeurope.com CZECH REPUBLIC + 420.2.510.88.711 info.cz@lennoxeurope.com RUSSIA +7 info.ru@lennoxeurope.com FRANCE +33 info.fr@lennoxeurope.com SLOVAKIA +421 info.sk@lennoxeurope.com GERMANY + 49 (0)…