Installation and maintenance manual
Manuel d’installation et de maintenance Installations- und Wartungshandbuch Manuale di installazione e di manutenzione Manual de instalación y de mantenimiento SyScrew 300-1400 Air CO/TR English 295 1395 kW Français Deutsch Italiano Español Air Cooled Water Chillers with Screw Compressors…
-
11--Introdução
Foreword 1.1 Introduction 1.3 Emergency stop / Normal stop Units, manufactured to state-of-the-art design and implementation standards, ensure top performance, reliability and fitness to any type of air-conditioning systems. The emergency stop of the unit can be enabled using the master switch on…
-
2 - Safety
2.1 Foreword These units must be installed in conformity with the provisions of Machinery Directive 2006/42/EC, Pressure Equipment Directive 2014/68/EU, Electromagnetic Compability Directive 2014/30/EU, as well as with other regulations applicable in the country of installation. If these provisions…
-
disassemble connections, filters, joints or other line items
2.2 Definitions OWNER: means the legal representative of the company, body or individual who owns the plant where unit has been installed; he/she has the responsibility of making sure that all the safety regulations specified in this manual are complied with, along with the national laws in force.…
-
n
periodically check the board’s internal wiring n n do not use cables having an inadequate section or flying connections, even for limited periods of time or in an emergency place a warning sign “do not turn on - maintenance in progress” on the external disconnecting switch n make sure that on-off…
-
2.7 Safety labels
Identification of the refrigerant - External door Identification of the unit - Outside, on the right-hand front column CODICE PRODOTTO NEUTRO USARE SOLO R134a E SPECIAL ESTER OIL MODELLO MODEL RECOVER - DO NOT VENT - EEC REGULATION N° 3093/94 RECUPERARE FLUIDO - NON DISPERDERE NELL’AMBIENTE…
-
Start-up warning - Outside the door
of the electrical board English 2 - Safety (continued) Final Test Certificate - Inside the external door ATTENZIONE INSERIRE LE RESISTENZE DI RISCALDAMENTO OLIO ALMENO 12 ORE PRIMA DI OGNI AVVIAMENTO (SE PREVISTE) PRIMA DELLA MESSA IN TENSIONE ASSICURARSI CHE LE VITI DEI CIRCUITI ELETTRICI SIANO…
-
2.8 Safety regulations
REFRIGERANT DATA Toxicity SAFETY DATA: R134a Low If sprayed, the refrigerant is likely to cause frost burns. If absorbed by the skin, the danger is very limited; it may cause a slight irritation, and the liquid is degreasing. Unfreeze the affected skin with water. Contact with skin Remove the…
-
2.8 Safety regulations (continued)
REFRIGERANT DATA General precautions Respiratory system protection SAFETY DATA: R134a Do not inhale concentrated vapours. Their concentration in the atmosphere should not exceed the minimum preset values and should be maintained below the professional threshold. Being more weighty than the air, the…
-
2.8 Safety regulations (continued)
LUBRICANT OIL DATA SAFETY DATA: POLYESTER OIL (POE) Classification Not harmful. Contact with skin May cause slight irritation. Does not require first aid measures. It is recommended to follow usual personal hygiene measures, including washing the exposed skin with soap and water several times a day.…
-
Refrigerators are supplied assembled (apart from standard
antivibrating rubber supports, that will be installed on site). The equipment are full of refrigerant and oil, in the quantity required for a proper operation. It is recommended to use a spacer to prevent cables from damaging the unit (see the figure). 3.1 Inspection When the unit is delivered, it…
-
3 - Transport, Lifting and Positioning (continued)
The eyebolts must be mounted on the unit whenever it shall be displaced and then lifted again. During the lifting and handling of the unit, be careful not to damage the finned pack of the coils positioned on the sides of the unit. WARNING WARNING WARNING 3.3 Anchoring The sides of the unit must be…
-
4.1 Positioning of the unit
DANGER 4.2 Spring Isolator Installation Before installing the unit, make sure that the structure of the building and/or the supporting surface can withstand the weight of the appliance. The weights of the units are listed in Chapter 8 of this manual. These units have been designed for outdoor…
-
4.3 External Water Circuit
A flow switch will stop the unit when the water is not circulating or a flow rate problem occurs. The flow switch and the filter water, although not included in the supply, must always be fitted such as plant components. Their installation is mandatory for warranty. WARNING To install the flow…
-
Then
n Provide the evaporator with a by-pass circuit equipped with a valve to wash the plant. n Insulate the piping, to prevent the risk of heat loss. n Position a filter on the suction side of the evaporator of the heat recovery condenser. Standard hydraulic circuit External water circuit Unit…
-
4.5 Connection of water temperature sensors
(on shell and tube evaporator) Each fitting is complete with sensor well to fasten temperature sensor (BT-IN and BT-OUT). Fittings are supplied separate and must be mounted during the installation of the unit. The units are provided with fittings for hydraulic connections between heat exchangers and…
-
4.6 Power supply
DANGER 4.7 Electrical connections The unit must be installed on site according to the Machinery Directive 2006/42/EC, Electromagnetic Compatibility Directive 2014/30/EU and the usual procedures and standards applicable in the place of installation. Before carrying out any operations on the…
-
Electrical connections - Units with standard step and stepless type compressors
-
WARNING
The unit must be started for the first time by personnel suitably trained by one Authorised Service Centre. Failure to meet this requirement will immediately void the warranty. n Start the pump and check that the water flow is correct. n Set the desired fluid temperature on the control board. n…
-
6 - Control
6 General information The control system consists of: This document contains the information and the operating instructions for screw compressors of step type. a) Main Board. The units are provided with a microprocessor card which is fully programmed by default for the control of a chiller of cold…
-
6.1 Display/Keyboard
Esc key: allows you to move from one mask to another. Alarm key: used to display the alarms, to reset them in manual. Press it one to display the mask of the activated alarm, press it again to reset the alarm signal. alarm Prg+Esc keys: Pressing these keys at the same time,allows you to turn the…
-
Alarms
Alarm code Description Main board - EPROM Failure Main board - Clock card Failure Main board - External air temperature sensor fault Main board - Return Water temperature sensor fault Main board - Leaving Water temperature sys 1 sensor fault Main board - Leaving Water temperature sys 2 sensor fault…
-
Alarm code
Description Driver 2 Battery alarm Autotune alarm Sys 1 Autotune alarm Sys 2 Low suction alarm Sys 1 Low suction alarm Sys 2 Driver 1 Regulation Alarm Driver 2 Regulation Alarm Expansion board 1 OFF LINE Expansion board 2 OFF LINE Expansion board 1 - Sensor 1 fault Expansion board 1 - Sensor 2 fault…
-
6.3 Protection and Safety Equipment
Electrical flow switch Refrigeration system A electrical flow switch must be installed, to prevent the unit working in case of insufficient circulation of the chilled fluid. The units are filled with R134a refrigerant fluid of non hazardous type (group II). Safety device (pressure switch and safety…
-
6.4 HPF version configuration
Units equipped with High pressure fan (HPF) can be set-up on the field to give the unit a specific static pressure. By entering parameter in service level - Max Speed (Vdc) - it is possible to modify high static pressure. The table below shows the correspondance between chiller model, fan RPM, high…
-
7 - Product Description
7.1 Introduction The units are air cooled water chillers provided with screw compressors with two refrigeration circuits. These units can be installed outdoor on the roof of a building or at ground level. These units are fit for cooling intermediate fluids (glycoled water), for air-conditioning…
-
7.5 Water heat exchanger
The power supply compartment includes: Evaporator n Master switch The units are provided with a direct-expansion refrigerant/water shell and tube heat exchanger with several refrigeration circuits. n Network isolator, contactors, compressor fuses Control panel includes: The evaporators are insulated…
-
7 - Product Description (continued)
Refrigerant flow diagram - Unit 300-360 S AT A A H G B S 6 BT S EXV CONTROL 5 UNIT CONTROL E 3 4 F 2 S COMPONENTS SAFETY / CONTROL DEVICES 1 Compressor (Screw type) A High pressure switch (19 bar) 2 Air cooled condenser B Low pressure switch (0.5 bar) 3 Filter drier AT High pressure transducer 4…
-
7 - Product Description (continued)
Refrigerant flow diagram - Unit 410-450-650-720-1000-1070-1130-1170-1300-1400 G S A A AT 2 5 D 7 5 S H 1 S S 6 B 12 BT 11 S EXV CONTROL E 4 F COMPONENTS SAFETY / CONTROL DEVICES 1 Compressor (Screw type) A High pressure switch (19 bar) 2 Air cooled condenser B Low pressure switch (0.5 bar) 3 Filter…
-
8 - Technical Data
-
8.2 Technical data
Standard Power supply 300 Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz 400V/3/50Hz PW PW PW % PW PW PW PW SD 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow) inch EXTERNAL…
-
Standard
Power supply 650 Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz 910 970 1000 SD SD SD SD 400V/3/50Hz SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type 2 Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow) inch…
-
Standard
Power supply 1070 1170 V/Ph/Hz Number of refrigerant circuits Start-up Type Total capacity steps 1130 English 8 - Technical Data (continued) 1200 1300 1400 400V/3/50Hz SD SD SD SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water…
-
Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz 400V/3/50Hz PW PW PW % PW PW PW PW SD 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow) inch EXTERNAL HEAT EXCHANGER (COILS)…
-
800 850 V/Ph/Hz Number of refrigerant circuits Start-up Type Total capacity steps 720 English 8 - Technical Data (continued) 910 970 1000 SD SD SD SD 400V/3/50Hz SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type 2 Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall &…
-
Number of refrigerant circuits Start-up Type Total capacity steps 1130 1170 V/Ph/Hz 1200 1300 1400 400V/3/50Hz SD SD SD SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections Shall & tube (Pure counterflow) inch EXTERNAL HEAT…
-
Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz English 8 - Technical Data (continued) 400V/3/50Hz PW PW PW % PW PW PW PW SD 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow)…
-
Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz 910 970 1000 SD SD SD SD 400V/3/50Hz SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type 2 Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow) inch EXTERNAL HEAT…
-
1170 V/Ph/Hz Number of refrigerant circuits Start-up Type Total capacity steps 1130 English 8 - Technical Data (continued) 1200 1300 1400 400V/3/50Hz SD SD SD SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections Shall & tube…
-
Number of refrigerant circuits Start-up Type Total capacity steps V/Ph/Hz 400V/3/50Hz PW PW PW % PW PW PW PW SD 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall & tube (Pure counterflow) inch EXTERNAL HEAT EXCHANGER (COILS)…
-
800 850 V/Ph/Hz Number of refrigerant circuits Start-up Type Total capacity steps 720 English 8 - Technical Data (continued) 910 970 1000 SD SD SD SD 400V/3/50Hz SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type 2 Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections 1 Shall &…
-
Number of refrigerant circuits Start-up Type Total capacity steps 1130 1170 V/Ph/Hz 1200 1300 400V/3/50Hz SD SD SD SD SD SD % 25-50-62-75-87-100 COMPRESSOR Number Type Screw INTERNAL HEAT EXCHANGER (EVAPORATOR) Number Type Water connections Shall & tube (Pure counterflow) inch EXTERNAL HEAT…
-
8.3 Unit electrical data
-
8.4 Hydraulic features
Evaporator Available Pressure (Low head - Pump “A” & “B”) Models 300-580 400 500-540-580 Avaliable Pressure [kPa] AvaliableStatic Static Pressure [kPa] 410-450 300-360 30000 40000 50000 60000 70000 80000 850-910 9701000 90000 Water Flow [l/h] Water Flow [l/h] Available Pressure (Low head - Pump “C”…
-
Available Pressure (Low Head - Pump “E”) Models 1130-1200
350 AvaliableStatic Static Pressure Avaliable Pressure[kPa] [kPa] 1130-1170-1200 50 0 50000 100000 150000 200000 250000 300000 Water Flow [l/h] Water Flow [l/h] Available Pressure (High Head - Pump “F”) Models 300-410 400 AvaliableStatic Static Pressure Pressure [kPa] Avaliable [kPa] 300-360 30000…
-
Available Pressure (High Head - Pump “G” & “H”) Models 450-720
450 Avaliable Static [kPa] Avaliable StaticPressure Pressure [kPa] 400 650-720 350 300 450-480 250 200 500-540-580 40000 50000 60000 70000 80000 90000 100000 110000 120000 130000 140000 Water Flow [l/h] Water Flow [l/h] Available Pressure (High Head - Pump “I” & “J”) Models 800-1070 500 450…
-
Available Pressure (High Head - Pump “K”) Models 1130-1200
450 Avaliable Static Pressure [kPa][kPa] Avaliable Static Pressure 400 350 1130-1170-1200 50000 100000 150000 200000 Water Flow [l/h] Water Flow [l/h] 49 250000 300000 350000
-
8.5 Position of shock adsorbers and weight distribution on supports
-
8.6 Dimensional drawings - 4V 300-360-410-450-480-500
-
8.6 Dimensional drawings - 5V 540
-
8.6 Dimensional drawings - 6V 580-650-720-800
-
8.6 Dimensional drawings - 8V 850-910-970-1000
-
8.6 Dimensional drawings - 9V 1070
-
8.6 Dimensional drawings - 10V 1130-1170-1200
-
8.6 Dimensional drawings - 11V 1300
-
8.6 Dimensional drawings - 12V 1400
-
8.7 Service spaces
-
When the recovered refrigerant cannot be reused, return it to the manufacturer
Do not throw away the waste oil of the compressor, because it contains refrigerant in solution. DANGER The waste oil must be returned to the manufacturer. Unless otherwise specified, the operations described below may be carried out only by a trained maintenance operator. 9.1 General requirements…
-
9.3 Refrigerant charge
Do not inject refrigerant liquid into the LP side of the circuit. Be very careful, and charge the circuit properly. WARNING If the charge is insufficient, the efficiency of the unit will be lower than expected. In the worst of cases the LP pressure switch may be activated, resulting in the halting…
-
9 - Maintenance (continued)
9.8 Sight glass Overheating calculation (S): The sight glass is used for inspecting the refrigerant flow and the humidity % of the refrigerant. The presence of bubbles indicates that the dehydrating filter is clogged or the charge insufficient. S = Tse - Tsa Overheating is regulated through the…
-
The table below lists the anomalies of operation of the unit, the relevant causes and the corrective measures. For anomalies of any other type or not listed, contact one of authorised Service Centre for technical assistance. Anomaly Cause Operation The unit continues to work, but without cooling…
-
11 - Spare Parts
11.1 Spare part list The table below shows the list of spare parts recommended during the first two years of operation. Component Number HP pressure switch 1 LP pressure switch 1 Gas filter 2 Electronic expansion valve 2 Auxiliary relays 2 Fan’s fuses 6 Compressor’s fuses 6 Auxiliary fuses 6 Set of…
-
After draining operations, the piping of the hydraulic networks can be
disconnected and disassembled. During the draining of the refrigeration circuits, do not let the refrigerant overflow in the surrounding atmosphere. DANGER Once they have been disconnected as specified, the packaged units can be disassembled in a single piece. First of all, disassemble the anchoring…
-