MILLENNIUM TM CONTROL CENTER
OPERATIONS MANUAL OPERATORS MANUAL Supersedes: 155.16-O3 (894) Form 155.16-O3 (797) ABSORPTION LIQUID CHILLERS 28342A MODELS YIA-ST-1A1 THROUGH YIA-ST-14F3 (STEAM) MODELS YIA-HW-1A1 THROUGH YIA-HW-14F3 (HOT WATER)
-
USING THIS BOOK
The “Theory of Operation” section provides an overview of the unit control provided by the MILLENNIUM CONTROL CENTER. Unit control is described and operating and status messages that are displayed on the Control Center display are highlighted. The “Operation Flow Chart” can be used as a quick…
-
Two variations of the Model YIA units are as follows
• Models YIA-ST-1A1 thru YIA-ST-14F3 with ADC for steam applications. • Models YIA-HW-1A1 thru YIA-ST-14F3 with ADC for hot water applications. Although two applications exist for Models YIA steam and hot water units; namely, standard and FAX-4500 versions, both are accomplished through the use of a…
-
manual dilution cycle is controlled via the MANUAL
PUMP key in the Service section of the keypad. The PUMP STATUS key employs a scrolling feature to allow control of the pumps, the manual dilution cycle, and the stabilizer refrigerant solenoid valve via the MANUAL PUMP key. In SERVICE mode, each pump may be operated manually if not already required…
-
it and opens when the level decreases below the float,
and 1F is at a higher level than 3F, it is not possible that 1F would be closed if 3F is still open; unless one of the switches is stuck in one position. If this condition is detected, a safety shutdown is performed and “DAY-TIMEREF PUMP FLOAT SW CONFLICT” is displayed. NOTE: the state of each float…
-
ing to 30% whenever the generator shell pressure threshold of 10.00 PSIA is reached. During this time, the panel displays the message “SYSTEM RUN-PRESS STATUS” and the warning relay contacts are closed. The STATUS key displays the warning message “HIGH PRESSURE OVERRIDE”. This feature allows the…
-
manual operation of the refrigerant level solenoid is only
allowed in MANUAL PUMPS key via the special access code in the PROGRAM MODE. If the refrigerant level solenoid is manually energized (open), it is de-energized (closed) as follows: • Manually, using the DISPLAY DATA key • Automatically, if the mode is changed for SERVICE to LOCAL or REMOTE Whenever…
-
ture provides a warning message and limits the maximum load to 60% of the steam or hot water valve position. The feature, which is bypassed for the first 30 minutes of unit operation, is in effect when the entering condenser water temperature exceeds the specified limit for 10 minutes continuously.…
-
DILUTION
The dilution cycle occurs at most shutdowns. The dilution cycle is required to prevent crystallization of the lithium bromide solution. During the dilution cycle, the solution (absorber and generator on 50 Hz Models YIA10E3 – YIA-14F3 with Franklin pumps); refrigerant; and chilled and condenser…
-
abled at the instant of unit shutdown. This allows the
refrigerant pump to start at the beginning of the dilution cycle without any delay. PURGE Since absorption chillers operate at pressures below atmospheric, a purge system is required to remove system impurities which degrade performance and cause internal corrosion. The system employs a purge pump…
-
UNIT OPERATION
LOCAL OR REMOTE MODE STEAM OR HOT WATER UNITS BEGIN ➤ 1 ➤ ➤ LOCAL OR REMOTE START NO YES ➤ 2 ➤ CYCLING SHUTDOWNDISPLAY “DAY-TIME-LVG WATER TEMP < SETPOINT” AS STATUS YES LVG WATER TEMP < SETPOINT NO ➤ 9 CYCLING SHUTDOWNDISPLAY “DAY-TIMESTEAM/HOT WATER VALVE LOADED ABOVE 10%” AS STATUS ➤ PAGE 43 YES…
-
START 30 SECOND TIMER ➤ ➤ NO CHILLED WATER FLOW SWITCH CLOSED ➤ NO 30 SECOND TIMER ELAPSED ➤ YES SAFETY SHUTDOWNDISPLAY “DAYTIME-CHILLED WATER FLOW SWITCH” AS STATUS YES ➤ ➤ 11 CLEAR 30 SECOND TIMER PAGE 44 ➤ CLOSE CONDENSER WATER PUMP CONTACTS TB4-55/56 ➤ START 30 SECOND TIMER ➤ ➤ NO CONDENSER…
-
DISPLAY “SYSTEM RUN-LEAVING CHILLED WATER CONTROL ➤ REFRIG TEMP >34°F (1.1°C) ➤ YES START SOLUTION PUMP (1M), ABSORBER PUMP (50 HZ MODELS YIA-10E3 – YIA-14F3 WITH FRANKLIN PUMPS) NO ➤ ➤ ENERGIZE 1R RELAY TO OPEN STEAM/HOT WATER SHUTOFF VALVE ➤ STEAM UNIT YES ➤ ENERGIZE 6SOL TO OPEN STEAM CONDENSATE…
-
FLOAT SW 3F CLOSED ➤ YES REFRIG PUMP (1F) ➤ START-UP DELAY YES TIMER ELAPSED FLOAT SW 1F CLOSED NO YES ➤ NO ➤ NO ➤ 4 ➤ ➤ START REFRIGERANT PUMP (2M) ➤ PAGE 35 REFRIG PUMP (2M) RUNNING NO REFRIG FLOAT SW SHUTDOWN TIMER ELAPSED ➤ ➤ YES SAFETY SHUTDOWN – DISPLAY “DAY-TIMEREFRIGERANT PUMP FLOAT SW…
-
PULLDOWN DEMAND PROGRAMMED YES START PULLDOWN INTERVAL TIMER (0-255 MIN) ➤ YES ➤ NO ➤ PULLDOWN DEMAND PROGRAMMED 20-100% YES PULLDOWN INTERVAL ELAPSED ➤ NO ➤ YES NO PULLDOWN LOAD LIMIT (%) = ➤ (STOP LIMIT-START LIMIT) T ELAPSED T INTERVAL [ ] + START LIMIT ➤ ➤ YES PULLDOWN LOAD LIMIT > MAX ALLOWED…
-
NO A ➤ REMOTE MODE CONTROL PER FAX-4500 LEAVING WATER TEMP SETPOINT ➤ YES ➤ YES YES NO NO ➤ FAX4500 FAX-4500 LOAD LIMIT > MAX ALLOWED LOADING VALUE UNIT LOADING = FAX-4500 LOAD LIMIT ➤ ➤ NO YES ➤ ➤ PWM REMOTE LOAD LIMIT (10-20)-100% YES ➤ LIMIT UNIT LOADING TO FAX-4500 LOAD LIMIT (10-20) - 100% ➤ ➤…
-
CHECK PROGRAMMED “MAX ALLOWED LOADING” VALUE (50-100%) ➤ AT MAX ALLOWED LOADING YES DISPLAY “SYSTEM RUN” MAXIMUM COOLING ➤ ➤ NO LIMIT LOAD COMMAND TO MAXIMUM ALLOWED LOADING (50-100%) ➤ ➤ CHECK CONDENSER WATER FLOW SWITCH @ TB2-20 ➤ OPEN FOR 30 SECONDS YES CYCLING SHUTDOWN DISPLAY “DAY-TIME-COND…
-
YES NO ➤ CYCLING SHUTDOWN-DISPLAY “DAY-TIME-LOW WATER TEMP-AUTOSTART” AS STATUS ➤ NO < 30 MINUTES SINCE LCWT SP RAISED ➤ ➤ LCWT < SP-2 YES ➤ 14 LOW WATER TEMP SHUTDOWN THRESHOLD = PREVIOUS SETPOINT-2 PAGE 48 ➤ ➤ NO LCWT < PREVIOUS SP-2 YES ➤ CHECK AUXILIARY SAFETY SHUTDOWN INPUT @ TB-31 ➤ CLOSED YES…
-
CLOSED NO ➤ CYCLING SHUTDOWN-DISPLAY “DAY-TIME-MULTI-UNIT CYCLING-AUTOSTART” AS STATUS YES ➤ ➤ 17 CHECK DAILY SCHEDULE START-STOP TIMES PAGE 51 ➤ SCHEDULED FOR SHUTDOWN YES CYCLING SHUTDOWN-DISPLAY “DAY-TIME-INTERNAL CLOCKAUTOSTART” AS STATUS ➤ NO ➤ 18 ➤ PAGE 52 CHECK LOW REFRIGERANT TEMP SAFETY…
-
ENERGIZE SOLUTION PUMP (1M) (ABSORBER PUMP ON 50 HZ MODELS YIA-10E3 – YIA-14F3 WITH FRANKLIN PUMPS) ➤ ➤ < 35.5°F (1.9°C) YES DISPLAY “WARNING-LOW REFRIGERANT TEMPERATURE” ➤ NO ➤ CLOSE ALARM CONTACTS TB4-89/90 TO SOUND AUDIBLE ALARM UNTIL RESET WITH “WARNING RESET” KEY ➤ YES ➤ ➤ DE-ENERGIZE (CLOSE)…
-
< 33°F (0.5°C) ➤ NO YES ➤ SAFETY SHUTDOWN-DISPLAY “DAY-TIME-LOW REFRIGERANT TEMP-ANALOG” AS STATUS ➤ ➤ CHECK CHILLED WATER FLOW SWITCH @ TB2-12 20 PAGE 56 ➤ TRIPPED ➤ YES SAFETY SHUTDOWN-DISPLAY “DAY-TIME-CHILLED WATER FLOW SWITCH” AS STATUS NO ➤ 23 ➤ PAGE 59 CHECK STRONG SOLUTION TEMP @ RT3 ➤ >…
-
BUFFALO PUMPS YES NO ➤ EPROM VERSION A.02F.02 OR LATER NO ➤ DE-ENERGIZE (CLOSE) MOTOR COOLANT ➤ YES SOLENOID VALVE (1SOL) <150°F (65.6°C) NO YES ➤ ➤ ➤ ➤ DE-ENERGIZE (CLOSE) MOTOR COOLANT SOLENOID VALVE (1SOL) YES < PROGRAMMED OPEN THRESHOLD MINUS 10°F (–23.3°C) >160°F (71.1°C) YES ➤ ENERGIZE (OPEN)…
-
YES BUFFALO PUMPS NO ➤ CHECK PUMP MOTOR COOLANT LEVEL FLOAT SWITCH (2F) INPUT @ TB1-11 ➤ ➤ CLOSED NO SAFETY SHUTDOWN-DISPLAY “DAY-TIME-MOTOR COOLANT LEVEL FLOAT SWITCH” AS STATUS YES ➤ ➤ ➤ 26 CHECK GENERATOR HIGH PRESSURE SAFETY (HP1) INPUT @ TB1-32. CALIBRATED TO TRIP @ 13.73 PSIA (94.7 kPa) PAGE…
-
➤ CLOSE ALARM CONTACTS TB4-89/90 TO SOUND AUDIBLE ALARM UNTIL RESET WITH “WARNING RESET” KEY < 6 PSIA (41.4 kPa) ➤ YES HIGH GEN PRESSURE OVERRIDE IN EFFECT YES ➤ ➤ REMOVE “HIGH GENERATOR PRESSURE OVERRIDE” -ALLOW UNIT LOADING TO >30% STEAM/HOT WATER VALVE POSITION ➤ ➤ PUT HIGH GENERATOR PRESSURE…
-
E
F 1F & 3F OPEN (REFRIG PUMP SHUTDOWN) NO D ➤ FORM 155.16-O3 ➤ BUFFALO PUMPS NO YES ➤ ➤ YES 1F & 3F OPEN (REFRIG PUMP SHUTDOWN) NO ➤ ➤ ➤ PERFORM PRIMARY LIMITED ADC PERFORM NORMAL ADC ➤ ➤ ➤ ➤ DISPLAY “SYSTEM RUNPRIMARY LIMITED AUTO-DECRYST” ➤ ENERGIZE (OPEN) STABILIZER REFRIGERANT SOLENOID VALVE…
-
A C D ➤ ➤ ALLOW STEAM/HOT WATER VALVE LOADING TO >50% ➤ DISPLAY “SYSTEM RUNSECONDARY LMTD AUTO-DECRYST” CLEAR AUTOMATIC DECRYSTALLIZATION MESSAGE ➤ ➤ ➤ DRIVE STEAM/HOT WATER VALVE TO 0% POSITION ➤ SET ADC TIMER TO 10 MINUTES YES ➤ ➤ 15 MIN. SECONDARY LMTD ADC TIMER ELAPSED ➤ NO YES 1F & 3F CLOSED…
-
B C RTLC >72°F (22.2°C) & <97°F (36.1°C) MAX ALLOWED STRONG SOLUTION TEMP = (1.4 x RTLC) + 69.2 ➤ ➤ MAX ALLOWED STRONG SOLUTION TEMP = (1.285 x RTLC) + 80.355 ➤ ➤ MAX ALLOWED STRONG SOLUTION TEMP = (1.307 x RTLC) + 78.072 ➤ NO ➤ ➤ NO YES ➤ STRONG SOLUTION TEMP CONTROL IN EFFECT RTLC >98°F (36.7°C) &…
-
BUTTERFLY VALVE NO ➤ APPLY 2 SECOND CLOSE PULSE TO STEAM/HOT WATER VALVE EVERY 60 SECONDS UNTIL STRONG SOLUTION TEMP < (ALLOWED-4) YES ➤ APPLY 1 SECOND CLOSE PULSE TO STEAM/HOT WATER VALVE EVERY 15 SECONDS UNTIL STRONG SOLUTION TEMP < (ALLOWED-4) ➤ ➤ ➤ NO UNIT RUNNING > 30 MINUTES YES ➤ CHECK…
-
CHECK ENTERING CONDENSER WATER TEMP @ RT 5 ➤ ➤ YES ENT COND WATER TEMP WARNING IN EFFECT YES < MAX ALLOWED ENTERING COND WATER TEMP NO NO ➤ ➤ ➤ CLEAR “ENT CONDENSER WATER TEMP HIGH LIMIT WARNING MESSAGE” WHEN WARNING RESET KEY PRESSED IN SERVICE MODE > PROGRAMMED LIMIT FOR 10 MINUTES NO YES ➤ UNIT…
-
➤ CHECK ABSORBER PUMP OVERLOADS INPUT @ TB1-71 YES 50 HZ YIA-10ES YIA-14F3 WITH FRANKLIN PUMPS NO ➤ ➤ YES CHECK SOLUTION PUMP OVERLOADS INPUT @ TB1-70 OPEN NO ➤ ➤ SAFETY SHUTDOWNDISPLAY “DAYTIME-ABSORBER PUMP OVERLOADS OPEN” AS STATUS YES ➤ OPEN SAFETY SHUTDOWN-DISPLAY “DAY-TIME-SOLUTION PUMP…
-
STEAM UNIT NO ➤ CHECK HOT WATER SUPPLY TEMP @ RT7 YES ➤ ➤ CHECK STEAM SUPPLY TEMP @ RT7 JP5 IN > 270°F ➤ (132.2°C) NO YES ➤ YES JP5 IN > 255°F (123.9°C) YES ➤ NO ➤ NO YES ➤ > 340°F (171.1°C) NO YES ➤ SAFETY SHUTDOWNDISPLAY “DAY-TIME-HIGH HOT WATER SUPPLY TEMP” AS STATUS NO ➤ ➤ ➤ ➤ YES > 290°F…
-
D
E ➤ ➤ ➤ < 336°F (168.9°C) REMOVE HIGH HOT WATER TEMP WARNING ➤ NO YES ➤ NO < 284°F (140°C) YES ➤ ➤ CLEAR HIGH HOT WATER TEMP WARNING MESSAGE HIGH STEAM SUPPLY TEMP WARNING IN EFFECT YES ➤ ➤ REMOVE HIGH STEAM SUPPLY TEMP WARNING ➤ OPEN ALARM CONTACTS TB4-89/90 ➤ NO CLEAR HIGH STEAM SUPPLY WARNING…
-
CLOSE ALARM CONTACTS TB4-88/90 TO SOUND AUDIBLE ALARM ➤ ➤ NO > 25.5 PSIA (175.8 kPa) YES ➤ ➤ REMOVE HIGH STEAM SUPPLY PRESSURE WARNING YES HIGH STEAM SUPPLY PRESS WARNING IN EFFECT ➤ CLEAR HIGH STEAM SUPPLY PRESSURE WARNING MESSAGE NO ➤ ➤ OPEN ALARM CONTACTS TB4-89/90 ➤ ➤ ➤ CHECK PURGE PUMP…
-
OPER HRS. > SETPOINT YES DISPLAY “WARNINGPURGE PUMP SERVICE RECOMMENDED” ➤ ➤ NO CLOSE ALARM CONTACTS TB4-89/90 TO SOUND AUDIBLE ALARM UNTIL RESET WITH WARNING RESET KEY ➤ PRESS WARNING RESET KEY IN SERVICE MODE ➤ NO YES ➤ PRESS PURGE PUMP OPERATING HOURS TO ZERO ➤ CLEAR PURGE PUMP SERVICE WARNING…
-
CHECK BATTERY VOLTAGE ON “REAL TIME CLOCK” IC CHIP, U16 ON MICRO BOARD ➤ OK ➤ NO DISPLAY “REPLACE RTC, U16 - REPROGRAM SETPOINTS” ➤ YES CLOSE ALARM CONTACTS TB4-89/90 TO SOUND AUDIBLE ALARM UNTIL RESET WITH WARNING RESET KEY ➤ ➤ CLEAR RTC BATTERY WARNING MESSAGE WHEN WARNING RESET KEY PRESSED IN…
-
CHECK LOW REFRIGERANT TEMP SAFETY CUTOUT SWITCH - (LRT) @ RELAY BOARD TB3-81 ➤ ➤ SAFETY SHUTDOWNDISPLAY “DAY-TIME-LOW REFRIGERANT TEMPDIGITAL” AS STATUS YES TRIPPED NO ➤ PAGE 53 ➤ 21 22 PAGE 54 ➤ CHECK REFRIGERANT LEVEL FLOAT SWITCH (1F) @ TB1-10 ➤ OPEN ? ➤ YES DISPLAY “DILUTION INTERRUPTED-REF ➤…
-
< 35.5°F (1.9°C) ➤ DISPLAY “WARNINGLOW REFRIGERANT TEMPERATURE” AS STATUS YES NO ➤ CLOSE ALARM CONTACTS TB4-89/90 TO SOUND AUDIBLE ALARM UNTIL RESET WITH “WARNING RESET KEY” ➤ BUFFALO PUMPS YES NO ➤ REFRIG PUMP RUNNING NO YES ➤ ➤ ENERGIZE (OPEN) STABILIZER REFRIGERANT SOLENOID VALVE (2SOL) ➤ ➤…
-
START 30 MINUTE CHILLED WATER PUMP TIMER ➤ ➤ ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 YES REFRIG TEMP < 33°F (.6°C) NO ➤ SAFETY SHUTDOWNDISPLAY “DAY-TIME-LOW REFRIGERANT TEMPANALOG” AS STATUS ➤ ➤ PAGE 56 6 YES REFRIG TEMP > 36°F (2.2°C) ➤ NO DE-ENERGIZE (CLOSE) STABILIZER REFRIGERANT SOLENOID VALVE…
-
D
➤ ➤ ➤ NO C B ➤ FORM 155.16-O3 STEAM UNIT LOCAL OR REMOTE START BUFFALO PUMPS YES NO YES YES NO ➤ 2 ➤ PAGE 11 ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE CHECK MOTOR COOLANT LEVEL FLOAT SWITCH (2F) @ TB1-11 ➤ ➤ 5 ➤ PAGE 35 OPEN? NO SAFETY SHUTDOWNDISPLAY “DAYTIME-MOTOR ➤ COOLANT YES LEVEL…
-
➤ ➤ CHECK GENERATOR PUMP OVERLOAD INPUT @ TB1-18 CHECK REFRIGERANT PUMP OVERLOAD INPUT @ TB1-70 ➤ OPEN NO YES ➤ ➤ OPEN SAFETY SHUTDOWN-DISPLAY “DAY-TIME-GEN PUMP OVERLOADS OPEN” AS STATUS ➤ YES SAFETY SHUTDOWNDISPLAY “DAY-TIMEREFRIG PUMP OVERLOADS OPEN” AS STATUS NO ➤ 33 PAGE 71 ➤ PAGE 77 ➤ 37 CHECK…
-
➤ CHECK CONDENSER WATER FLOW SWITCH @ TB2-20 DISPLAY “DILUTION INTERRUPTED-CH WATER FLOW SW” AS STATUS ➤ ➤ TERMINATEDILUTION SHUTDOWN ALL PUMPS YES OPEN FOR 30 CONTINUOUS SECONDS ➤ NO ➤ ➤ ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE YES FLOW SWITCH CLOSED STEAM UNIT ➤ YES RESUME…
-
A ➤ ➤ RESUME DILUTIONSTART ALL PUMPS YES FLOW SWITCH CLOSED NO ➤ ➤ YES CHECK STRONG SOLUTION TEMP @ RT 3 STEAM UNIT NO ➤ NO ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE >136°F (57.8°C) ➤ ➤ LOCAL OR REMOTE START NO ➤ ➤ 5 2 PAGE 11 ➤ PAGE 35 ➤ * ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤…
-
SAFETY & CYCLING SHUTDOWN
UNIT OPERATION SUBROUTINES PAGE 11 9 ➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ ➤ LVG WATER TEMP > SETPOINT YES ➤ OPEN CYCLING STATUS CONTACTS TB4-40/41 10 ➤ 2 PAGE 11 ➤ 2 PAGE 11 PAGE 11 ➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ ➤ YES STEAM/ HOT WATER VALVE > 10% NO ➤ OPEN CYCLING STATUS…
-
PAGE 12 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ START 30 MINUTE CHILLED WATER PUMP TIMER ➤ ➤ CHILLED WATER PUMP TIMER ELAPSED YES ➤ OPEN CHILLED WATER PUMP CONTACTS TB4-44/45 NO ➤ ➤ ➤ UNIT SW IN STOP/RESET NO YES ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 ➤ NO LOCAL OR REMOTE START YES ➤ 2 PAGE 11…
-
PAGE 12 ➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ OPEN CHILLED WATER PUMP CONTACTS TB4-44/45 ➤ OPEN CONDENSER WATER PUMP CONTACTS TB4-55/56 ➤ ➤ COND FLOW SW CLOSED YES ➤ OPEN CYCLING STATUS CONTACTS TB4-40/41 NO ➤ ➤ 2 PAGE 11 UNIT SW IN STOP/RESET NO YES ➤ OPEN CYCLING STATUS CONTACTS TB4-40/41 ➤…
-
PAGE 17
13 ➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ STEAM UNIT YES ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTIONSHUTDOWN ALL PUMPS ➤ ➤ COND FLOW SW CLOSED ➤ YES OPEN CYCLING STATUS CONTACTS TB4-40/41 ➤ NO 2 ➤…
-
FORM 155.16-O3 A C B ➤ ➤ ➤ OPEN CYCLING STATUS CONTACTS TB4-40/41 NO UNIT SW IN STOP/ RESET ➤ YES ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 OPEN CYCLING STATUS CONTACTS TB4-40/41 ➤ ➤ ➤ YES ➤ NO YES ➤ 2 UNIT SW IN STOP/ RESET ➤ NO LOCAL OR REMOTE START PAGE 11 OPERATOR PRESS WARNING RESET IN SERVICE…
-
➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ LCWT > (SP + 2) YES OPEN CYCLING ➤ STATUS CONTACTS @ TB4-40/41 ➤ 2 PAGE 11 NO ➤…
-
➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ AUX SAFETY INPUT OPEN YES UNIT SW IN STOP/ RESET ➤ OPEN SAFETY ➤ STATUS CONTACTS YES…
-
➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ TB2-13 CLOSED OPEN CYCLING ➤ STATUS CONTACTS TB4-40/41 YES ➤ 2 PAGE 11 NO ➤ NO 6…
-
➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ TB2-9 CLOSED OPEN CYCLING ➤ STATUS CONTACTS TB4-40/41 YES ➤ 2 PAGE 11 NO ➤ NO 6…
-
➤ CLOSE CYCLING STATUS CONTACTS TB4-40/41 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ ➤ SCHEDULED FOR START YES OPEN CYCLING ➤ STATUS CONTACTS TB4-40/41 ➤ 2 PAGE 11 NO ➤…
-
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ 21 PAGE 36 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT YES ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS EXCEPT CHILLED WATER PUMP ➤ START 30 MINUTE CHILLED WATER…
-
A C B ➤ ➤ CHECK STRONG SOLUTION TEMP @ RT 3 START ALL PUMPS ➤ ➤ >136°F YES (57.8°C) STEAM UNIT NO YES ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ ➤ START 6-MINUTE DILUTION CYCLE TIMER DISPLAY “DAY-TIME-LRTCHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ ➤ ➤ ➤ SHUTDOWN CHILLED WATER PUMP YES…
-
D
E ➤ A ➤ FORM 155.16-O3 ➤ ➤ ➤ OPERATOR PRESS WARNING RESET KEY IN SERVICE MODE UNIT SW IN STOP/ RESET TERMINATE DILUTION – SHUTDOWN ALL PUMPS NO ➤ NO ➤ YES ➤ YES ➤ STEAM UNIT NO ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 OPEN SAFETY STATUS CONTACTS TB4-42/43 YES ➤ ➤ LOCAL OR REMOTE NO START YES ➤ ➤ 2 ➤…
-
PAGE 21
20 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE ➤ NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS EXCEPT CHILLED WATER PUMP ➤ START 30 MINUTE CHILLED WATER PUMP TIMER…
-
FORM 155.16-O3 A C B ➤ ➤ CHECK STRONG SOLUTION TEMP @ RT 3 START ALL PUMPS ➤ ➤ YES >136°F (57.8°C) STEAM UNIT NO YES ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ ➤ START 6-MINUTE DILUTION CYCLE TIMER DISPLAY “DAY-TIME-LRTCHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ ➤ ➤ ➤ SHUTDOWN CHILLED…
-
➤ A D E ➤ ➤ ➤ OPERATOR PRESS WARNING RESET KEY IN SERVICE MODE UNIT SW IN STOP/ RESET TERMINATE DILUTION – SHUTDOWN ALL PUMPS NO ➤ NO ➤ YES ➤ YES ➤ STEAM UNIT NO ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 OPEN SAFETY STATUS CONTACTS TB4-42/43 YES ➤ ➤ LOCAL OR REMOTE NO START YES ➤ ➤ 2 ➤ ➤ LOCAL OR…
-
PAGE 21
23 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT YES ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS EXCEPT CHILLED WATER ➤ START 30 MINUTE CHILLED WATER PUMP TIMER ➤ ➤…
-
A C B ➤ ➤ CHECK STRONG SOLUTION TEMP @ RT 3 START ALL PUMPS ➤ ➤ YES >136°F (57.8°C) STEAM UNIT NO YES ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ ➤ START 6-MINUTE DILUTION CYCLE TIMER DISPLAY “DAY-TIME-LRTCHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ ➤ ➤ ➤ SHUTDOWN CHILLED WATER PUMP YES…
-
D
E ➤ FORM 155.16-O3 ➤ TERMINATE DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ STEAM UNIT NO ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 OPEN SAFETY STATUS CONTACTS TB4-42/43 YES ➤ ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE LOCAL OR REMOTE NO START YES ➤ ➤ 2 PAGE 11 LOCAL OR REMOTE START ➤ NO ➤ ➤ YES ➤…
-
PAGE 22
24 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ STRONG SOLUTION TEMP <336°F (168.9°C) UNIT SW IN STOP/ RESET ➤ YES OPEN SAFETY ➤…
-
PAGE 22
25 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ PAGE 42 * ➤ ➤ HT1 MANUALLY RESET YES UNIT SW IN STOP/ RESET ➤ OPEN STATUS ➤ STATUS CONTACTS YES…
-
26 PAGE 23
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE PAGE 39 27 ➤ ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS ➤ NO ➤ ➤ ➤ ➤ EPROM VERSION A.02F.01 AND LATER ➤ YES UNIT SW…
-
➤ ➤ ➤ NO B ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ UNIT SW IN STOP/ RESET EXIT DILUTION CYCLE @ * PAGE 42 YES ➤ ➤ ➤ NO 6 MIN. DILUTION TIMER ELAPSED OPERATOR PRESS WARNING RESET KEY IN SERVICE MODE ➤ NO ➤ NO YES YES ➤ ➤ YES UNIT SW IN STOP/ RESET TERMINATE DILUTION – SHUTDOWN ALL PUMPS OPEN SAFETY STATUS…
-
PAGE 23
28 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ HIGH PRESSURE SAFETY (HP1) TRIPPED UNIT SW IN STOP/ RESET ➤ NO OPEN SAFETY ➤…
-
PAGE 23
29 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ GENERATOR PRESS (PT1) >14.99 PSIA (103.4 kPa) ➤ YES UNIT SW IN STOP/ RESET OPEN…
-
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE PAGE 39 ➤ 31 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS ➤ ➤ SOLUTION PUMP OVERLOAD CLOSED ➤ NO CHECK STRONG…
-
PUMP OVERLOAD COUNTER <2 ➤ NO ➤ YES ➤ START ALL PUMPS DISPLAY “DAY-TIMEPO-CHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ YES STEAM UNIT ➤ NO ➤ ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE SOLUTION PUMP OVERLOAD CLOSED NO ➤ YES START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ UNIT SW IN STOP/ RESET ➤ NO ➤…
-
A B ➤ ➤ ➤ ➤ NO UNIT SW IN STOP/ RESET NO 6 MIN. DILUTION TIMER ELAPSED YES YES ➤ ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 TERMINATE DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ NO LOCAL OR REMOTE START STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO YES ➤ ➤ 2 ➤ PAGE 11 ➤ UNIT SW IN…
-
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE PAGE 40 ➤ 33 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS ➤ ➤ REFRIG PUMP OVERLOAD CLOSED ➤ NO CHECK STRONG SOLUTION…
-
REFRIG PUMP OVERLOAD COUNTER <2 ➤ NO ➤ YES ➤ START ALL PUMPS DISPLAY “DAY-TIMEPO-CHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ ➤ YES STEAM UNIT NO ➤ ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE REFRIG PUMP OVERLOAD CLOSED NO ➤ YES START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ UNIT SW IN STOP/ RESET ➤ NO…
-
FORM 155.16-O3 A B ➤ ➤ ➤ ➤ NO UNIT SW IN STOP/ RESET NO 6 MIN. DILUTION TIMER ELAPSED YES YES ➤ ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 TERMINATE DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ NO LOCAL OR REMOTE START STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO YES ➤ ➤ 2 ➤ PAGE 11…
-
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE PAGE 39 ➤ 35 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS ➤ ➤ REFRIG PUMP OVERLOAD CLOSED ➤ NO CHECK STRONG SOLUTION…
-
ABSORBER PUMP OVERLOAD COUNTER <2 ➤ NO ➤ YES ➤ START ALL PUMPS DISPLAY “DAY-TIMEPO-CHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ STEAM UNIT ➤ YES NO ➤ ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE ABSORBER PUMP OVERLOAD CLOSED NO ➤ YES START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ UNIT SW IN STOP/ RESET…
-
A B ➤ ➤ ➤ ➤ NO UNIT SW IN STOP/ RESET NO 6 MIN. DILUTION TIMER ELAPSED YES YES ➤ ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 TERMINATE DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ NO LOCAL OR REMOTE START STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO YES ➤ ➤ 2 ➤ PAGE 11 ➤ UNIT SW IN…
-
➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ PAGE 40 37 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION CYCLE – SHUTDOWN ALL PUMPS ➤ ➤ GENERATOR PUMP OVERLOAD CLOSED ➤ NO CHECK STRONG…
-
GENERATOR PUMP OVERLOAD COUNTER <2 ➤ YES ➤ NO ➤ START ALL PUMPS DISPLAY “DAY-TIMEPO-CHK FOR CRYSTALLIZATION” AS STATUS ➤ ➤ ➤ YES STEAM UNIT NO ➤ ➤ ENERGIZE 6 SOL TO OPEN STEAM CONDENSATE DRAIN VALVE GENERATOR PUMP OVERLOAD CLOSED NO ➤ YES START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ UNIT SW IN STOP/…
-
FORM 155.16-O3 A B ➤ ➤ ➤ ➤ NO UNIT SW IN STOP/ RESET NO 6 MIN. DILUTION TIMER ELAPSED YES YES ➤ ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 TERMINATE DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ NO LOCAL OR REMOTE START STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO YES ➤ ➤ 2 ➤ PAGE 11…
-
PAGE 31
38 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ JP5 IN ➤ NO HOT WATER TEMP @ RT7 <269°F (128.3°C) NO YES YES ➤ ➤ HOT WATER SUPPLY @…
-
PAGE 31
39 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ JP5 IN ➤ NO STEAM TEMP @ RT7 < 339°F (170.6°C) NO YES YES ➤ ➤ STEAM SUPPLY @ RT7 <…
-
PAGE 32
40 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ START 6 MINUTE DILUTION CYCLE TIMER ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ * PAGE 42 ➤ ➤ STEAM PRESS @ PT2 > 28.9 PSIA (199.3 kPa) ➤ YES UNIT SW IN STOP/ RESET OPEN…
-
41 PAGE 35
➤ ➤ POWER RESTORED NO YES ➤ DISPLAY 10-SECOND LOCKOUT DELAY COUNTDOWN TIMER ➤ CHECK STRONG SOLUTION TEMP @ RT 3 ➤ <136°F (57.7°C) YES ➤ SAFETY SHUTDOWN – DISPLAY “DAY-TIME--PF-CHK FOR CRYSTALLIZATION” AS STATUS NO ➤ ➤ ➤ CYCLING SHUTDOWN – DISPLAY “DAY-TIME-POWER FAILURE – AUTOSTART” AS STATUS YES…
-
CLOSE SAFETY SHUTDOWN STATUS CONTACTS TB4-42/43 ➤ ➤ 10-SECOND LOCKOUT TIMER ELAPSED NO YES ➤ START 6-MINUTE DILUTION CYCLE TIMER ➤ STEAM UNIT ➤ YES ENERGIZE STEAM CONDENSATE DRAIN VALVE (6 SOL) NO ➤ ➤ ➤ ENTER DILUTION CYCLE @ 8 PAGE 35 ➤ EXIT DILUTION CYCLE @ PAGE 42 * ➤ NO UNIT SW IN STOP/ RESET NO…
-
TERMINATE DILUTION – SHUTDOWN ALL PUMPS OPEN SAFETY SHUTDOWN STATUS CONTACTS TB4-42/43 ➤ ➤ YES ➤ ➤ DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE C B STEAM UNIT LOCAL OR REMOTE START ➤ FORM 155.16-O3 NO YES NO ➤ 2 ➤ PAGE 11 ➤ ➤ UNIT SW IN STOP/ RESET NO YES ➤ OPEN SAFETY SHUTDOWN STATUS…
-
PAGE 14, 26
42 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ UNIT SW IN STOP/ RESET NO YES ➤ OPEN SAFETY STATUS CONTACTS TB4-42/43 ➤…
-
PAGE 14
43 ➤ CLOSE SAFETY STATUS CONTACTS TB4-42/43 ➤ DE-ENERGIZE 1R RELAY TO CLOSE STEAM/HOT WATER SHUTOFF VALVE ➤ STEAM UNIT ➤ YES DE-ENERGIZE 6 SOL TO CLOSE STEAM CONDENSATE DRAIN VALVE NO ➤ ➤ BYPASS DILUTION – SHUTDOWN ALL PUMPS ➤ ➤ UNIT SW IN STOP/ RESET NO YES ➤ ➤ FLOAT SWITCH CONFLICT RE- NO MOVED…
-
CONTROL CENTER
28342A(D) FIG. 1 – MICROCOMPUTER CONTROL CENTER KEYPAD The Control Center front panel layout consists of five key groups, one switch, and a I-line by 40-character alpha numeric vacuum fluorescent display (see Fig. 1). Character Display – The alphanumeric vacuum fluorescent display is located to the…
-
OPERATION
DISPLAYING SYSTEM PARAMETERS The Display keys are used to display selected monitored parameters as follows (refer to Fig. 1): • Press and release the appropriate Display key – the message will be displayed for 2 seconds. – or – • Press and hold the appropriate Display key – the message will be…
-
* *Units equipped with EPROM version A.02F.02 (or later) To initiate a PRINT to the printer: (Refer to the Instruction, Form 155.16-NO1.2 for details of the optional printers.) To display OPTIONS: The OPTIONS key is used to display any options that are installed. It is also used for the LiBr…
-
LAST 7 DAYS = XXX; TOTAL PURGES = XXXXX
Total purges in last 7 days Total purges to date over lifetime of unit LiBr CONCENTRATION CALCULATOR The concentration calculator allows the service technician to determine the concentration of any lithium bromide solution without referring to the traditional “PTX” chart. By entering a SOLUTION…
-
provides a purge pump service reminder. When the cumulative purge pump operating hours since last service equals the programmed service interval, WARNING – PURGE PUMP SERVICE RECOMMENDED is displayed on the keypad display. The service interval is programmable from 5-100 hours. The default value is…
-
day, the compressor will not automatically stop until a
scheduled time is encountered on a subsequent day. HOLIDAY – One or more of the days of the week can be designated as holidays. (See description of DAILY SCHEDULE above.) On those designated days, the chiller will automatically start and stop per the HOLIDAY start and stop times programmed in the…
-
– or –
REMOTE RESET TEMP RANGE = 20°F To display DAILY SCHEDULE setpoints: • Press and hold the DAILY SCHEDULE setpoint key. The chiller start and stop times for each day of the week are sequentially displayed, beginning with Sunday and ending with Holiday. The display will continuously scroll until the…
-
2 2,4,6,8 1,10 7 28342A(D) FIG. 3 – KEYPAD – PROGRAMMING SYSTEM SETPOINTS 9. Enter setpoints as detailed below. If you make a mistake when entering a value, press CANCEL key and then ENTER key. The display will revert to the default values and the cursor will return to the first changeable digit.…
-
4,6 28342A(D) 28342A(D) 3 2 FIG. 6 – KEYPAD – PROGRAMMING “PULL DOWN DEMAND” SETPOINT FIG. 7 – KEYPAD – PROGRAMMING “CLOCK” SETPOINT To enter PULL DOWN DEMAND setpoint. (Refer to Fig. 6.): 7. Press and release the ENTER key. 1. Press and release the PULL DOWN DEMAND setpoint key. The following…
-
28342A(D) 3,5,6 28342A(D) FIG. 8 – KEYPAD – PROGRAMMING “DAILY SCHEDULE” SETPOINT FIG. 9 – KEYPAD – PROGRAMMING “HOLIDAY” SETPOINT 5. Press the ADVANCE DAY/SCROLL key. The following prompt message is displayed. 4. After you have placed an “*” next to each of the days that you wish to designate a…
-
2 UNIT KEYS 1 28342A(D) FIG. 10 – KEYPAD – PROGRAMMING “REMOTE RESET” TEMP RANGE NOTE: In units equipped with EPROM version A.02F.00, a continuous load or unload signal is applied when the LOAD or UNLOAD key is pressed and released. If the unit is equipped with EPROM version A.02F.01 or later, each…
-
SYSTEM RUN – UNIT HOLDING
is displayed. If the system is not running, SYSTEM READY TO START – UNIT HOLDING is displayed. The unit will continue holding until the HOLD, UNLOAD, or AUTO (returns unit to automatic, leaving water temp control) key is pressed. AUTO – Press and release this key to place the unit in automatic…
-
c. Press and release the MANUAL PUMP key. The
displayed message will change from < FUNCTION > – OFF to < FUNCTION > – ON or vice versa. If selected function cannot be turned on or off, a message(s) giving the reason(s) will scroll on the display until the MANUAL PUMP key is released. Refer to “Manual Pump Operation Fault Messages” in “Display…
-
REF LEVEL UNLOADER SOLENOID – CLOSED
REMOTE LOAD LIMIT = XXX% 2 EPROM version A.02F.02 or later: STEAM VALVE POSITION = XXX% 1 HOT WATER VALVE POSITION = XXX% 1 GENERATOR SHELL PRESSURE = XX.XX% 3. Displayed only when unit is equipped with EPROM version A.02F.02 (or later) and Buffalo pumps (Micro Board program jumper JP2 in). 4.…
-
normal background message to be displayed. Pressing
the CANCEL key exits the HISTORY display. 3. Using the Entry keys, enter “9 6 7 5”. 4. As each digit is entered, the characters Y O R K are displayed. OPERATING MODES NOTE: If digits other than are entered, Y O R K is still displayed. The Millennium Control Center can be operated in four different…
-
UNIT SWITCH
SYSTEM READY TO START – UNIT HOLDING (See Fig. 11, page 98). – or – This rocker switch is used to locally operate the unit. It is used to start, run and stop the unit. Also, it resets the Control Center after a safety shutdown. To START unit in LOCAL mode: Move the UNIT switch from the STOP/RESET to…
-
SYSTEM RUN – REMOTE LOAD LIMIT
System is running in REMOTE mode and the unit loading is being inhibited by the remote load limit command from a remote device. The load limit value that is in effect can be viewed by pressing the DISPLAY DATA keypad key. One of the scrolled messages is “REMOTE LOAD LIMIT = XXX%”. The steam or hot…
-
effect, the stabilizer refrigerant solenoid valve (2SOL) is
not energized (opened) and the steam/hot water valve is driven to the closed (0%) position. If float switches 1F and 3F close to start the refrigerant pump before the “Secondary Limited ADC” terminates, a standard ADC is performed and the unit continues to run. Otherwise, a safety shutdown is…
-
SYSTEM RUN – UNIT HOLDING
The system is running in SERVICE mode. The load command is in the process of holding because the operator has pressed the HOLD key. The load command is unchanging. SWITCH, the thermal switch does not have to be reset, it automatically recloses. The motor protector is located in the power panel. The…
-
brated to trip 13.73 PSIA (94.7 kPa)
SUN 12:00 AM LOW REFRIGERANT TEMP – DIGITAL Unit has shut down because the low refrigerant temperature safety device (LRT) has opened. It is calibrated to open at 33°F (0.6 °C). It will automatically close at 37°F (2.7°C). To restart unit, press UNIT switch to STOP/ RESET position, then to START…
-
perature, as sensed by thermistor RT7, has increased
to 260°F (126.7°C). It will be allowed to restart when temperature decreases to 259°F (126.1°C). To restart unit, press UNIT switch to STOP/RESET position, then to START position. (EPROM version A.02F.01 or later) The unit has shutdown because the hot water supply temperature, as sensed by…
-
SUN 12:00 AM RFS-CHK FOR CRYSTALLIZATION
(RFS = Refrigerant Float Switch) (EPROM version A.02F.02 or later; applicable only to units equipped with Buffalo pumps, Micro Board program jumper JP2 IN) Unit has shut down because a “Secondary Limited AutoDecrystallization Cycle” was performed and completed without the refrigerant pump running.…
-
After it has been determined that crystallization has not
occurred during the shutdown, the unit can be restarted. To restart unit, press UNIT switch to STOP/RESET position, then press the WARNING RESET key in SERVICE mode, and then initiate a start. SUN 12:00 AM HIGH STEAM SUPPLY PRESSURE (Steam Units Only; not applicable to units equipped with EPROM…
-
the unit has shut down on “Low Water Temp”,
then the criterion for that restart applies. SUN 12:00 AM SYSTEM CYCLING – AUTO START A remote device (Energy Management System, time clock, etc.) connected to the REMOTE/LOCAL cycling input (TB2- 1 and 13 ) of the digital input board has shut down the unit. Relay contacts or switch connected from 1…
-
crease) until the refrigerant temperature increases to
36.0°F (2.2°C). The reset threshold is 36.0°F (2.2°C). WARNING – HIGH STEAM SUPPLY PRESSURE (Steam Units Only) WARNING – HIGH GEN PRESSURE OVERRIDE Indicates the generator pressure increased to 10.0 PSIA (68.9 kPa). The steam valve (steam units) or hot water valve (hot water units) will be driven to…
-
(EPROM version A.02F.01 and later)
Displayed when the steam supply temperature (as sensed by thermistor RT7) has increased to > the warning threshold, the warning message is automatically cleared and the alarm is automatically silenced. The actual shutdown threshold is determined by the position of Micro Board program jumper JP5. The…
-
Motor Coolant Float Switch (2F) is open. REFRIGERANT TEMP BELOW ACCEPTABLE LIMITS Indicates the solution pump is prevented from starting or a manual dilution cycle is inhibited because the refrigerant temperature (as measured by Thermistor RT8) is less than or equal to 34°F (1.1°C). UNIT SWITCH NOT…
-
NOTES
YORK INTERNATIONAL 115
-
NOTES
116 YORK INTERNATIONAL
-