YIA Single-Effect Absorption Chillers Steam And Hot Water Chillers
m Metric Conversions 120-1377 TONS (420 - 4840 kW)
-
Introduction
TURBINE COGENERATION WASTE HEAT RECOVERY INLET AIR COOLING PEAK SHAVING/COMMERCIAL COOLING Today’s environmental and energy considerations demand innovative chiller plant designs which save expensive peak load kW hours and eliminate CFC’s. In a growing number of applications with waste heat or…
-
OptiView Control Center
YIA OPTIVIEW CONTROL CENTER WITH SMARTPURGE The YORK YIA OptiView Control Center, furnished as standard on each chiller, provides the ultimate in efficiency, monitor-ing, data recording, chiller protection and operating ease. The Control Center is a factory-mounted, wired and tested state-of-the-art…
-
When the power is applied to the chiller, the HOME screen
is displayed. This screen displays a visual representation of the chiller and a collection of data detailing important operations and parameters. When the chiller is running the flow of chilled liquid is animated by the alternating shades of color moving in and out of the pipe nozzles. The primary…
-
OptiView Control Center - continued
• • System Purge The SYSTEM screen gives a general overview of common chiller parameters for both shells. This is a view of the refrigerant tank and pump. With the proper access level, this screen also serves as a gateway to controlling the Dilution Cycle. From this screen you can view the…
-
Programmable
• Max Purge per Week • Manual/Auto Restart After Power Failure • Refrigerant Pump Shutdown Time Setpoint • Percent Valve Open • Low Leaving Chilled Liquid Offset • Pulldown Demand Limit • Pulldown Loading StopSetpoint • Pulldown Loading Sart Setpoint • Pulldown Interval Timer • Ramp Down Interval…
-
OptiView Control Center - continued
• • Print Details Print File Navigation • Home • Trending • Safeties • Cycling • Inhibit • Warnings • Last Normal Stop Also under the History screen is the TRENDING screen, accessible by the key marked the same. On this screen up to 6 operator-selected parameters selected from a list of over 140…
-
Run Messages include
• ADC in progress – load Limit to 50% • Cooling Start Sequence Initiated • Dilution Cycle is in progress • High Concentration Control in Effect • Leaving Chilled Liquid Temperature Control in Effect • Primary Limited ADC in Progress – Load set to 50% • Secondary Limited ADC in Progress • Unit Load…
-
Reliability Features
FIG. 1 – SINGLE-STAGE ABSORPTION CHILLER RELIABILITY FEATURES The YORK OptiView w/SmartPurge YIA Absorption Chiller introduces a revolutionary system of unit controls and mechanical devices designed to keep the chiller running in even the most extreme circumstances. Old concerns about…
-
10. Load Inhibition – Before the YIA unit shuts down due
to a given safety condition (see Controls section for a complete list), it first crosses a warning threshold which will cause the panel to limit heat input to the machine. In this manner, the YIA unit continues its vital task of making chilled water, while allowing operators the opportunity to find…
-
Reliability Features - continued
Available Capacity at Varying Tower Water Temperature 110 Percent Cooling (tons) °F 45 °C 7.22 50 10.00 55 12.78 60 15.56 65 18.33 70 21.11 Condenser Water Temperature to Absorber 12 JOHNSON CONTROLS
-
INTENTIONALLY LEFT BLANK
JOHNSON CONTROLS 13
-
How It Works
FORM 155.16-EG3 (1010) FIG. 2 – STANDARD STEAM/HOT WATER CYCLE DIAGRAM 14 JOHNSON CONTROLS
-
ELIMINATOR
BAFFLES FORM 155.16-EG3 (1010) The single effect absorption cycle uses water as the refrigerant and lithium bromide as the absorbent. It is the TEMP. strong affinity that these two substances have for one SENSOR another that makes the cycle work. The entire process occurs in almost a complete…
-
Mechanical Specifications
The mechanical features listed here apply to chillers sold in North America. Some of the features may differ on chillers delivered to other regions. Among those differences are the method of chiller shipment preparation and the types of piping interface. The YORK YIA Absorption Liquid Chiller is…
-
STABILIZER VALVE
A solenoid actuated valve sends refrigerant water into the solution heat exchanger circuit in order to combat any minor crystallization. UNLOADER VALVE Steam – The valve is a cage type (for low steam mass flow) with a cast iron body or butterfly type (high steam mass flow) with a carbon steel body.…
-
Mechanical Specifications - continued
FORM 155.16-EG3 (1010) PAINT SHIPMENT Exterior surfaces are protected by a single finish coat of Caribbean blue, air drying, high solids, enamel machinery paint. The entire chiller will be shrink wrapped using a 12.0 mil thick, 5 ply, cord reinforced, UV stabilized protective covering. Water nozzles…
-
Optional Features
SPECIAL TUBE MATERIALS AND WALL THICKNESSES YIA units are designed for long life with the standard tube materials and wall thicknesses in each heat exchanger. For special applications where different tube specifications are required, YORK offers a wide array of copper and copper-nickel tubing of…
-
Application Data
The following discussion is a guide for the application and installation of YIA Single-Effect Absorption Chillers to ensure reliable, trouble free life for which this equipment was designed. LOCATION YIA units make very little noise or vibration and may generally be located at any level in a…
-
on chiller nozzles and components. Hangers must allow
for alignment of the pipe. Isolators in the piping and in the hangers are highly desirable in achieving sound and vibration control. Convenience Considerations – With a view to facilitating the performance of routine maintenance work, some or all of the following steps may be taken by the purchaser.…
-
STEAM AND CONDENSATE THEORY
Saturation Temperature The temperature at which a fluid changes from the liquid phase to the vapor phase, or conversely, from the vapor phase to the liquid phase is called the saturation temperature. A liquid at the saturation temperature is called a saturated liquid and a vapor at the saturation…
-
To determine the total heat content contained in a quantity of steam multiply the specific enthalpy by the mass of the steam. seen is equivalent to saturated steam with a quality of 1.0 (100% vapor). It is important to note that as the quality decreases, the heat content of the steam also decreases.…
-
be nearly as much as if the design steam valve pressure
drop is low. For a 3 PSIG (21 kPa) design steam valve pressure drop, one can expect about a 50% increase in steam demand on start up. If the design were based on a 4 PSIG (28 kPa) steam valve pressure drop, the increase in start up demand would be around 35% above normal. Likewise, a 2 PSIG (14 kPa)…
-
purities may manifest themselves in the form of dirt, rust
or precipitates. This strainer will prevent chiller system components from getting plugged. Plugged components will reduce system capacity and increase maintenance costs. A pressure gauge must be installed before and after the steam strainer. If the pressure drop as read from these two gauges…
-
Vacuum Breaker (If Desired) – A vacuum breaker will
often not be necessary, but they can prevent condensate build up in the generator section of the chiller at part load. A discussion of the chillers operation and the function of the vacuum breaker follows: after the trap for necessary maintenance; and a full size bypass provided with globe valve for…
-
TABLE 2 – YIA CHILLER SHELL AND TUBE VOLUMES
SHELL SIDE MODEL YIA-ST 1A1 1A2 2A3 2A4 2B1 3B2 3B3 4B4 4C1 5C2 5C3 6C4 7D1 7D2 8D3 8E1 9E2 10E3 12F1 13F2 14F3 GEN/COND TUBE SIDE ABS/EVAP ABSORBER EVAPORATOR GENERATOR CONDENSER US US US US US US LITERS LITERS LITERS LITERS LITERS LITERS GALLONS GALLONS GALLONS GALLONS GALLONS GALLONS 1004 1130…
-
Three basic types of return systems are possible: (1) a
completely atmospheric system; (2) a system that allows the chiller and steam traps to function at atmospheric pressure, but the remainder of the condensate system/ boiler feed to operate in a vacuum; (3) and a system that FORM 155.16-EG3 (1010) quires a float controlled pump to move condensate from…
-
as detailed under condensate cooler in the component
details section. It must be sized to cool the maximum flow to a temperature 5-10°F (3-6°C) below the saturation point of the vacuum return system. A condensate cooler must be provided in the line between the steam trap and the auxiliary receiver, as detailed under condensate cooler in the component…
-
FLOAT AND THERMOSTATIC
TYPE STEAM TRAP(S) STOP VALVE THERMOSTATIC TRAP AIR COOLANT 12" MIN. CHECK VALVE CONDENSATE, FLASH STEAM AND AIR CONDENSATE COOLER GENERATOR CONDENSATE OUTLET CONDENSATE AND AIR TO VACUUM CONDENSATE PUMP FIG.6 – SYSTEM 3: VACUUM CONDENSATE RETURN SYSTEM. by installing a check valve in the return hot…
-
1) Manual isolation valves
2) Hot water (diverging) control valve 3) Check valve PI = pressure indicator TI = Temperature indicator To chiller supply Valve Operation input By-pass valve section view here 2 24” (620 mm) minimum vertical rise Hot water supply 1 Hot water return PI TI 3 PI Check Valve with ¾” By-pass FIG. 7…
-
1 Manual block valves
-
TABLE 5 – APPROXIMATE INSULATION FOR HOT AND COLD SURFACES – ENGLISH MEASURE
COLD SURFACES COLD SURFACES HOT SURFACES EVAP REFRIG SUCTION SUCTION EVAP. REFRIG HEADS OUTLET & DISCHARGE & DISCHARGE UPPER GEN. MODEL MODEL HEADS & OUTLET & BOX & LINES – YIA YIA END BOX & LINES –TUBULAR SHELL HEADS END PUMP TUBULAR INSUL SHEETS PUMP SQ. FT. SQ. FT. SHEETS SQ. FT. SQ. FT. DIA.…
-
TABLE 7 – TUBE SIDE FLUID VOLUMES
Model Size 1A1 1A2 2A3 2A4 2B1 3B2 3B3 4B4 4C1 5C2 5C3 34 Tube Wall Thickness 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025…
-
TABLE 7 – TUBE SIDE FLUID VOLUMES -CONT
Model Size 6C4 7D1 7D2 8D3 8E1 9E2 10E3 12F1 13F2 14F3 Tube Wall Thickness 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025 0.028 0.035 0.049 0.022 0.025…
-
TABLE 8 – WATER BOX FLUID VOLUMES
Water Box Fluid Volumes Family Evaporator A B C D E F Passes Compact 150 psi GPM Compact 300 psi Liters GPM Liters Marine 150 psi GPM Liters 106.29 1 8.4 31.75 8.1 30.67 28.1 2 6.0 22.64 5.7 21.57 28.1 90.86 3 6.0 22.64 5.7 21.57 28.1 90.86 4 6.0 22.64 5.7 21.57 28.1 106.29 1 9.8 37.00 9.4 35.74…
-
TABLE 8 – WATER BOX FLUID VOLUMES - CONT
Water Box Fluid Volumes Family Evaporator E F Passes Compact 150 psi GPM Compact 300 psi Liters GPM Liters Marine 150 psi GPM Liters 1 54.2 205.32 201.97 572.90 2 51.3 194.34 190.99 565.10 1 74.5 281.96 278.16 811.30 2 74.5 281.96 278.16 811.30 Condenser A 1 B 4.1 15.57 15.01 44.62 6.8 25.76 25.06…
-
TABLE 9 – FLUID FLOW RATES LIMITS - BASED UPON STANDARD TUBES
Minimum and Maximum Flow Rates (GPM) 1 Pass Min Max Evaporator 2 Pass 3 Pass Min Max Min Max 4 Pass Min Max Absorber/Condenser 1 Pass 2 Pass 3 Pass Min Max Min Max Min Max Generator (HW Only) 1 Pass 2 Pass 3 Pass Min Max Min Max Min Max 1A1, 1A2 432 1556 2A3,2A4 432 1556 Model Number 2B1 583 2101…
-
TABLE 9 – FLUID FLOW RATES LIMITS - BASED UPON STANDARD TUBES - CONT
-
Ratings
-
90 CONDENSER WATER TEMPERAT PERCENT DESIGN ENERGY IN PERCENT DESIGN LOAD FIG. 10 – TYPICAL PART LOAD ENERGY CONSUMPTION – STANDARD UNIT 160 Percent of Full Load Capacity (tons) 140 Consumption Capacity Time (in minutes) FIG. 11 – TYPICAL PART LOAD ENERGY CONSUMPTION – STANDARD UNIT JOHNSON CONTROLS…
-
Ratings - continued FIG. 12 – TYPICAL CHILLER COOLING CAPACITY FOR REQUIRED LCHWT FIG. 13 – TYPICAL CHILLER COOLING CAPACITY FOR AVAILABLE STEAM INLET PRESSURE FIG. 14 – TYPICAL CHILLER STEAM CONSUMPTION FOR LCHWT 42 JOHNSON CONTROLS
-
Example COP Calculation
In SI Metric, the formula is: COP for an absorption chiller is calculated with the following equation: IPLV or = 0.01A + 0.42B + 0.45C + 0.12D APLV COP = Q output = Capacity (tons) • 12,000 (Btuh / ton) Q input Mass Flow • Enthalpy The example chiller has the following operating conditions: Capacity…
-
Nozzle Arrangements
LEFT END STEAM INLET FIG. 15 – STEAM CHILLER NOZZLE ARRANGEMENTS LEFT END HOT WATER INLET FIG. 16 – HOT WATER CHILLER NOZZLE ARRANGEMENTS 44 JOHNSON CONTROLS
-
TABLE 14 – EVAPORATOR PASS ARRANGEMENTS
-
Physical Data
BB G CONTROL PANEL LEFT END AA RIGHT END LD00688(R) FIG. 17 – UNIT DIMENSIONS 46 JOHNSON CONTROLS
-
TABLE 17 –DIMENSIONS (ENGLISH)
-
Physical Data - continued
-
Electrical Data
TABLE 18 – ELECTRICAL RATINGS Chiller Model 1A1 1A2 2A3 2A4 2B1 3B2 3B3 4B4 4C1 5C2 Voltage (VoltsPh-Hz) 200/208-3-60 230-3-60 380-3-50 400-3-50 460-3-60 575-3-60 200/208-3-60 230-3-60 380-3-50 400-3-50 460-3-60 575-3-60 200/208-3-60 230-3-60 380-3-50 400-3-50 460-3-60 575-3-60 200/208-3-60 230-3-60…
-
Electrical Data - continued
TABLE 18 – ELECTRICAL RATINGS - CONT. Chiller Model 6C4 7D1 7D2 8D3 8E1 9E2 10E3 12F1 Voltage (VoltsPh-Hz) Solution Pump Refrigerant Pump Purge Pump Minimum Circuit Ampacity LRA Disconnect Switch (Customer supplied) Max-Dual Elem. Fuse (Customer supplied) Total KW FLA LRA FLA LRA FLA 200/208-3-60…
-
Guide Specifications
GENERAL Provide Single-Stage Steam (or Hot Water) Absorption Chiller(s) capable of producing chilled water per the capacities shown on drawings and schedules. Chiller shall be capable of starting and operating at entering condenser water temperatures as low as 45°F (7.2°C). Each chiller shall be of…
-
Guide Specifications - continued
eration. Non-condensibles shall be drawn from a purge header located in the absorber and removed through the operation of an electric vacuum pump. The purge pump shall be of an oil rotary single-stage design, and shall be furnished complete with a ½ hp (0.68 kW), 3-Phase TEFC motor, and all required…
-
• • • • • • • Solution concentration Indication of refrigerant/solution/purge pump operation Operating hours Number of starts Number of Purge Cycles (last 7 days and total cumulative) Inlet steam or hot water temperature Steam or hot water valve actuator potentiometer position (in %) Generator shell…
-
Guide Specifications - continued
operating commands to the control center including but not limited to the following: • • • Remote unit start/stop Remote chilled water temperature reset Remote steam limit input The OptiView Control Panel shall also be capable of providing a limited interface to other building automation systems…
-
JOHNSON CONTROLS
-
Form 155.16-EG3 (1010) New Release