ITALIANO
ENGLISH 260RK - 320RK ISTRUZIONI INTERFACCIA UTENTE CONTROLLER MANUAL
-
LACK OF VOLTAGE 28 23.15 UTILITIES BLOCK ALARM TABLE 28 24.MODBUS VARIABLES 29 5
-
1. PURPOSE AND CONTENT OF THE MANUAL
The purpose of the control manual for 260RK-320RK units is to provide the essential information necessary for the correct use of all the functions of the machine, in particular, it provides the essential information for the setup of unit control. The informations contained in this manual are written…
-
IS PROHIBITED
To remove and/or to manipulating any safety device. Unauthorised access to the electrical panel. To touch the systems if not autorised to do so. To performe any cleaning operation when the master switch in ‘ON’ To pull, detach or twist the appliance’s electric cable. To step on, sit down on and/or…
-
DISPLAY 4.1.1 KEYS Select the operating mode and manually reset any alarms. Each time you press the key you have the following sequence: OFF -> COOL -> COOL+SAN* -> HEAT -> HEAT+SAN* -> OFF During parameter settig has the function of the back key. (*= if sanitary is enabled) Allows to enter the…
-
MENU The items controlled by the main menu are listed below. Some of this are only visible to the installer, who must access to the PSS menu to enter the password and enable higher privilege access. MENU Setpoint Password Alarms Probes Digital inputs Parameters Hours of operation Alarm log Firmaware…
-
DIGITAL INPUTS MENU [Id] Entering with the installer password, the status of the digital inputs can be view in this menu: 0 = input disabled 1 = input enabled = input not configured It is strictly PROHIBITED to disable the digital input ID1, corresponding to the flow switch. 4.8 PARAMETERS MENU…
-
Power up the unit, setting the mains witch to the ON position;
Access the firmware update menu and start the procedure through the following sequence: PRG -> PSS -> PRG -> (enter installer password) -> PRG -> USB -> UPPA -> PRG 6. A countdown advances on the display, at the end of the procedure the word "boot" appears and the 4 LEDs light up in sequence; 7.…
-
EXAMPLE: consider that we want to obtain the following conditions in heating mode
• set-point of 28°C with external temperature of 18°C • set-point of 45°C with external temperature of 2°C Set Hea = 28 e b08 = 1, while the other parameters will be calculated as follows: • b10 = 45 – 28 = 17 • b12 = 18 • b14 = 2 – 18 = -16 EXAMPLE: consider that we want to obtain the following…
-
NOTE
The circulator switches off immediately in case of a pump blockage alarm, including a manual reset flow switch alarm The circulator remains on with automatic reset flow switch alarm even if the compressor is switched off. The circulator is always switched on if the anti-freeze resistors are…
-
PROPORTIONAL REGULATION
Speed [%] P06/P09 P07 P08 ΔT [°C] P10 In practice, in cooling mode, if the temperature difference between the inlet and outlet is greater than P09 + P10, the circulator runs at maximum speed, but if the difference is less than P09 - 0.2°C, it runs at minimum speed; in the remaining cases, the pump…
-
• The compressor shutdown is set by the parameter b05: the compressor shutdown when Tw,out < Tw,out,set - b05 • The compressor restart when Tw,out > (Tw,out,set + ∆T,set + b25) EXCEPTION: se ∆T,set > 8°C, the compressors restart when the discharge probe temperature is lower than the setpoint…
-
VALUE
0 (default) Function Function disabled Function active in heating and cooling mode. The remote on/off function does not disable DHW production. Function active in heating and cooling mode. The remote on/off function disables DHW production. Function active only in heating mode The remote on/off…
-
DHW CALL FROM DIGITAL INPUT If DHW operation is enabled and parameter H51 = 28, is set, as an alternative to using the DHW temperature probe (H17 = 0), the DHW function can be activated by closing/opening digital input DI7. The unit goes into DHW mode when the contact closes and exits DHW production…
-
VALUE
L02 L03 Function Function not active Enable Hz minimum Function not active Function active only in cooling mode Function active only in heating mode Function active only in sanitary mode Function active in cooling and sanitary mode Function active in heating and sanitary mode Function in cooling and…
-
INTEGRATION RESISTANCE SELECTION MODE The resistors can be activated simultaneously if r14 = 0 (default), otherwise the priority of the order of activation of the system-side and DHWside integration resistors can be set, in particular the configurations are: • r14 = 1 for resistance activation in…
-
INTEGRATION LOGIC
Outside temp. Heat pump STANDARD WORKING r22 Heat pump + Boiler/Heater JOINT OPERATION I ZONE r28 Boiler + Heat pump/Heater JOINT OPERATION II ZONE r08 Boiler/Heater OPERATION IN SUBSTITUTION If it is necessary to change the values of the parameters, the formula r22 ≥ r28 ≥ r08 must be followed.…
-
NOTE: in the event of water-side antifreeze protection, the circulator is still activated (or kept active). 18.12 OPERATING BANDS The possible configurations of the integration parameters are listed in tables 1,2,3 and 4 shown below, divided by operating brackets (In the boxes relating to the…
-
TABLE 2. JOINT OPERATION, BRACKET 1
INTERVENTION ORDER STATUS 1) Heat pump 2) After r16 minuti, boiler 3) After further r16 minutes, system in- HEAT+SAN tegration resistence 1) Heat pump HEAT / 2) After r12 minutes, system/DHW inteHEAT+SAN gration resistence 1) Heat pump 2) After r12 minutes, boiler HEAT / HEAT+SAN 1) Heat pump 2)…
-
TABLE 4. OPERATIO IN SUBSTITUTION
INTERVENTION ORDER 1) Sanitary integration heater 2) After r12 minutes, boiler STATUS OPERATION r10 r15 r12 r16 r23 r24 HEAT+SAN SANITARIO 0/1 0/1/2 / Set the minutes 2/3 2/3 HEAT/SANITARY 0/1 0/1/2 Set the minutes Set the minutes 6 3 HEAT/SANITARY 0/1 0/1/2 Set the minutes Set the minutes 3 3 1)…
-
In this way the heat pump will stop at the set point and the thermal jump, according to the set offset, will be borne by the boiler and/or the integration resistors. 19. ANTIFREEZE PROTECTION RESISTANCES (IF KA ACCESSORY IS PRESENT) In units with KA accessory, this function is active from the…
-
Description
Unit Default Range Visibility Coo Hea First cooling setpoint First heating setpoint °C °C 7.0 45.0 25÷Coo2 Hea2÷H01 U U San Sanitary setpoint °C 48.0 25÷H01 U Coo2 Hea2 18.0 35.0 Coo÷25 25÷Hea U U 60.0 -50÷80 I 5.0 -50÷80 I 0 0÷6 I H17 Second cooling setpoint °C Second heating setpoint °C Maximum…
-
b08
b09 b10 Description Unit P02 Enable dinamic setting / Maximum cooling offset °C Maximum heating offset °C Cooling outdoor tempera°C ture setting Heating outdoor tempera°C ture setting Cooling temperature delta °C Heating temperature delta °C 0-10V analogue input set°C ting decalibration band Input…
-
Description
Unit r22 Upper limit Joint function I °C band r23 r24 Type of boiler use / Type of use integration re/ sistors r28 Upper limit for joint opera- °C tion 2nd band Default Range -16÷50 I Respect r22 ≥ r28 ≥ r08 6 0÷6 I See par. 18.6 3 0÷3 I See par.18 -7 -16÷50 I Respect r22 ≥ r28 ≥ r08 0 0÷100 I See…
-
[E691÷E701] TRANSDUCER ALARMS The alarm is activated if the relevant pressure transducers are faulty or disconnected. This alarm is manual reset. 23.6 [E801] INVERTER TIMEOUT When the on-board control does not communicate with the compressor driver board, a time-out alarm is activated to avoid…
-
Alarm code
E042 E050 E611 E621 E631 E641 E651 E661 E671 E691 E701 E711 E801 E851 E861 E871 E881 E891 E901 E911 E921 E931 E941 E951 E961 E971 DESCRIPTION Insufficient heat exchange alarm High DHW tank temperature alarm Water inlet probe failure Water outlet probe failure Compressor suction probe failure…
-
23 VARIABLES MODBUS
The control has the following modbus configuiration by def ault: BAUD RATE PARITA' DATA BIT BIT DI STOP DEVICE ID 9600 EVEN To configure the Modbus communication according to your needs, you need to modify the following registers: H124 : BAUD RATE 0 4800 1 9600 2 19200 3 38400 H125 : PARITA', STOP…
-
Bit
R/W Range Descripon Note - W - Name (2) Heang - W - (4) Only Sanitary¹ - W - (5) Cooling + Sanitary¹ unexpected operaons, so keep only those values that are allowed in wring. - W - (6) Heang + Sanitary¹ 7201 BIT MASK 1 R/W - Enablement of wring the machine status remotely 7203 °C/10 - R/W 5.0 ÷ 23.0…
-
Bit
R/W Range 315 ora - R - compressor 2 circuit 2 317 ora - R - compressor 3 circuit 2 253 °C/10 - R - evaporaon 254 °C/10 - R - 626 °C/10 - R - 627 °C/10 - R - condensaon circuit 2 400 °C/10 - R - Water inlet 401 °C/10 - R - Water outlet 405 °C/10 - R - DWH 422 °C/10 - R - Compressors inhalaon 428…
-
Format Bit Descripon Note 2 High discharge temperature of Cp2 E019 3 Inverted pressure transducers E020 6 Compressor 3 thermal protecon E023 7 Fan 3 thermal protecon E024 9 Pump 2 thermal protecon E026 11 incongruous temperatures E041 12 Poor heat exchange DHW E042 13 DHW accumulaon tank in high…
-
Format BIT MASK Descripon Note 2 Link inverter 2 E802 3 Link inverter 3 E803 4 Hardware fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature inverter 1…
-
Bit
R/W Range Name Descripon ¹⁾ if enabled ²⁾ the cycle is acvated only if the DHW (4-5-6) status is terminated by the machine. ³⁾ if the read value is equal to 32766 the probe is not configured, if 32767 the probe is faulty ͍ ⁾ reset alarms, write the value 0 with thecommand 6 on any of the registers of…
-