WIRED CONTROLLER
MODULAR CHILLER USER MANUAL KJRM-120H AIR CONDITIONING
-
● This manual gives detailed description of the precautions
that should be brought to your attention during operation. ● In order to ensure correct service of the wire controller please read this manual carefully before using the unit. ● For convenience of future reference, keep this manual after reading it.
-
Contents
1 Safety Precautions 1 2 Overview of Wired Controller 3 3 Menu Operations 5
-
1 Safety Precautions
The product and Operation and Installation Instructions record the following content, including the operation method, how to prevent harms to others and property losses, and how to use the product correctly and safely. Read the text after understanding the content (identification and marker maps)…
-
1 Safety Precautions
Name Icon It indicates "prohibited". The specific content of prohibition is provided using graphics or text in the icon or nearby. It indicates "mandatory". The specific mandatory content is provided using graphics or text in the icon or nearby. Entrust your distributor or a professional to install…
-
2 Overview of Wired Controller
Enter the menu structure from the home page Turn on or off the space operation mode Navigate the cursor on the display/navigate in the menu structure/ adjust the settings Come back to the up level Go to the next step when programming a schedule in the menu structure / confirm a selection/enter a…
-
2 Overview of Wired Controller
Set temperature Number of parallel units Heating mode Cooling mode A 09/20/2015 Auto mode COOL WEEKLY TIME icon 20 WEEKLY TIMER ON MON 10:35 A C ONLINE UNITES 16 TIMER ON Timer icon Alarm icon Number of parallel units Lock icon Compressor operating Silent mode on Fan on Centralized control access of…
-
3 Menu Operations
3.3 Setting Mode In Unlock mode, press the "MENU" button to enter the menu setting interface, press the "▼" and "▲" buttons to select "MODE" and set a mode, and press the "OK" button as shown in the above figure to access the submenu (mode setting). As shown below: Three modes available. 3.1…
-
c. Water pump mode
USER MENU QUERY 09.20.2015 MON10:35 A TEMP PUMP SILENCE SWITCH OK Select "QUERY" to access the query function. The interface and operation are as follows: When the current mode button is selected (blinking), press "◄" and "►" to set a mode or temperature, and then press "▼" and "▲" to adjust the…
-
UNIT 07#
TEMP QUERY QUERY STATE QUERY OUT-LET WATER TEMP. IN-LET WATER TEMP. AMBIENT TEMP. 25 C 25 C 25 C TEMP QUERY CURRENT ERROR QUERY OK OK ◆ State query: ◆ Current error: Select "STATE QUERY", and press the "OK" button to enter the interface. The interface display is as follows: STATE QUERY Select…
-
CURRENT ERROR QUERY
UNIT 07# DAILY TIMER CURRENT ERROR CODE ACT T. ON T. OFF MODE TEMP. ON 00:00 A 00:00 A HEAT 18 C ON 00:00 A 00:00 A HEAT 18 C E5 BACK OK ◆ Setting the timer: When the cursor stays at "ACT", press the "▲" and "▼" buttons to select the parameter value "OFF" (default value, indicating that the timer of…
-
Timer1 and Timer1 OFF is set to 15:00, then the values of Timer2 ON and Time2 OFF can be accessed in the range of 12:00-15:00. If timing intervals cross each other, the timed-on signal is sent in the case of Timer ON, and the timed-off signal is sent in the case of Timer OFF. After timer setting is…
-
◆ Setting date/time
TIME Select "DATE AND TIME", and press the "OK" button to enter the interface. The interface display is as follows: DATE AND TIME DATE HOUR MINUTE AM/PM 7 00 PM OK Operation instructions: Press the "◄" and "►" buttons to select year, month and date, press the "▲" and "▼" buttons to adjust the…
-
the setting and return to the previous
interface,press the "BACK" button to cancel the setting and return to the previous interface. CANCEL DAILY TIMER CANCEL DAILY TIMER? YES ◆ Silent mode switch: Select "SILENCE SWITCH", and press the "OK" button to enter the interface. The interface display is as follows: OK Press the "▲" and "▼"…
-
PROJECT MENU
3.5 Setting PROJECT MENU SORRY, WRONY PASSWORD, PLEASE INPUT AGAIN. ◆ Entering the password: 0 Select "PROJECT MENU", and press the "OK" button to enter the menu. The screen prompts the user to enter the password, as shown below: OK PROJECT MENU The query interface as follows is displayed if the…
-
◆ State query
◆ Parameters query: Select "PARAMETERS QUERY", and press the "OK" button to enter the interface. The screen prompts the user to select the address for query, as shown below: Select "STATE QUERY", and press the "OK" button to enter the interface. The screen prompts the user to select the address for…
-
PARAMERERS QUERY
MANUAL DEFROST 7# LOW PRESSURE ANTI-FREEZE TEMP 95 95 SELECT THE QUERING ADDRESS 07 OK 2/3 BACK PARAMERERS QUERY 7# CONDENSOR PIPE TEMP DISCHARGE TEMP 95 60 BACK Press the "▼" and "▲" buttons to select the module address to view (the offline address is skipped automatically), and press the "OK"…
-
b. Setting the silent mode
Select "SILENT MENU", and press the "OK" button to enter the interface. The interface display is as follows: SILENT SETTING STANDARD MODE SILENT MODE SILENT SETTING NIGHT SILENT MODE RUN SILENT MODE? SUPER SILENT MODE YES OK Press the "▼" and "▲" buttons to select the option to enter, and press the…
-
Press the "◄" and "►" buttons to select the
night silent mode I/II/III/IV, press the "▼" and "▲" buttons to change the set status, and press the "OK" button to save the setting and go back to the previous interface; or press the "BACK" button to go back to the previous menu. HISTORY ERROR SELECT THE QUERING ADDRESS 07 d. Setting the super…
-
3.6 Setting SERVICE MENU
HISTORY ERROR 1 E5 19/03/2015 06:30A 2 E5 19/03/2015 06:30A 3 E5 19/03/2015 06:30A 4 E5 19/03/2015 06:30A ◆ Entering the password: Select "SERVICE MENU", and press the "OK" button to enter the interface. The screen prompts the user to enter the password, as shown below: SERVICE MENU BACK PLEASE…
-
SERVICE MENU
SERVICE MENU SORRY, WRONY PASSWORD, PLEASE INPUT AGAIN. 3/4 OPEN THE FIRST REFRIGERATI ON UNIT SET PROPORTI ON 0 OPEN THE FIEST HEATING UNIT SET PROPORTI DELAY OFF TIME FOR WATER PUMP OK OK The query interface as follows is displayed if the input is correct: SERVICE MENU 4/4 EAH ON TEMP. SERVICE…
-
c. Exit defrost temperature
Select "EXIT DEFROST TEMP", and press the "OK" button to enter the interface. The interface display is as follows: SERVICE MENU DEFROST CYCLE 35 MIN SERVICE MENU EXIT DEFROSTING TEMP. 0C OK Press the "▼" and "▲" buttons to adjust the parameter, and press the "OK" button to save the setting and…
-
the setting and return to the previous interface
Press the "BACK" button to cancel the setting and return to the previous interface. SERVICE MENU HYSTERESIS TEMP. 2C e. Capacity adjust cycle: Select "CAP ADJUST CYCLE", and press the "OK" button to enter the interface. The interface display is as follows: OK Press the "▼" and "▲" buttons to adjust…
-
parameter, and press the "OK" button to
save the setting and return to the previous interface. Press the "BACK" button to cancel the setting and return to the previous interface. SERVICE MENU REFRIGERATION PROPORATION 50% h. Anti-freezing temperature of low temperature outlet water: Select "ANTI-FREEZING TEMP OF LOW TEMP OUTLET WATER"…
-
m. Temperature of stopping electric auxiliary
heating: Select "EAH OFF TEMP", and press the "OK" button to enter the interface. The interface display is as follows: SERVICE MENU DELAY OFF TIME FOR WATER PUMP 2 MIN SERVICE MENU EAH OFF TEMP. OK 0C Press the "▼" and "▲" buttons to adjust the parameter, and press the "OK" button to save the…
-
the setting and return to the previous
interface. CHECK MENU SELECT THE QUERING ADDRESS 07 o. Setting temperature difference protection of inlet and outlet water: Select "TEMP. DIFFERENCE OF WATER INLET AND OUTLET PROTECTION VALUE", and press the "OK" button to enter the interface. The interface display is as follows: OK The user first…
-
CHECK MENU
OUT-LET WATER IN-LET WATER TEMP. TEMP. 6C Press the "◄" and "►" buttons to switch the interface display. 2/4 25 C ANTI-FREE TEMP. 3.7 Setting Wired Controller Address Press the "MENU" and "►" buttons for 3s at the same time to access wired controller address selection, and press the "▲" and "▼"…
-
4) Start point of data sharing: After the
power-on/off button is pressed, data can be shared during parameter adjustment. The "OK" button must be pressed after parameters are adjusted, and the finally adjusted values will be shared. 5) Since the bus is processed in the polling mode, the data of the wired controller with the minimum number…
-
6 INSTALLATION MANUAL
6.1 Safety precaution Read the safety precautions carefully before installing the unit. Stated below are important safety issues that must be obeyed. Conform there is no abnormal phenomena during test operation after complete, then hand the manual to the user. Meaning of marks: WARNING Means…
-
CAUTION
Do not install the unit in a place vulnerable to leakage of flammable gases. Once flammable gases are leaked and left around the wire controller, fire may occure. The wiring should adapt to the wire controller current. Otherwise, electric leakage or heating may occur and result in fire. The…
-
Name
Qty. 1 Wire controller Cross round head wood mounting screw Cross round head mounting screw Remarks 3 GB950-86 M4X20 (For Mounting on the Wall) 2 M4X25 GB823-88 (For Mounting on the Electrical Switch Box) 4 Installation & Owner's Manual 1 5 Plastic bolt 2 This accessory is used when install the…
-
6.2.3 Note to installation of wire controller
1) This installation manual contains information about the procedure of installing Wired Remote Controller. Please refer to Indoor Unit Installation Manual for connecting between Wired Remote Controller and Indoor Unit. 2) Circuit of Wired Remote Controller is low voltage circuit. Never connect it…
-
6.3.1 Structure size figure
-
6.3.2 Wiring
-
6.3.3 Back cover installation
Buckling position Back cover Front cover Straight head screwdriver Screw hole installed on the wall,use three GB950-86 M4X20 32
-
Screw hole fixed on the wall,use
one GB950-86 M4X20 Screw hole installed on 86 Electrician box, use two M4X25 GB823-88 Back cover Signal switching wires 33
-
1) Use straight head screwdriver to insert into
the buckling position in the bottom of wire controller, and spin the screwdriver to take down the back cover. (Pay attention to spinning direction, otherwise will damage the back cover!) 6.3.4 Wire outlet A 2) Use three GB950-86 M4X20 screws to directly install the back cover on the wall. 3) Use two…
-
B
44mm Electrician box C 60mm Wall hole and wiring hole Diameter:Φ8--Φ10 Wiring hole Putty Trap Putty Avoid the water enter into the wired remote controller, use trap and putty to seal the Trap connectors of wires during wiring installation. Putty Trap 35
-
6.4 Front cover installation
After adjusting the front cover and then buckle the front cover; avoid clamping the communication switching wire during installation. Sensor can not be affected with damp. 36
-
Correct install the back cover and firmly buckle the front cover and back
cover, otherwise will make the front cover drop off. 37
-
Error code EEPROM error of main control board 2E0 EEPROM error of inverter module A 3E0 2 Content 1E0 E1 EEPROM error of inverter module B Power phase sequence error 3 E2 Communication error between main control board and wired controller 4 E3 Total water outlet temperature sensor error(master only)…
-
Error code
Content 19 P5 System B Current protection (protection occurs for 5 times in 120 minutes and the failure can be recovered by power disconnection only) 20 1P6 System A inverter module protection 2P6 System A inverter module protection 21 P7 Condenser high temperature protection 22 P9 Protection of…
-
Error code
36 FE 37 Content Heat recovery temperature sensor error 1FF DC fan A error 2FF DC fan B error 38 FP DIP inconsistency of multiple water pumps(Power failure recovery required) 39 L0 Inverter module protection 40 L1 DC bus low voltage protection 41 L2 DC bus high voltage protection 42 L4 MCE error 43…
-
NOTE CONCERNING PROTECTION OF
ENVIRONMENT This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal…