Installer manual
-
Quick guide
Navigation Ok button (confirm/select) Up/down buttons (move/increase/reduce) Back button (back/undo/exit) A detailed explanation of the button functions can be found on page 22. How to scroll through menus and make different settings is described on page 23. Increase hot water volume true off 1X 2X…
-
Table of Contents
1 Important information Safety information Delivery and handling 5 Transport Assembly Supplied components Removing the covers The Heat pump design 10 4 Pipe and air connections 12 General pipe connections Dimensions and pipe connections Connecting cold and hot water Installation alternative General…
-
1 Important information
Safety information This manual describes installation and service procedures for implementation by specialists. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been…
-
Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be carried out by a suitably qualified person. ✔ Description Notes Signature Date Ventilation, exhaust air (page 14) Setting the ventilation flow Exhaust air filter Ventilation…
-
Contact information
AT KNV Energietechnik GmbH, Gahberggasse 11, 4861 Schörfling Tel: +43 (0)7662 8963-0 Fax: +43 (0)7662 8963-44 E-mail: mail@knv.at www.knv.at CH NIBE Wärmetechnik c/o ait Schweiz AG, Industriepark, CH-6246 Altishofen Tel: (52) Fax: (52) E-mail: info@nibe.ch www.nibe.ch CZ Druzstevni zavody Drazice…
-
2 Delivery and handling
Transport Transport F110 should be transported and stored vertically in a dry place. However. the F110 may be carefully laid on its back when being moved into a building. The centre of gravity is in the upper part. 0 R 0 R 40 mm Assembly ■ Position F110 on a firm base that can take the weight…
-
Installation area
NOTE Leave a free space of 800 mm in front of the heat pump. Approx. 50 mm free space is required on each side, to remove the side panels. The panels do not need to be removed during service, all service can be carried out from the front. Leave space between the heat pump and the wall behind (and…
-
Supplied components
Location The kit of supplied items is placed in the lower section of the product. LEK Filter cartridge Silencer LEK Air connection vi nk ar oM LEK NIBE™ F110 LEK Chapter 2 | Delivery and handling 7
-
Front cover
Removing the covers Remove the front hatch by pulling it straight out. Air treatment hatch K LE 4 1. Slacken off the screws for the securing plate above F110. 2. Slide the hatch upwards and pull it towards you. 3. Pull the hatch towards yourself. NOTE A ground cable is installed in the hatch, it can…
-
Side panels
Air treatment section LEK LEK LEK Undo the screws at the edge. Twist the cover slightly outward. Move the side cover outwards and backwards. Assembly takes place in the reverse order. 1. 2. 3. 4. Heater section LEK LEK Undo the screws at the edge. Twist the cover slightly outward. Move the side…
-
3 The Heat pump design
-
Pipe connections
Electrical components XL 3 XL 4 XL43 XL44 WM2 AA2 AA 4 CA1 EB 1 EB10 FD 1 Connection, cold water Connection, hot water Connecting incoming air Connecting outgoing air Overflow water discharge1 Base card Display unit Capacitor Immersion heater Compressor heater Temperature limiter1 HVAC components FL…
-
4 Pipe and air connections
General pipe connections Pipe installation must be carried out in accordance with current norms and directives. F110 is only designed for be installed vertically. The water heater is equipped with compression ring couplings for copper or plastic pipes. Internal support bushes must be fitted when a…
-
Connecting cold and hot water
The valve connector must not be used for external installation, relocation or separation. K LE Dimensions and pipe connections B C A LEK XL3 WM1 XL4 Setting out dimensions Connection XL3 Cold water XL4 Hot water WM1 Drip tray (mm) (mm) (mm) A B C (mm) (mm) (mm) Pipe dimensions Connection XL3 Cold…
-
Installation alternative
Outdoor air F110 must be connected according to the instructions in this manual. Installation must be carried out in accordance with current standards and directives. Exhaust air Connecting the outdoor air Connecting the exhaust air With an exhaust air connection the heat in the building's…
-
Surrounding air
Take incoming air from one room and release the outgoing air to the same room. Connecting surrounding air With surrounding air connection the heat in the room air is used to heat up the hot water. The outgoing air can be used to cool a room. ■ If the incoming air is taken from the same room where…
-
LEK
Install the filter cartridge General air connections Air installation must be carried out in accordance with applicable directives. To prevent fan noise being transferred to the ventilation devices, it may be a good idea to install a silencer in the duct, alternatively mount the enclosed silencer in…
-
Exhaust air duct /kitchen fan
Exhaust air duct (kitchen fan) must not be connected to F110. To prevent food vapour being transferred to F110 the distance between the kitchen fan and the exhaust air device must be considered. The distance should not be less than 1.5 m, but this can vary between different installations. Always use…
-
LEK
5 Electrical connections K LE General Temperature limiter All electrical equipment is connected at the factory. The temperature limiter (FD1) cuts the power to the electric additional heat if the temperature reaches above 95 °C and is reset manually. Installation must be carried out in accordance…
-
Optional connections
AUX inputs Switch for external blocking off additional heat and/or compressor Blocking for addition heat and compressor is connected on two different AUX inputs. When external blocking of additional heat and/or the compressor is desired, this can be connected to terminal block X13 on the base board…
-
6 Commissioning and adjusting
Preparations Start-up and inspection 1. Check that the display is off. 2. Check that any filling valves are fully closed and that the temperature limiter has not deployed. Caution Check the temperature limiter (BT35) in the heat pump. It may have tripped during transportation. Filling and venting…
-
Setting ventilation (exhaust air)
Ventilation must be set according to applicable standards. The setting is made in menu 5.1.5. Even if ventilation is roughly set at installation it is important that a ventilation adjustment is ordered and permitted. NOTE Order a ventilation adjustment to complete the setting. Fan capacity Available…
-
7 Control - Introduction
Display unit Date Clock A Status icons B C D E A B Display Instructions, settings and operational information are shown on the display. The information menu shows: ■ on starting. ■ when the back button in the main menu is pressed. ■ after 15 minutes of inactivity. Press any button to go to the main…
-
Symbols in the display
Operation The following symbols can appear in the display during operation. To move the cursor, press the up or down button. The marked position is brighter and/or has a turned up tab. Symbol Description Selecting menu This symbol is displayed when the compressor is operating. To advance in the menu…
-
Setting a value
periodic increase 2.9.1 activated period days Next increase Adjustable value To set a value: 1. Mark the value you want to set using the up or down button. 2. Press the OK button. The background of the value becomes green, which means that you have accessed the setting mode. 3. Press the up button…
-
8 Control - Menus
Menu 1 - ventilation Overview 1 - ventilation Menu 1 - ventilation Setting range: normal and speed 1-4 Default value: normal This menu is only shown with exhaust air installation. The ventilation in the accommodation can be temporarily increased or reduced here. When a new speed has been selected a…
-
Menu 2 - HOT WATER
Overview 2 - HOT WATER 2.1 - temporary lux 2.2 - comfort mode 2.3 - scheduling 2.9 - advanced * Accessory needed. Sub-menus For the menu HOT WATER there are several submenus. Status information for the relevant menu can be found on the display to the right of the menus. temporary lux Activation of…
-
TIP
If you wish to set similar scheduling for every day of the week start by filling in “all” and then changing the desired days. Caution If the stop time is earlier in the day than the start time it means that the period extends past midnight. Scheduling always starts on the date that the start time is…
-
Menu 3 - INFO
Overview 3 - INFO 3.1 - service info 3.2 - compressor info 3.3 - add. heat info 3.4 - alarm log Sub-menus For the menu INFO there are several sub-menus. No settings can be made in these menus, they just display information. service info shows temperature levels and software versions in the heat…
-
Menu 4 - MY SYSTEM
Overview 4 - MY SYSTEM 4.2 - op. mode 4.4 - time & date 4.6 - language 4.7 - holiday setting 4.8 - alarm 4.9 - advanced 4.9.4 - factory setting Sub-menus Menu 4.4 - time & date For the menu MY SYSTEM there are several submenus. Status information for the relevant menu can be found on the display to…
-
Caution
After factory settings, user settings must be reset. 30 Chapter 8 | Control - Menus NIBE™ F110
-
Menu 5 - SERVICE
Overview 5 - SERVICE 5.1 - operating settings 5.1.1 - hot water settings 5.1.5 - fan speed 5.1.15 - air in-temperatures 5.1.16 - installation 5.5 - factory setting 5.6 - forced control 5.7 - start guide 5.8 - quick start Go to the main menu and hold the Back button in for 7 seconds to access the…
-
Menu 5.1.5 - fan speed
Menu 5.5 - factory setting Exhaust air installation All settings can be reset (including settings available to the user) to default values here. Setting range: 30 – 100 % Factory setting normal: 70 % Factory setting speed 1: 30 % Factory setting speed 2: 50 % NOTE When resetting, the start guide is…
-
9 Service
Service actions NOTE Servicing should only be carried out by persons with the necessary expertise. When replacing components on F110 only replacement parts from NIBE may be used. Emptying 1. Cut the current to the heat pump by pulling out the supply cable. 2. Close the shut-off valve (QM30) (turn…
-
10 Disturbances in comfort
If F110 is not installed together with the indoor module, go directly to section Troubleshooting. In most cases, the heat pump notes operational interference (operational interference can lead to disturbance in hot water comfort) and indicates this with an alarm in the display. Info menu All the…
-
Communication alarm display
Gurgling sound The display has lost contact with the base card. ■ Check the connection between F110 and the base card and that the cable has not got a short-circuit. ■ Not enough water in the water seal. Troubleshooting ■ Refill the water seal with water. ■ Choked water seal. ■ Check and adjust the…
-
11 Accessories
Base extension EF 45 Part no. 067 152 Separable valve connector For external installation, relocation or separation. F110 Copper Part no. 624 922 F110 Stainless steel Part no. 624 923 Top cabinet Top cabinet for concealing the ventilation ducts. 245 mm Part no. mm Part no. 089 757 395-645 mm Part…
-
12 Technical data
440 20 2075 560 25-50 2010 Dimensions and setting-out coordinates Ø160 Ø125 NIBE™ F110 Chapter 12 | Technical data 37
-
Technical specifications
Supplier NIBE Model F110 Type of installation Specified output according to EN16147 COP Sound power level (LW(A)) according to EN 12 1024) Sound pressure level in the boiler house (LP(A)) according to EN ISO 11 2035) Exhaust air Outdoor air Surrounding air 1.321) 1.082) 1.321) 2.89 3.27 dB(A) 2.36…
-
1x230 V
Additional power Output immersion heater (max) Electrical data Rated voltage Max operating current Driving power circulation pump Driving power fan Specified compressor output according to EN161476) Fuse Enclosure class Refrigerant circuit Type of refrigerant Volume Compressor type Cut-out value…
-
Miscellaneous
Water heater Corrosion protection Volume, hot water heater Min pressure in water heater Max pressure in hot water heater Safety valve deploys at Max temperature with compressor Max temperature with additional heat Capacity hot water heating according to EN 161477) litre MPa/bar MPa/bar MPa/bar °C °C…
-
Energy labelling
Supplier NIBE AB Model Declared load profile Water heating energy efficiency class, average climate F110 Exhaust air F110 Outdoor air F110 Surrounding air XL A XL A XL A Water heating energy efficiency, average climate, ƞwh % Annual energy consumption water heating, average climate, AEC Thermostat…
-
Electrical circuit diagram
42 Chapter 12 | Technical data NIBE™ F110
-
13 Item register
Item register A Accessories, 36 Adjusting ventilation, 17 Assembly, 5 C Commissioning and adjusting, 20 Filling and venting, 20 Preparations, 20 Start-up and inspection, 20 Connecting cold and hot water, 13 Contact information, 4 Control, 22, 25 Control - Introduction, 22 Control - Menus, 25 Control…
-
SE
Återvinning Lämna avfallshanteringen av emballaget till den installatör som installerade produkten eller till särskilda avfallsstationer. När produkten är uttjänt får den inte slängas bland vanligt hushållsavfall. Den ska lämnas in till särskilda avfallsstationer eller till återförsäljare som…
-
WS name: -Gemensamt
WS version: a81 (working edition) Publish date: 2015-09-16 09:56 NIBE AB Sweden Hannabadsvägen 5 Box 14 SE-285 21 Markaryd info@nibe.se www.nibe.eu 231974
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.