Installer manual
NIBE F370 Exhaust air heat pump LEK IHB GB 1722-1 431424
-
Quick guide
Navigation Ok button (confirm/select) Back button (back/undo/exit) Control knob (move/increase/reduce) A detailed explanation of the button functions can be found on page 38. How to scroll through menus and make different settings is described on page 40. Set the indoor climate INDOOR CLIMATE HOT…
-
Table of Contents
1 Important information Safety information General 2 Delivery and handling Transport Assembly Supplied components Removing the covers Removing parts of the insulation 3 The heat pump design Component positions 4 Pipe and ventilation connections General pipe connections Dimensions and pipe…
-
1 Important information
Safety information This manual describes installation and service procedures for implementation by specialists. The manual must be left with the customer. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of…
-
Area checks
Before work is started on systems that contains combustible refrigerants, safety checks must be performed to ensure that the ignition risk is kept to a minimum. Working method The work must be carried out in a controlled way to minimise the risk of contact with combustible gas or liquid during the…
-
■ Refrigerant pipes and components are
positioned in such a way that it is not likely that they be subjected to substances that can corrode components containing refrigerant, if these components are not made of material that is resistant against corrosion, or not appropriately protected against such corrosion. Checking electrical…
-
relevant refrigerant. The leak tracing
equipment must be set and calibrated for the relevant refrigerant, to ensure that the gas concentration is a maximum of 25% of the lowest combustible concentration (Lower Flammability Limit, LFL) of the relevant refrigerant. Leak detection fluids are suitable for use with most refrigerants but the…
-
Good practice prescribes that all refrigerant
is collected safely. Before the work is carried out, samples of oil and refrigerant must be taken, if analyses are required before collected refrigerant can be reused. There must be a power supply when this task is started. 1. Familiarise yourself with the equipment and its use. 2. Isolate the…
-
maintained, and that corresponding electrical components are sealed, to prevent
ignition if any refrigerant should come out. Contact the manufacturer in the event of any doubts. Return the collected refrigerant to the refrigerant supplier in the correct collection container and with the relevant Waste Transfer Note. Do not mix refrigerants in collection devices or containers.…
-
General
Serial number The serial number can be found at the bottom right of the front cover and in the info menu (menu 3.1). Serial number Caution You need the product's (14 digit) serial number for servicing and support. Recovery Leave the disposal of the packaging to the installer who installed the…
-
Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be carried out by a suitably qualified person. In addition, fill in the page for the installation data in the User Manual. ✔ Description Notes Signature Date Ventilation (page 20)…
-
2 Delivery and handling
Transport Installation area F370 should be transported and stored vertically in a dry place. However. the F370 may be carefully laid on its back when being moved into a building. The centre of gravity is in the upper part. Leave a free space of 800 mm in front of the product. Leave free space…
-
Side covers
Supplied components Outside sensor Room sensor LE K LE K LE K LEK Current sensor LEK Earth cabling (2 pcs) LE K Location The kit of supplied items is placed on top of the product. Removing the covers Front cover 1 3 The side covers can be removed to facilitate the installation. 1. Remove the screws…
-
3 The heat pump design
-
Pipe connections
XL1 XL2 XL3 XL4 XL8 XL31 XL32 Connection, heating medium flow line Connection, heating medium return line Connection, cold water Connection, hot water Connection, docking in Ventilation connection, exhaust air Ventilation connection, extract air HVAC components CM1 FL1 FL2 FQ1 GP1 QM10 QM11 QM13…
-
4 Pipe and ventilation connections
General pipe connections System diagram Pipe installation must be carried out in accordance with current norms and directives. F370 consists of a heat pump, water heater, immersion heater, fan, circulation pump and control system.F370 is connected to the ventilation system and heating medium…
-
Setting out dimensions
-
Symbol key
Heating medium side Symbol Meaning Connecting the climate system A climate system is a system that regulates indoor comfort with the help of the control system in F370 and for example radiators, under floor heating/cooling, fan coils etc. ■ When connecting to a system with thermostats on all…
-
Installation alternative
F370 can be installed in several different ways, some of which are shown below. Further option information is available at www.nibe.eu and in the respective assembly instructions for the accessories used. See page 55 for a list of the accessories that can be used with F370. Extra hot water heaters…
-
General ventilation connection
Ventilation flow Ventilation installation must be carried out in accordance with current norms and directives. Connect F370 so that all of the exhaust air, except kitchen duct air (kitchen fan), passes the evaporator (EP1) in the heat pump. The lowest ventilation flow must comply with the applicable…
-
5 Electrical connections
General NOTE All electrical equipment, except the outdoor sensors, room sensors and the current sensors are ready connected at the factory. ■ Disconnect the heat pump before insulation testing the house wiring. Electrical installation and service must be carried out under the supervision of a…
-
Removing the cover, base circuit board
Accessibility, electrical connection The plastic cap of the electrical boxes is opened using a screwdriver. Caution To remove the cover for the base board, the cover for the input circuit board must first be removed. NOTE The cover for the input card is opened without a tool. A Removing the cover…
-
Connection 3x230V
Connections NOTE AA1-X1 To prevent interference, unscreened communication and/or sensor cables to external connections must not be laid closer than 20 cm from high voltage cables. PE L1 1 L2 2 L3 Power connection F370 must be installed via an isolator switch with a minimum breaking gap of 3mm.…
-
Connecting external operating voltage for
-
Room sensor
F370 is supplied with a room sensor enclosed (BT50). The room sensor has up to three functions: 1. Show current room temperature in F370's display. 2. Option of changing the room temperature in °C. 3. Makes it possible to change/stabilise the room temperature. Install the sensor in a neutral…
-
Settings
BT30 AA1-X3 AA1-SF2 Electrical addition (kW) Max (A) L1 Max (A) L2 Max (A) L3 0.0 2.0 4.7 6.7* 8.0 10.0 3.9 3.9 14.0 14.0 23.6 23.6 3.9 11.2 11.2 19.6 23.6 31.1 8.7 17.6 25.3 20.1 28.0 AA1-X7 *Factory setting The table displays the maximum phase current for the relevant power step for the heat pump.…
-
kW
-
Optional connections
NIBE Uplink Load monitor Connect the network connected cable (straight, Cat.5e UTP) with RJ45-contact (male) to RJ45 contact (female) on the rear of the heat pump. Integrated load monitor F370 is equipped with a simple form of integrated load monitor, which limits the power steps for the electric…
-
Caution
Some of the following functions can also be activated and scheduled via menu settings. Possible selection for AUX inputs Switch for external blocking of addition and/or compressor Blocking for addition heat and compressor is connected on two different AUX inputs. If external blocking of additional…
-
Switch for external blocking of hot water
In cases where external blocking of hot water is used, this can be connected to terminal block X6 on the input board (AA3), which is positioned behind the front cover. Hot water operation is disconnected by connecting a potential-free switch function to the input selected in menu 5.4, see page 47. A…
-
Connecting accessories
Instructions for connecting accessories are provided in the manual accompanying the accessory. See page 55 for the list of the accessories that can be used with F370. NIBE F370 Chapter 5 | Electrical connections 31
-
6 Commissioning and adjusting
LEK Venting the climate system Preparations 1. Check that the switch (SF1) is in position " ". 2. Check that the filling valves (QM10) and (QM11) are fully closed. Caution 1. Turn off the power supply to the heat pump. 2. Vent the heat pump via the vent valve (QM20) and the rest of the climate…
-
Start-up and inspection
Operation in the start guide A. Page B. Name and menu number Start guide language 4.6 NOTE There must be water in the climate system before the switch is set to " ". 1. Set switch (SF1) on F370 to position " ". 2. Follow the instructions in the display's start guide. If the start guide does not…
-
Setting the ventilation
Commissioning without fan Ventilation must be set according to applicable standards. Set the fan speed in menu 5.1.5. The heat pump can be run without recovery, as only an electric boiler, to produce heat and hot water, for example before the ventilation installation is complete. Even if ventilation…
-
Pump speed, proportional pressure (PP)
Setting circulation pump Capacity, circulation pump (PP) LEDs Tryck Pressure (kPa) GP1-SF4 0 0,05 0,1 0,15 0,2 0,25 0,3 Flöde Flow (l/s) Output, circulation pump (PP) Effekt Output The circulation pump (GP1) is equipped with five LEDs. In normal mode, the LEDs show the power consumption. They can…
-
Pump speed, constant pressure (CP)
Pump speed, constant curve (CC) Capacity, circulation pump (CP) Capacity, circulation pump (CC) Tryck Pressure (kPa) 35 Tryck Pressure 30 50 (kPa) 0,05 0,1 0,15 0,2 0,25 0,3 0 0 0,05 0,1 0,15 0,2 0,25 0,3 Flöde Flow Flöde Flow (l/s) (l/s) Output, circulation pump (CP) Output, circulation pump (CC)…
-
Alarm
In the event of an alarm the LED changes 1 colour from green to red. When one or several alarms are active, this is indicated according to the following table. If more than one alarm is active, the one with the highest priority is displayed. LED indication Cause / Action Red + yellow LED (LED The…
-
7 Control - Introduction
Display unit F A Display INDOOR CLIMATE ■ Standby ( ) HOT WATER INFO ■ Emergency mode ( D Back button F370 A Display B Status lamp ) (see page 49) Emergency mode must only be used in the event of a fault on the heat pump. In this mode, the compressor switches off and the immersion heater engages.…
-
Symbols in the display
Menu system When the door to the heat pump is opened, the menu system’s four main menus are shown in the display as well as certain basic information. Outdoor temperature Indoor temperature - (if room sensors are installed) INDOOR CLIMATE HOT WATER The following symbols can appear in the display…
-
Menu number – marked sub menu
Name and menu number – main menu Symbol – main menu INDOOR CLIMATE HOT WATER INDOOR CLIMATE 1 temperature ventilation normal scheduling off advanced HEAT PUMP INFO Marked main menu Symbols – sub menus Operation To move the cursor, turn the control knob to the left or the right. The marked position…
-
Use the virtual keyboard
Help menu In many menus there is a symbol that indicates that extra help is available. To access the help text: 1. Use the control knob to select the help symbol. 2. Press the OK button. Different keyboards The help text often consists of several windows that you can scroll between using the control…
-
8 Control - Menus
Menu 1 - INDOOR CLIMATE Overview 1 - INDOOR CLIMATE 1.1 - temperature 1.2 - ventilation 1.3 - scheduling 1.3.1 - heating 1.3.3 - ventilation 1.9 - advanced 1.9.1.1 - heating curve 1.9.2 - external adjustment 1.9.3 - min. flow line temp. 1.9.4 - room sensor settings 1.9.6 - fan return time 1.9.7…
-
Menu 4 - HEAT PUMP
Overview 4 - HEAT PUMP 4.1 - plus functions * 4.1.3 - internet 4.1.3.1 - NIBE Uplink 4.1.3.8 - tcp/ip settings 4.1.3.9 - proxy settings 4.1.4 - sms * 4.1.5 - SG Ready 4.1.6 - smart price adaption™ 4.1.7 - smart home 4.2 - op. mode 4.3 - my icons 4.4 - time & date 4.6 - language 4.7 - holiday setting…
-
Menu 5 - SERVICE
Overview 5 - SERVICE 5.1 - operating settings 5.1.1 - hot water settings 5.1.2 - max flow line temperature 5.1.4 - alarm actions 5.1.5 - fan sp. exhaust air 5.1.12 - internal electrical addition 5.1.13 - max inst. el.pwr (BBR) 5.1.99 - other settings 5.2 - system settings 5.2.4 - accessories 5.3…
-
Menu 5.1.1 - hot water settings
Menu 5.1.2 - max flow line temperature economy climate system Setting range start temp. economy: 15 - 52 °C Setting range: 20-70 °C Factory setting start temp. economy: 45 °C Default value: 60 °C F370 copper: 43 °C F370 stainless steel: 42 °C Setting range stop temp. economy: 15 - 55 °C Factory…
-
Menu 5.1.12 - internal electrical addition
Menu 5.1.99 - other settings set max electrical add. trend calculation limit Setting range 3x400 V: 0 - 10.25 kW Setting range: 0 – 20 °C Setting range 3x230 V: 0 - 12 kW Default value: 7 °C Default values: 5.3 kW transfer time fuse size Setting range: 1 - 60 min Setting range: 1 - 200 A Default…
-
Menu 5.3 - accessory settings
Menu 5.8 - quick start The operating settings for accessories that are installed and activated are made in the sub-menus for this. It is possible to start the compressor from here. Menu 5.3.3 - extra climate system Caution There must be a heating or hot water demand to start the compressor. mixing…
-
5.12 - country
Select here where the product was installed. This allows access to country specific settings in your product. Language settings can be made regardless of this selection. NOTE This option locks after 24 hours, restart of display or program updating. 48 Chapter 8 | Control - Menus NIBE F370
-
9 Service
NOTE Draining the water heater Servicing and maintenance should only be carried out by persons with the necessary expertise. The water heater can be drained via the safety valve (FL1) or via the overflow cup (WM1). 1. Disconnect the overflow pipe from the safety valve (FL1) and connect a hose to a…
-
Helping the circulation pump to start
The circulation pump in F370 has an automatic start help function. If necessary the pump can be started manually. In such cases, take the following action: 1. Shut off F370 by setting the switch (SF1) to mode " ". 2. Remove the front hatch. 3. Press the screw for start help in using a star head…
-
Menu 7.1 - update firmware
USB service outlet update firmware7.1 start updating choose another file LEK This allows you to update the software in F370. NOTE The display unit is equipped with a USB socket that can be used to update the software, save logged information and manage the settings in F370. INDOOR CLIMATE HOT WATER…
-
choose another file
Menu 7.3 - manage settings update firmware7.1 manage settings 7.3 save settings recover settings Select “choose another file" if you do not want to use the suggested software. When you scroll through the files, information about the marked software is shown in a fact box just as before. When you…
-
10 Disturbances in comfort
In most cases, the heat pump notes operational interference (operational interference can lead to disturbance in comfort) and indicates this with alarms and shows action instructions in the display. Info-menu All the heat pump measurement values are gathered under menu 3.1 in the heat pump menu…
-
■ "Holiday mode" activated in menu 4.7
The compressor does not start – Enter menu 4.7 and select "Off". ■ There is no heating requirement. ■ External switch for changing the room heating activ- ated. – Check any external switches. ■ Circulation pump (GP6) has stopped. – See section "Helping the circulation pump to start" on page 50. ■…
-
11 Accessories
Not all accessories are available on all markets. Water heater/Accumulator tank Communications module SMS 40 Eminent When there is no internet connection, you can use the accessory SMS 40 to control F370 via SMS. Water heater with immersion heater. Part no 067 073 Copper Part no. 072 310 Copper Part…
-
12 Technical data
60 25-50 2075 35 Dimensions and setting-out coordinates Avoid routing pipes through the Undvik rördragning marked area inom markerat område 56 Chapter 12 | Technical data NIBE F370
-
Technical specifications
IP 21 3x400 V Output data according to EN 14 511 Specified heating output (PH)1 Rostfritt kW COP1 Specified heating output (PH)2 3.93 kW COP2 Specified heating output (PH)3 2.03 3.24 kW COP3 Additional power Max power, immersion heater (factory setting) Electrical data Rated voltage Max operating…
-
Other 3x400 V
Water heater and heating section Volume heating section Volume, hot water heater Max pressure in hot water heater Capacity, hot water Tap volume 40 °C according to EN 16 147(Vmax)6,7 Rostfritt litre litre MPa/bar litre COP at Normal comfort (COPt) Idle loss at Normal comfort (Pes) Dimensions and…
-
3x230 V
Rostfritt Output data according to EN 14 511 Specified heating output (PH)1 kW COP1 3.93 )2 kW Specified heating output (PH)3 kW Specified heating output (PH 2.18 COP2 3.24 COP3 Additional power Max power, immersion heater (factory setting) Electrical data Rated voltage Max operating current Min.…
-
Other 3x230 V
Water heater and heating section Volume heating section Volume, hot water heater Max pressure in hot water heater Capacity, hot water Tap volume 40 °C according to EN 16 147(Vmax)6,7 Rostfritt litre litre MPa/bar litre COP at Normal comfort (COPt) Idle loss at Normal comfort (Pes) Dimensions and…
-
Energy labelling
Information sheet Supplier NIBE Model F370 Temperature application °C Declared load profile for water heating 35 / 55 L A+ / A+ Seasonal space heating energy efficiency class, average climate Water heating energy efficiency class, average climate A Rated heat output (Pdesignh), average climate…
-
Technical documentation
Model F370 Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Yes No Integrated immersion heater for additional heat Yes No Heat pump combination heater Yes No Climate Average Temperature application Applied standards Rated heat output Prated Warm ƞs 110 %…
-
Electrical circuit diagram
-
Chapter 12 | Technical data NIBE F370
-
таблицы и схемы — в просмотре
-
Chapter 12 | Technical data NIBE F370
-
таблицы и схемы — в просмотре
-
Chapter 12 | Technical data NIBE F370
-
таблицы и схемы — в просмотре
-
Chapter 12 | Technical data NIBE F370
-
таблицы и схемы — в просмотре
-
Chapter 12 | Technical data NIBE F370
-
таблицы и схемы — в просмотре
-
Chapter 12 | Technical data NIBE F370
-
13 Item register
Item register A Accessibility, electrical connection, 22 Accessories, 55 Adjusting ventilation, 20 Alarm, 53 Assembly, 12 B Back button, 38 C Cable lock, 22 Cold and hot water, 18 Commissioning and adjusting, 32 Filling and venting, 32 Preparations, 32 Start guide, 33 Start-up and inspection, 33…
-
Menu system, 39
Help menu, 33, 41 Operation, 40 Scroll through the windows, 41 Selecting menu, 40 Selecting options, 40 Setting a value, 40 Use the virtual keyboard, 41 Miniature circuit-breaker, 21 N NIBE Uplink, 28 O OK button, 38 Operation, 40 Optional connections, 28 Outdoor sensor, 24 Output locking, 26 P Pipe…
-