VERSO PRO 2
INSTALLATION MANUAL komfovent
-
1. INTRODUCTION
This Installation Manual is intended for professionals, qualified to install VERSO PRO 2 air handling units. Qualified professionals are people with sufficient professional experience and knowledge of ventilation systems and installation thereof, knowledge of electrical safety requirements and…
-
VERSO CF – air handling units with counter-flow recuperators (heat exchangers). Plates of a heat exchanger come in contact with different air flows and so heat exchange between extracted and incoming fresh supply air takes place. Amount of recovered heat or cold is controlled by adjusting the air…
-
1.3. Unit Components and Sections
VERSO PRO2 air handling units are assembled from separate sections. Depending on the order and unit size, sections may be pre-assembled in a factory or transported separately. Type of each section is marked with a label attached to the section door. The following are the main sections of the air…
-
1.3.2. Counter-Flow Heat Exchanger (CF) Section
Due to heat exchange and condensation in counter-flow heat recovery units, heat exchangers may freeze at lower air temperatures. To prevent freezing or to defrost, a heat exchanger is equipped with an air bypass damper or a multi-stage damper system (according to the order). Formed condensate flows…
-
1.3.3. Rotary Recuperator (R) Section
Rotor wheel of a rotary recuperator is belt driven by an electric gear motor. Brush seals are installed at the perimeter of a rotating wheel and between air flows to prevent different air flows from mixing. Recuperator section is also fitted with an automation box to which many of the main…
-
1.3.4. Liquid coupled heat exchanger
A liquid coupled heat exchanger used for airflow separation consists of two coils (radiators) in which an antifreeze mixture of water and glycol circulates. Coils are located in separate sections that should be installed in the supply or extract air flows. Additionally, a drop eliminator is placed…
-
1.3.6. Cooler and Heater Sections
Cooler section is fitted with water or direct evaporation (DX) coolers as well as combined heater/cooler heat exchangers. Cooling air causes condensation, therefore, a condensate tray is installed under a heat exchanger. If air velocity in the air handling unit is high (> 2 m/s), an optional drop…
-
1.3.7. Air Dampers
Air dampers are mounted on the outside of the unit and are fastened with self-tapping screws. Air dampers are designed to isolate the unit and to protect against air flows and draughts when the unit is stopped. Damper blades are closed/opened with an electric actuator (24 V AC), the power and torque…
-
1.3.9. Humidifier section
VERSO PRO2 units that was ordered with humidity function can control external steam humidifier. Humidifier generates steam that reaches steam distributors located inside of the AHU in the supply airflow. A drop eliminator is placed inside the humidifier section to prevent excess condensate from…
-
1.3.10. Smoke extraction section
The smoke extraction section is used to direct the gases and smoke generated by fire in the building, directly to the exhaust air fan, which throws them out, bypassing the AHU filters and the heat exchanger. Smoke ducts of the building are connected to a smoke bypass damper, which is mounted at the…
-
1.4. Inspection Sides
Depending on the installation position and connection of air ducts, VERSO PRO2 air handling units are available in four inspection sides. Inspection side is determined by a supply air duct (SUP) position: L1 Air duct for supply air connected on the left bottom side of the unit VERSO R VERSO CF EHA…
-
2. UNIT TRANSPORTATION AND STORAGE
Units must be transported and stored in their original packaging. During transportation, units must be properly fixed and additionally protected against possible mechanical damage, rain or snow. Only an employee qualified to operate a forklift truck or crane and familiar with the principles of cargo…
-
Individual sections of the unit shall be lifted with an installation frame. Pipes should be inserted through the mounting frame into designated openings and lifting ropes or belts fixed. It must be ensured that belts will not disconnect or pipes will not be pulled out of the frame when lifting. Max.…
-
If fully assembled AHU will be lifted, not each section separately, it must be done using additional reinforced mounting frame. When the unit is ordered fully assembled, it will already be mounted on a reinforced installation frame at the factory. If the unit’s sections are transported separately…
-
VERSO PRO2 12-72
-
• • • • • Air handling units are heavy, therefore care must be taken during lifting, carrying or moving operations. Use personal protection equipment, do not stand under a suspended unit or a part thereof. Only an employee qualified to operate a forklift truck or crane and familiar with the…
-
3.2. Inspection Area
Based on its type, an air handling unit may be installed indoors or outdoors. When selecting an installation or mounting location, you must foresee sufficient and security compliant access space for repair and maintenance operations. The unit must be installed in a way to allow partial or full…
-
3.3. Door Handles and Hinges
VERSO PRO2 door handles are designed in such a way that the unit door does not swing open due to the pressure accumulated inside the unit and does not injure the person opening the door. By pressing the handle, the door slightly opens and locks to release air pressure inside the unit. Return the…
-
3.4. Connection of Sections
unit. Connect connecting cables and wires of the sections (see Chapter “Electrical Installation”) before fastening sections of an air handling • • • • • If, for any reason, sections of the unit were disassembled, before installation at it’s final location, airtightness of the unit may differ from…
-
Depending on the unit size and purpose of sections thereof, separate sections may be interconnected with external tightening elements or internal tightening brackets, using supplied screws and/or spacers. Sealing gaskets must be attached to joints before joining the sections (supplied with the…
-
3.5. Installation of External Heating/Cooling Devices
Based on their equipment, VERSO PRO2 air handling units may be operated with various heating or cooling devices. Heaters/coolers are usually installed in separate sections that are connected at the end of the unit (in the supply air stream). For air handling units with R1 or L1 inspection sides…
-
Pipes of water heater and cooler are connected to a water mixing unit (PPU) that supplies hot/cold water from the building’s water system. Heat exchangers for direct evaporation (DX) coolers/heaters are factory-filled with nitrogen gas. Before connecting a heat exchanger to a refrigerant system…
-
When operating air handling unit in temperatures lower than 0°C, it is necessary to use water-glycol mixture as a heat carrier or to maintain a return water temperature of at least 25°C. Pipework package1 must include circulation pump, which circulates heating/cooling medium through the coil…
-
3.7. Connection to Air Ducts
• • • • Ducts and air closing dampers connecting the unit to the exterior of the building must be insulated (insulation thickness 50–100 mm) to prevent condensation on cold surfaces. Air intake and exhaust ducts must be fitted with air shut-off dampers (electric with actuators) to protect the unit…
-
3.8. Outdoor Units
VERSO PRO2 air handling units for outdoor installation must be additionally protected against environmental effects by installing a protective roof and exhaust air hoods. Units shall be mounted on an installation frame which is attached to an installation base. Ventilation devices, when possible…
-
VERSO PRO2 12-72
-
VERSO PRO2 82-92
a+100 b/2 b/2 c+100 a b>1110 c a+100 b c+100 a b<1110 c Fig. 35. Installation of a separately ordered protective roof Part count and measurements may differ depending on the unit type or project requirements. UAB KOMFOVENT we reserve the right to make changes without prior notice VERSO…
-
4. ELECTRICAL INSTALLATION
Only qualified professionals may perform electrical installation works in accordance with the manufacturer’s instructions and applicable legal acts and safety requirements. Before installation of any electrical components: • • • • Make sure the unit is unplugged from the mains. If the unit has been…
-
If circuit breaker bracket is used, it must be mounted on the edge of the unit casing, otherwise self-tapping screws may damage wires or tubing that is routed inside. Units fitted with an additional electric heater section will be equipped with a separate main circuit breaker inside the section. OFF…
-
4.2. Connection of Electrical Components
All internal and external devices are connected to the main board of the C5 control panel (RG1 in wiring diagrams) located in the automation box. Automation box is fitted at the front of the unit, top part of the heat exchanger section. Box is airtight and is opened by removing four screws and…
-
Terminals for the external elements of the controller board are numbered and are used only to connect external components. These may remain empty if no additional features are required. B9 Humidity sensor Cold water mixing valve / DX capacity control Hot water mixing valve Water pump for cooling…
-
Fig. 42. Return water temperature sensor with thread1
B1 (11–12) – terminal for a supply air temperature sensor (NTC 10kΩ) for controlling air temperature. Fig. 43. Supply air temperature sensor For the most accurate temperature measurement, sensor in a duct must be installed after all heating/cooling devices at least two duct diameters away from the…
-
Indication (40–42) – terminals are used when a normally open (NO) contact is necessary for operation status or fault indication. Terminals 40 and 42 are closed when AHU is in operation, thus it can be connected to any external device, which needs such a signal (for example humidifier). Terminals 41…
-
4.2.1. Connection terminals of VERSO RA air handling units
VERSO RA units consist of two separate assemblies (for supply and exhaust airflows). Each block has a separate automation box with terminals inside, and the main C5 controller board can be found in the automation box of the supply air assembly. Both blocks will also have a separate main power switch…
-
4.3. Control Panel Installation
The control panel must be installed in a room with: Ambient temperature – 0..40°C; Relative humidity – 20..80 %; Guaranteed protection against accidental water drops. Control panel can be mounted in a concealed mounting box or directly on the wall (screws supplied with the panel). You can also use…
-
4.4. Connection of Cables and Wires Between Sections
X1 X1 2 2 Before fastening parts of the air handling unit, you shall connect connecting cables and wires of the sections. Cable connectors are labelled with connector numbers; only connect connectors with the same number. Number of cables and connectors in different sections may differ depending on…
-
4.5. Connecting the Unit to the Internal Computer Network or the Internet
Your AHU may be controlled not only with a control panel, but also with a computer or smart phone. For this reason the unit must be connected to the internal computer network or the Internet. In case of a computer, the unit is controlled via a web browser, and in case of a smart phone - via the…
-
Connection to the local computer network
„Komfovent“ app Connection via the Internet INTERNET „Komfovent“ app Fig. 55. Examples for the AHU connection to the Internet or the local network 5. FILTERS Air filters are intended for removing dust, bacteria and other fine particles from the supplied and extracted air. VERSO PRO2 air handling…
-
Fig. 56. Filter clamping device
To insert/remove filters, push two handles at the top and bottom of the filter forward to release a filter clamping device. Filters are removed/inserted one by one (number of filters depends on the unit size). Once the filters are replaced/inserted, handles are retracted and the filter clamping…
-
6. COMMISSIONING AND INSPECTION OF THE UNIT
Before switching on the device, check for foreign objects, debris or tools inside the unit. Make sure that air filters are installed and condensate drainage is connected (if necessary), fill the siphon with water. Make sure that the ductwork is free from obstructions such as fully closed diffusers…
-
tap
If the unit is connected to the mains, the control panel will display a home screen or a screen saver that you can switch off with a single To start an air handling unit or change a ventilation mode: Change operation mode? During the first minute of starting the unit, the unit automation checks the…
-
To turn of the AHU and return to a home screen
6.2. Starting the Unit With a Computer If the unit was ordered without a control panel or it is not used, you can start it with your computer. In this case the unit is controlled via a web browser. Connect your computer directly to the AHU or to the same computer network as described in Chapter 4.5.…
-
To start the unit and change the ventilation mode settings
1. Press button “Modes”. 2. Select a desired ventilation mode from the list. 3. Enter desired air flow and temperature in the selected mode settings. 4. Press “Save” button at the bottom of the screen. You can stop the unit by pressing ON/OFF button in the “Overview” window. 46 UAB KOMFOVENT we…
-
6.3. Calibration of Clean Filters
VERSO PRO2 control automation continuously monitors filter contamination. Pressure drop of clean filters is preset in the factory. If filters are from another manufacturer or of different filtering class, we recommend performing initial calibration of clean filters before commissioning of the unit.…
-
6.4. Quick Inspection
The first time you start your device, make sure that: Task Yes No Comments Control panel is working, responds to touch, no error messages All air filters are installed Air dampers fully open There are no unusual noise or vibrations Changing the ventilation modes changes the fan speed The unit is…
-
ANNEX NO. 1. ADJUSTMENT OF THE ROTARY HEAT EXCHANGER WHEEL
Since, during the operation, the airflow constantly pushes the rotor wheel, due to its dimensions, to one side, it can eventually distort, causing the rotor sealing brushes and axle bearings to wear out faster or even may jam after time. To prevent this, check and, if necessary, adjust the position…
-
VERSO ≥82 VERSO 12-72 Screw in the adjusting screw. This will cause the wheel axis to tilt and release the adjustment plates. 4 5 1/2 L L AIR FLOW DIRECTION L 1/2 L 1/2 L L AIR FLOW DIRECTION L 1/2 L Tilt the heat exchanger axis so that the rotary wheel is slightly inclined against the direction of…
-
VERSO 12-72 VERSO ≥82 After adjusting the wheel tilt, loosen the adjusting screw so that the rotor shaft presses firmly against the adjusting plates. 7 VERSO 12-72 VERSO ≥82 Tighten the fixing screw. UAB KOMFOVENT we reserve the right to make changes without prior notice VERSO Pro2_installation…
-
ANNEX NO. 2
WARRANTY INFORMATION Dear Customer, KOMFOVENT thanks you for your choice. We are pleased that you have chosen us and will strive to ensure you are satisfied with your purchased product. To avoid misunderstandings, we kindly ask you to read the installation and operating instructions of the product…
-