HANDBOK FÖR INSTALLATION OCH ANVÄNDING
ÅÃ×ÅÉÑÉÄÉÏÅÃÊÁÔÁÓÔÁÓÇÓÊÁÉËÅÉÔÏÕÑÃÉÁÓ ENGLISH ESPAÑOL MANUAL DE INSTALAÇÄO E DE FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING SVENSKA Do not perform installation work, without referring to our installation manual. No realice la instalación de este equipo, sin…
-
PRECAUCIÓN – Riesgos o prácticas poco seguras que PODRÍAN provocar lesiones
personales de menor importancia o daños en el producto u otros bienes. VORSICHT – Gefahrenquellen oder leichtfertige Vorgehensweisen, die geringfügige Schäden am Produkt oder an Sachen oder leichte Verletzungen verursachen können. ATTENTION – Utilisation dangereuse ou sans garantie de sécurité qui…
-
1 1 1. SAFETY SUMMARY Õ DANGER: DO NOT pour water into the central station. This product is equipped with electrical parts. If poured, it will cause a serious electrical shock. Ô WARNING: DO NOT perform installation work and electrical wiring connection by yourself. Contact your distributor or…
-
/ INSTALLATION WORK
2 2 2.3. INSTALLATION SPACE In case of installing the central stations in the vertical direction, keep a distance more than 50mm between the central stations vertically. If the distance is insufficient, the front cover of the central station can not open wide enough. More than 50mm 2.4. INSTALLATION…
-
3 3 3. ELECTRICAL WIRING 3.1. ELECTRICAL WIRING Up to 8 Central Stations can be connected to the H-LINK. Outdoor Unit Central Station Terminal Terminal Board Board TB1 TB2 To be connected to the terminal board and of indoor unit or outdoor unit FG Power Supply H-LINK (AC 220V or To TB2…
-
4. GROUP SETTING In case that group setting is not performed, the indication of the central station is as shown below for checking indoor unit connection after turning ON the power supply. Completion of Connection Check Refrigerant Cycle on Connection Check In Case of Item 1 Below (14 Units…
-
4 5 Central Station Master Slave Slave Master Refrigerant No. Setting Indoor Unit RSW Setting Group Number Master Master Without Remote Control Switch 4.2.1. GROUP SETTING PROCEDURE Changing to Group Setting Mode 1. Depress the “CHECK” switch for 3 seconds during the units of all groups are…
-
“1” shows the master unit setting mode. Ref. No. of Outdoor Unit To Be Set (Can be changed by depressing the “∇” (TEMP) switch.) When the “SET” indication appears, the indicated indoor unit is set as the master unit. (When “SET” does not appear, the master unit is not set.) Address of Indoor Unit To…
-
4 7 2. Selection of Indoor Unit To Be Set: Change Ref. No. by depressing “∇” (TEMP) switch and I.U. Add. by “∆” (TEMP) switch, and select the indoor unit to be set. The indication is changed in order as shown below. Ô ATTENTION: - When the indication of Ref. No. is “- -”, the indication of I.U. Add.…
-
Setting of Slave Unit Indication of Slave Unit Setting Mode When the central station is changed to the slave unit setting mode, the LCD indication on the central station is as shown below. The indication of the group to be set is flickered. The Ref. No. and I.U. Add. indicates the address of the…
-
4 9 2. Selection of Indoor Unit To Be Set Change Ref. No. by depressing “∇ ” (TEMP) switch and I.U. Add. by “∆ ” (TEMP) switch, and select the indoor unit to be set. The indication is changed in order as shown below. Ô ATTENTION: - Ref. No. with no indoor unit connected and I.U. Add. not connected…
-
5 10 INPUT/OUTPUT FUNCTION CAUTION: - Up to 15 slave units can be set in one group (Max. 16 units (including the master unit) in one group). - For changing the setting of slave unit to another group, cancel the present slave unit setting and perform the setting for another group. - In case that all…
-
5 11 2. Changing to Demand Setting Mode Depress the “CHECK” switch and change the 7-segment indication for check to “5” (Demand Setting Mode). The LCD indication of the central station is as shown below. “5” shows the demand setting mode. Ref. No. of Indoor Unit Set as Master Unit of Group To Be Set…
-
6 12 OPTION SETTING 6. OPTION SETTING 6.1. CHANGING TO OPTION SETTING MODE Changing to Option Setting Mode 1. Depress the “CHECK” switch for more than 3 seconds while all the groups are stopped. The central station is changed to the option setting mode and the “CHECK” indication appears, and “1”…
-
7 13 Setting Procedure 1. Depress the “CHECK” switch and select the setting item A – E. 2. Select the group to be set by depressing the “GROUP” switch. 3. Depress the “RUN/STOP” switch, the option setting is done. At that time, the “Ø” indication appears and the “SET” indication also appear.…
-
7 14 INITIALIZATION OF CENTRAL STATION 2. Initialization When the central station is changed to the initializing mode, the LCD indication on the central station is as shown below. In this condition, depress the “RESET” switch, and the flickering “06” indication is changed to ON and the…
-
8 15 8. SWITCH NAMES AND FUNCTIONS Liquid Crystal Display Section The figure below shows all the indications for reference.The actual display during operation is different. Indication of Demand Control (Page 21) Indication of Group Number (Page 16) Indication of Timer (Page 21) Indication of…
-
9 16 OPERATION PROCEDURE 9. OPERATION PROCEDURE Group Selection and Monitoring Unit Operation Status The central station can control up to 16 groups by each group or simultaneously. (The selected groups can be operated and the unit operation status of the groups can be monitored.) NOTE: The group…
-
9 17 Setting of Operation Mode <Function> “COOL” Operation: To cool the room temperature by distributing the cooled air. “HEAT” Operation: To heat the room temperature by distributing the heated air. “DRY” Operation: To dehumidify more than standard cooling operation. “FAN” Operation: To circulate…
-
9 18 OPERATION PROCEDURE <FAN SPEED> Depress the “FAN SPEED” switch. By depressing the “FAN SPEED” switch, the indication is changed in the following order; HIGH MED LOW The above figure shows the case of setting “HIGH” fan speed. NOTE: - In case of dry operation, the fan speed is automatically…
-
9 19 Ô ATTENTION: The louver angle is automatically changed during heating operation for unit control. When heating operation is started When dry operation is started When temperature controller is activated The louver angle is automatically changed. When the discharged air temperature is increased…
-
9 20 OPERATION PROCEDURE Prohibiting Operation by Remote Control Switch <Function> To prohibit the operation by the remote control switch. When this function is available, the “CENTRAL” indication appears on the LCD on the remote control switch and the operation by the remote control switch is not…
-
9 21 Timer Operation <Function> To set the schedule operation “available” or “not available” by the signal from the control timer in case of connection with the control timer (PSC-5T; Option). The schedule operation can be set “available” or “not available” individually for each unit, however, the…
-
9 22 OPERATION PROCEDURE <DEMAND> The “DEMAND” is indicated when the demand input is set by the outside input function. The indication is indicated for the group with demand setting and the “DEMAND” indication flickers when the demand signal is input. Contact your distributor or dealer of HITACHI…