Текст инструкции
-
FUNCIONAMENTO BRUGER- OG MONTERINGSVEJLEDNING INSTALLATIE- EN BEDIENINGSHANDLEIDING HANDBOK FÖR INSTALLATION OCH ANVÄNDING ÅÃ×ÅÉÑÉÄÉÏÅÃÊÁÔÁÓÔÁÓÇÓÊÁÉËÅÉÔÏÕÑÃÉÁÓ ENGLISH SVENSKA Do not perform installation work, without referring to our installation manual. No realice la instalación de este equipo…
-
– Hazards or unsafe practices which COULD result in minor personal injury or
CAUTION product or property damage. PRECAUCIÓN – Riesgos o prácticas poco seguras que PODRÍAN provocar lesiones personales de menor importancia o daños en el producto u otros bienes. VORSICHT – Gefährliche oder unsichere Anwendung, die geringfügigen Personen-, Produkt- oder Sachschaden verursachen…
-
1 1 1. SAFETY SUMMARY Õ DANGER: DO NOT pour water into the control timer (hereafter called “Timer”). This product is equipped with electrical parts. If poured, it will cause a serious electrical shock. Ô WARNING: DO NOT perform installation work and electrical wiring connection by yourself. Contact…
-
/ INSTALLATION WORK
2 2 2.3. INSTALLATION SPACE In case of installing the Timers in vertical line, keep a distance more than 50mm between the Timers vertically. If the distance is insufficient, the front cover of the Timer can not open wide enough. More than 50mm 2.4. INSTALLATION PROCEDURES] 1. Insert the edge of the…
-
Lead the cable through the groove
Attach the stopper to the cable at the inside of the draw-out hole. Twist Pair Cable Cable Band (FieldSupplied) Accessory Cable Band (Field-Supplied) Cable NOTE: In case of connecting the accessory cable to the connector, remove the protection case. Connector Terminal Board Attach the Timer onto…
-
/ INSTALLATION WORK
2 4 When Using Switch Box Prepare a field-supplied JIS Box (JIS C 8336-1988). Attach the holding bracket onto the switch box. The following 5 types are available. 1. Switch Box for 1 Controller (Without Cover) 2. Switch Box for 2 Controllers (Without Cover) 3. Switch Box for 1 Controller (With…
-
3. ELECTRICAL WIRING Use this Timer with Remote Control Switch or Central Station. - CAUTION: Use the twist pair cable (1P-0.75mm ) as a transmitting wire cable for prevention of the 2 malfunction. In case of a cable length less than 30 m also can be used: - Shielded pair cable (Shield connected to…
-
/ SETTING OF DIP SWITCH
4 6 4. SETTING OF DIP SWITCH Set the two dip switches on the PCB as follows. (The factory-settings for dip switches of DSW1 and DSW2 are all OFF.) Dip Switch Setting Pin No. DSW1 4 Contents of Setting DSW Setting OFF ON For Address Setting Refer to the table below. Setting is required only when…
-
5 7 5. SWITCH NAMES AND FUNCTIONS 5.1. LIQUID CRYSTAL DISPLAY SECTION The figure below shows all the indications for reference. The actual display during operation is different. Setting Switch of Present time Indication Operation switch Model: PSC-5T Order No:60299957 ❶ Indication of Present Time…
-
/ OPERATION PROCEDURE
6 8 6. OPERATION PROCEDURE SETTING PRESENT DAY AND PRESENT TIME (<Example> present Day: Friday, Present Time: 5:15 PM). During the setting mode, the setting of the present time is not available when depressing the “PRESENT” switch more than 3 seconds. 1. Supply power to the unit. Ô ATTENTION…
-
There are 2 (two) patterns (A or B) set for the weekly schedule. Each pattern can be set with 3 (three) times ON/OFF settings for each weekly day. <Function> To select the pattern for setting and operating the schedule. The schedule of A or B pattern can be set for each week and changed for a…
-
6 10 OPERATION PROCEDURE 3. Select the weekly day to set ON/OFF control by depressing the “DAY” switch. By depressing the “DAY” switch, the flickering “W” mark moves in order of “Sun → Mon → → Sat”. Depressing the “DAY” switch after “Sat”, all the “W” marks (from “Sun” to “Sat”) are flickered. In…
-
SETTING RUNNING DAY
<Function> To set the day for actual operation of the running schedule set before. (Though the ON time and OFF time are set, the schedule operation is not available unless the running day is set.) <Example> “B” pattern, Tuesday 1. Depress the “SET/MONITOR” switch. The timer is changed to the setting…
-
6 12 OPERATION PROCEDURE 3. Select the day to be set as “holiday” by depressing the “DAY” switch. Refer to 3. “Setting ON/OFF Time” for the indication of the “W” mark. The right figure shows the case of selecting the day “Tuesday”. 4. Depress the “HOLIDAY” switch, the “HOLI” indication is turned on…