Direct Drive Compact Air Handling Units
WESPAK 1.39, 2.69 & 3.99 Engineering Data Manual EDM WPKDD-A.2GB Date : June 2007 Supersedes : TM WPKDD-A.1GB/02.07
-
General Specifications
Introduction Coils Wespak direct drive compact air handling units are designed, in a modular construction, to meet the heating and air conditioning requirements of all medium-size areas. 2-row (heating coils) or 4-row coils (water or direct expansion cooling coils), with copper tubes and aluminium…
-
Description of Basic Sections
Fan section with fan and drive motor. Can be equipped with filter (synthetic type with G2 efficiency or metallic type with G1 efficiency). Coil section which can take a choice of cooling coil (chilled water or direct expansion), moisture eliminator, heating coil (hot water or electric) and filter…
-
Unit Coding
WESPAK 2.69 H M G 49 A Air outlet A - B - C Air inlet D - E Position Identification of basic sections * see notes For two-section air handling units only 0 : Heating coil 1 : Cooling coil 2 : Heating coil + cooling coil 3 : Cooling coil + heating coil 4 : Filter + heating coil + cooling coil 5…
-
Air Inlet and Outlet Arrangement
A B C D Fan discharge arrangement A, B, D and E arrangement can only be obtained with the use of a separate fan section n° 9. E Fan suction arrangement Single section WESPAK unit does not allow a 90° in/out air flow. No possibility to have an integrated filter in fan section n° 9. Double…
-
Mounting Possibilities
SINGLE SECTION UNITS (HORIZONTAL) Arrangement HP0 Arrangement HP1 Arrangement HP2 Arrangement HP3 Arrangement HP4 Arrangement HP5 Arrangement HP6 Arrangement HP7 See page 20 for overall dimensions and page 26 for weights. FAN SECTION Arrangement HM8 Arrangement VM8 Arrangement HM9A Arrangement HM9D…
-
Mounting Possibilities (continued)
-
таблицы и схемы — в просмотре
-
Options and Accessories
6-row water cooling coil BF6 Moisture eliminator EL Direct expansion coil BD Air-to-air heat recuperator RP 12 mm metallic filter with G1 efficiency replacing standard filter FM1 Electric heating coil 1 stage BE1 2 stages BE2 3 stages BE3 2-way mixing box with face and top dampers MD1 External…
-
Quick Selection - Air flow/External Static Pressure
-
Quick Selection - Air flow/External Static Pressure (continued)
Fan section incl. G2 filter and cooling coil External static pressure (Pa) Air flow (m3/h) LS - MS - - - 257 1.39 HS Air flow (m3/h) 2.69 1100 1300 1500 1700 - - - - - 201 120 - - - - - - - - - 700 1000 1300 1600 1900 2200 2500 2800 3100 LS - - - - - - MS - - - - - HS - - - - - - Air flow (m /h)…
-
Fan Performance Curves
Wespak 1.39 Static pressure (Pa) 300 200 LS MS HS 1500 2000 1000 Air volume (m /h) 3 Wespak 2.69 Static pressure (Pa) 300 200 LS HS MS 100 0 1000 2000 3000 4000 Air volume (m /h) 3 Wespak 3.99 Static pressure (Pa) 300 200 LS MS HS 100 0 2000 3000 4000 5000 Air volume (m3/h) Note : Indicated static…
-
Air Pressure Drop Curves
Air-to-air plate heat recuperator 2 Cooling coil and silencer 3 G4 synthetic filter Heating coil - Discharge plenum size 1.39 G1 metal filter - Droplet eliminator Mixing box - Discharge plenum size 2.69 6 G2 synthetic filter - Discharge plenum size 3.99 7 Electric heating coil Use of droplet…
-
Heating Capacity
NOMINAL CAPACITY Air : 15 °C - Water : 90 / 70 °C 60 3.99 50 2.69 Heating capacity (kW) 40 30 1.39 1000 2000 3000 5000 Air flow (m3/h) Correction factors for different operating conditions Inlet air temperatures (°C) Water temperatures (°C) -5 -10 -15 90 / 70 0.91 1.00 1.09 1.19 1.28 1.38 1.49 1.59…
-
Cooling Capacity
Wet bulb temperatures (°C) 21 22 t Entering water temp. (°C) Sizes 15 1.39 2.69 3.99 32 Air flow (m3/h) A B C D E - - Cooling capacity (kW) kW 103 kcal/h 103 kcal/h 103 kcal/h Cooling Capacity (kcal/h) 25 Dry bulb temperatures (°C) 24 28 E kW 13 kW D 30 C B A 1.39 2.69 3.99 Data are given for…
-
Air-to-Air Plate Heat Recuperator
Recuperator nominal efficiency curve Multiplier 65 Efficiency (%) Unit size 1.39 2.69 3.99 500 1000 1000 1500 2000 1000 2000 2000 3000 3000 4000 5000 Air volume (m3/h) Efficiency (%) 60 0.60 1.20 0.70 1.15 0.80 1.10 0.90 1.05 1.00 1.00 1.10 0.95 1.20 0.90 1.30 0.85 1.40 0.80 1.50 0.75 1.60 0.70 1.70…
-
Technical Specifications
Cooling coils Heating coils Sizes 1.39 Rows 4 4 Fin spacing (*) 2.1 2.1 Front area (m2) 0.19 0.3 Water connections 2.69 3.99 Sizes 1.39 4 Rows 2.1 Fin spacing (*) 2.1 2.1 2.1 0.41 Front area (m2) 0.19 0.3 0.41 Water connections 26/34 male threaded Water volume (l) 2.3 3.4 3.99 26/34 male threaded…
-
Technical Specifications (continued)
Fan motor Max. running current (A) * Sizes Motor absorbed power * (W) Voltage Number of wheels LS MS HS 1.39 740 220-240/1/50 1 1.4 2.4 3.3 2.69 960 220-240/1/50 2 2.02 3.0 4.22 3.99 1185 220-240/1/50 2 3.3 3.95 5.01 * Characteristics in accordance with the maximum air flow given by fan performance…
-
Dimensions of Options and Accessory
2-way mixing box "MD1" B 30 370 A 2-way mixing box "MD2" B 320 25 A In-line 3-way mixing box "MD3" B Sizes 1.39 2.69 3.99 A B 582 970 1320 762 1150 1500 Dimensions in mm. Page A Mixing boxes are supplied with ball joint assembly suitable for Ø 6 mm linking rod.
-
Dimensions of Options and Accessory (continued)
Superposed 3-way mixing box "MD3" B A Antifreeze damper "AG" B C Sizes 1.39 2.69 3.99 A B 582 970 1320 762 1150 1500 C 586 974 1324 Antifreeze damper and mixing box are supplied with ball joint assembly suitable for Ø 6 mm linking rod. Dimensions in mm. Page 23
-
External filter : FA1 - FA2 - FA4 B Minimum space for filter access Sizes 1.39 2.69 3.99 Left or right side Top or bottom side A 90 Plate heat exchanger for heat recovery : RP C 740 740 Filter access (service side) 1.39 2.69 3.99 PVC Ø30/32 condensate drain connection on service side Inlet duct…
-
Inlet and Bracket Arrangements
-
WinPak Selection Software
To select the most suitable Wespak direct drive compact air handling units according to job specifications, Airwell provides a computer selection program operating under MS Windows System. This selection software allows you to select quickly the best solution for each application. For any specific…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.
Другие файлы документа
- Модели Wespak 1.39, 2.69, 3.99 Мини-центральные кондиционеры Airwell. Руководство по монтажу и техническому обслуживанию.PDF · 240.14 Kb
- Wespak 4.05, 5.05, 6.05 Мини-центральные кондиционеры Airwell Wespak. Инструкция по монтажу и эксплуатации.PDF · 1.47 Mb
- Wespak 1.39, 2.69, 3.99 Компактные мини-центральные кондиционеры Airwell Wespak. Инструкция по монтажу и эксплуатации.PDF · 1.62 Mb
- Wespak 4.05, 5.05, 6.05 Мини-центральные кондиционеры Airwell Wespak. Техническое руководство.PDF · 1.63 Mb
- Wespak 4.05, 5.05, 6.05 Мини-центральные кондиционеры Airwell Wespak. Технический каталог 2005г.PDF · 4.29 Mb
- Wespak 1.39, 2.69, 3.99 Компактные мини-центральные кондиционеры Airwell Wespak. Справочное руководство.PDF · 621.72 Kb