Installation and maintenance manual
Manuel d’installation et de maintenance WESPAK 1.39, 2.69 & 3.99 English Français Direct drive compact air handling units Centrales compactes de traitement d'air à entraînement direct IOM WPKDD-N.3GBF/09.08 Part number / Code : Q3NSTE878 Supersedes / Annule et remplace : IOM WPKDD-N2GBF/11.06
-
Introduction p.2 Safety Precautions p.2 Description p.3 Inspection and storage p.3 Electrical data p.3 Operating limits p.3 Dimensional Data and Weight p.4 Installation p.7 Unit handling p.7 Installation location p.7 Instructions d'installation p.7 Water Connections p.8 Water coil connections p.8…
-
1 - Introduction
The purpose of this manual is to provide the installation, start-up, operating and maintenance rules to the users of the small packaged air handling units. It does not give a full description of all maintenance works assuring the long life and reliability of this type of equipment. Only the services…
-
English
3 - Description 3.1 - Inspection and storage Do not stand or transport the unit on its end. Temporary storage must be indoor, completely sheltered from rain, snow, etc. When the equipment is received, all items must be carefully checked against the bill of lading to be sure all crates and cartons…
-
4 - Dimensional Data and Weight
-
4.1 - Dimensional Data (cont'd)
Modules : VP1, VP6, VP7, VM80, VM90 320 B 25 A Minimum space for servicing 51 Hole provision for 90 electric power supply C Modules : VM39, VM49, VM59 B 370 A Minimum space for servicing 1110 51 C Hole provision for 90 electric power supply Modules : VM19, VM69, VM79 370 MODELS 1.39 2.69 3.99 A 582…
-
4 - Dimensional Data and Weight (cont'd)
-
5.1 - Unit Handling
Minimum clearances on service side Be careful to avoid rough handling on the unit. Do not lift the unit by the condensate outlet or by the water connections. Use a lifting truck to facilitate the unit installation. MODELS 1.39 2.69 3.99 mm 779 1167 1517 Warning Warning Do not install the unit in a…
-
6 - Water Connections
6.1 - Water Coil Connections 6.2 - Condensate Drain Connection Each water coil is equipped with headers having 1" male threaded type connection on water supply and water return. The condensate drain pan is supplied with 5/8" OD copper tube outlet. Ensure that water condensate will be properly…
-
7.1 - Unit connection
Caution All units are allowed for being connected on a power supply of 230 V ±10 % / 1ph / 50 Hz + Earth. Do not wire two units or more with one fan speed switch or control thermostat without using auxiliary relays. Before undertaking any electrical connection, make sure that the fan motor is…
-
7 - Electrical Connections (cont'd)
CMVM fan speed selector switch FMA Earth Yellow/Green � Neutral Blue HS HS Black MS MS Violet LS Red � � LS 230/1/50 SUPPLY VOLTAGE � EARTH � � � � � � � � � NEUTRAL FIELD WIRING LIVE FACTORY WIRING � � ��� ���� FMA M R LS MS HS Fan motor assembly Electrical junction block Relay Low speed Medium…
-
Example of wiring diagram with TRM-FA remote control including on/off switch, fan
speed switch, room thermostat and summer/winter manual change-over FMA HS Black Yellow/Green LS Red Blue R MS MS Violet R HS R LS V M EARTH 1N230V~ NEUTRAL FIELD WIRING LIVE FACTORY WIRING N L T.R.M. FMA M TRM LS MS HS V R WE 46963 C Fan motor assembly Electrical junction block Wall thermostat Low…
-
7 - Electrical Connections (cont'd)
-
3. Ensure that air filter is clean and properly installed
1. Make sure that system piping has been cleaned and all the air has been purged, before starting up the unit. 4. Make certain that fan rotates freely. 2. Check that condensate drain pipe is connected and allows correct drainage. Also check that it is connected to a siphon. 5. Make sure that all…
-
10 - Maintenance (cont'd)
10.4 - Fan motor assembly 10.6 - Water Piping System There is no particular maintenance on fan motor assembly. Once a year, drain the piping system and check the furringup of the pipes. The units are equipped with permanently lubricated fan motor bearings. It is not necessary to add oil. However…
-
As part of our ongoing product improvement programme, our products
are subject to change without prior notice. Non contractual photos. Dans un souci d’amélioration constante, nos produits peuvent être modifiés sans préavis. Photos non contractuelles.