Installation and maintenance manual
Manuel d’installation et de maintenance WESPAK 4.05, 5.05 & 6.05 English Français Belt drive compact air handling units Centrales compactes de traitement d'air à entraînement par courroies IOM WPKBD-N.2GBF/09.08 Part number / Code : Q3NSTE864 Supersedes / Annule et remplace : IOM WPKBD-N1GBF/06.05
-
The purpose of this manual is to provide the installation, start-up, operating and maintenance rules to the users of the compact air handling units. It does not give a full description of all maintenance works assuring the long life and reliability of this type of equipment. Only the services of…
-
3 - Inspection and Storage
When the equipment is received, all items must be carefully checked against the bill of lading to be sure all crates and cartons have been received. Do not stand or transport the unit on its end. Temporary storage must be indoor, completely sheltered from rain, snow, etc. The units are shipped on…
-
4 - Technical Features (continued)
4.2 - Physical data (cont'd) MODELS 4.05 5.05 6.05 COOLING COILS Copper tubes - Aluminium fins - 2.1 mm spacing Type Finned length mm Number of tubes per row 1360 1800 1800 Number of rows Number of circuits Number of empty tubes Header diameter (inlet/outlet) mm 33 / 42 - 33 / 42 33 / 42 - 33 / 42…
-
5 - Dimensions
5.1 - Fixation dimensions a) By threaded rods only Dimensions (mm) Fan only casing or electric heater casing Sizes 4.05 5.05 6.05 A B 1498 1940 1940 b) By threaded rods and hanger rails Dimensions (mm) Sizes A B 4.05 5.05 6.05 1498 1940 1940 C D 1074 1150 1274 1350 1274 1350 E G F H G2 filter G4…
-
5 - Dimensions (continued)
-
таблицы и схемы — в просмотре
-
6.1 - Unit handling
English 6 - Installation Warning Be careful to avoid rough handling on the unit. Do not lift the unit by the condensate outlet or by the water connections. Use a lifting truck to facilitate the unit installation. Do not install the unit in a machinery shop or kitchen where vapour from oil or its…
-
6 - Installation (continued)
6.4 - Installation instructions 1. Prepare the fixing center distances at the ceiling for each casing (see section "Dimensions" for fixing center distances). 2. Fix the suspension kit (optional) composed of threaded rods only or threaded rods and hanger rails. 3. In the case that the suspension kit…
-
7.1 - Definition of the service side
English 7 - Water Connections Caution The service side, the side where coil connections are located, is defined left-hand or right-hand, when observer looks at the unit from above in the direction of air. If the units are not equipped with control valves, the air temperature must not exceed 50 °C.…
-
7 - Water Connections (continued)
7.3 - Condensate drain connection 7.4 - Winterizing water coils The condensate drain pan is supplied with 7/8" OD copper tube outlet. In winter, due to a general shutdown of the installation or a failure of outdoor air damper control, coil freeze-up may occur. Ensure that water condensate will be…
-
8.1 - Unit connection
-
9 - Preliminary Checks Before Start-up
When performing startup and service, thorough safety precautions should always be taken. 5. Check that all holes for cable entry are tightly sealed. 6. Check tightness of setscrews on motors, bearings and fans. Only qualified individuals should perform these functions. 1. Check that the unit is…
-
9.1 - Adjustable pulley adjustment
3. Securely tighten the set screw "B" on the flat surface of the pulley fixed sheave. Mounting 4. Put on the belt and adjust its tension. Do not force the belt on the pulley sheaves (see paragraph "Belt tensioning"). 5. The future adjustments should be performed by loosening the belt tension and by…
-
10 - Maintenance
10.2 - Condensate drain pan It is recommended to proceed to the following maintenance works in order to ensure a good operation of the unit. The condensate pan must be checked periodically to make sure that drain piping is not obstructed. Caution If required, it must be cleaned and rinsed. Before…
-
Step 3 : Fans dismounting
English 10 - Maintenance (continued) Step 3 Remove the first and the second support rails of the fans, after releasing the 3 fixing screws of the rails to the vibration isolators, and the 6 fixing screws of the fans to the support rails. Note : On sizes 5.05 and 6.05, it is not necessary to remove…
-