Инструкция на Чиллеры спиральные с водяным охлаждением конденсатора York серии YCWL0240SE-YCWL0395SE, YCWL/YCRL0200HE - YCWL/YCRL0610HE. Рyкoводство по эксплуатации.
Смотрите также: Основной документ →
Загружаем документ…
Текст инструкции
-
& YCWL / YCRL0200HE-YCWL / YCRL0610HE INSTALLATION, OPERATION & MAINTENANCE Revision 5 Form 201.26-NM2 (0709) 035-21965-110 WATER AND REMOTE AIR COOLED CHILLERS WITH SCROLL COMPRESSORS STYLE A (188-580 KW) SE - STANDARD EFFICIENCY & HE - HIGH EFFICIENCY Zafiro R410A
-
IMPORTANT!
Read BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure…
-
CHANGEABILITY OF THIS DOCUMENT
In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. While Johnson Controls makes no commitment to update or provide current information automatically to the manual owner, that information, if…
-
GENERAL CHILLER INFORMATION & SAFETY
INTRODUCTION YORK YCWL chillers are manufactured to the highest design and construction standards to ensure high performance, reliability and adaptability to all types of air conditioning installations. The unit is intended for cooling water or glycol solutions and is not suitable for purposes other…
-
• ARI Standard 550/590 - Positive Displacement
Compressors and Water Cooled Rotary Sdrew Water Chilling Packages. • Conform to UL code 1995 for construction of chillers and provide ETL/cETL listing label. • OSHA - Occupied Safety and Health Act. • ARI 370 Sound Rating of Large Outdoor Refrigeration and Air Conditioning Equipment. FLUORINATED…
-
MISUSE OF EQUIPMENT
Electrical Suitability for Application The unit must be earthed. No installation or maintenance work should be attempted on the electrical equipment without first switching power OFF, isolating and lockingoff the power supply. Servicing and maintenance on live equipment must only be performed by…
-
Safety Labels
The following labels are fixed to each unit to give instruction, or to indicate potential hazards which may exist. 1 White symbol on blue background For safe operation, read the Instructions first Black symbol on yellow background Warning: This machine may start automatically without prior warning…
-
MATERIAL SAFETY DATA
Refrigerant Safety Data R410A: COMPOSITION/INFORMATION ON INGREDIENTS Components Material PENTAFLUOROETHANE (HFC-125) DIFLUOROMETHANE (HFC-32) CAS Number 354-33-6 75-10-5 % 50 50 HAZARDS IDENTIFICATION Inhalation of high concentrations of vapour is harmful and may cause heart irregularities…
-
Refrigerant Safety Data R410A
Extinguishing Media As appropriate for combustibles in area. Fire Fighting Instructions Cool cylinder with water spray or fog. Self-contained breathing apparatus (SCBA) is required if cylinders rupture and contents are released under fire conditions. Water runoff should be contained and neutralized…
-
Refrigerant Safety Data R410A
Polymerization Polymerization will not occur. Other Hazards Decomposition : Decomposition products are hazardous. This material can be decomposed by high temperatures (open flames, glowing metal surfaces, etc.) forming hydrofluoric acid, and possibly carbonyl halides. TOXICOLOGICAL INFORMATION The…
-
Oil Safety Data YORK 'V' Oil
Section 1 Substance Product Information 1 Product Trade Name: YORK "V" Oil. Chemical Name: Carboxylic Ester. Section 2 Components and Hazard Statement This product is non-hazardous. This material has no known hazards under applicable laws. Section 3 Safe Handling and Storage Handling: Keep…
-
Thermal & Acoustic Materials Data
Health Hazard & First Aid Stability / Reactivity Handling / Use / Disposal Fire & Explosion 14 Toxicity Index <10 to NES713 Issue 3 (1991): Non-hazardous, non-toxic. No first aid necessary. Stable. No special handling precautions required. Dispose of according to local laws and regulations governing…
-
PRODUCT DESCRIPTION
2 INTRODUCTION Compressors YORK Zafiro 410A chillers are designed for water or water-glycol cooling. The unit has suction-cooled, hermetic scroll compressors. High efficiency is achieved through a controlled orbit and the use of advanced scroll geometry. The compressors incorporate a compliant…
-
Refrigerant Circuits
Condenser (YCWL units only) Two independent refrigerant circuits are provided on each unit. Each circuit uses copper refrigerant pipe formed on computer controlled bending machines to reduce the number of brazed joints resulting in a reliable and leak resistant system. The twin-refrigerant circuit…
-
The microprocessor control includes
• Day, date and time • Automatic control of compressor start/stop, anticoincidence and anti-recycle timers, automatic pumpdown on shutdown, evaporator pump and unit alarm contacts. Automatic reset to normal chiller operation after power failure. • Daily start/stop times • Remote water temperature…
-
ACCESSORIES AND OPTIONS
Soft Starters Factory mounted soft starters reduce the inrush current to the last compressor on each refrigerant circuit. They are preset so that no field adjustment is required. Power Factor Correction Factory mounted passive (static) power factor correction capacitors to correct unit compressor…
-
REFRIGERANT FLOW DIAGRAM
YCWL Low-pressure liquid refrigerant enters the cooler tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the cooler shell. Low-pressure vapour enters the compressors where pressure and superheat are increased. High pressure superheated…
-
UNIT MODEL NUMBER NOMENCLATURE
NOMENCLATURE The model number denotes the following characteristics of the unit. Y C W L - 0446 - H - E - 50 - X - AA YORK CHILLER WATER COOLED SCROLL COMPRESSOR MODEL NUMBER UNIT DESIGNATOR S - Standard Efficiency H - High Efficiency 20 DESIGN SERIES/ DEVELOPMENT LEVEL DOL STARTING VOLTAGE CODE…
-
HANDLING AND STORAGE
DELIVERY AND STORAGE To ensure consistent quality and maximum reliability, all units are tested and inspected before leaving the factory. Units are shipped completely assembled and containing refrigerant under pressure. Units are shipped without export crating unless crating has been specified on…
-
таблицы и схемы — в просмотре
-
INSTALLATION
Location Requirements To achieve optimum performance and trouble-free service, it is essential that the proposed installation site meet with the location and space requirements for the model being installed. For installation in equipment rooms near noise-critical areas, common walls should be of…
-
Pipework and fittings immediately next to the heat
exchangers should be readily de-mountable to enable cleaning prior to operation, and to facilitate visual inspection of the exchanger nozzles. Each heat exchanger must be protected by a strainer, preferably of 20 microns, fitted as close as possible to the liquid inlet connection, and provided with…
-
Condenser Cooling Liquid System
Refrigerant Relief Valve Piping The compressor, cooler and condensers are each protected against internal refrigerant over-pressure and fire by refrigerant relief valves. The pressure relief valve is set at the design pressure of the system and has discharge capacity required by the relevant…
-
Condenser Cooling Liquid Systems
Inlet Temperature Control (by others) For primary cooling of units, condensers are usually piped in conjunction with a cooling tower or a dry cooler, although in some cases they can be cooled by well water. For a cooling tower / dry cooler system, the simplest forms of control are to use fan…
-
CONDENSERLESS UNIT REFRIGERANT PIPING
Condenser Below Chiller General When the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due the vertical rise. The value of static head loss of 11.3 kPa/m must be added to the friction loss pressure drop in addition to all…
-
To ensure that no eddy currents are set up in the power
panel, the cables forming each 3 phase power supply must enter via the same cable entry. Temperature Cutout’ or any of the compressors are running or the daily schedule is not calling for a shutdown with the unit switch on. All sources of supply to the unit must be taken via a common point of…
-
Remote Load Limiting
Load limiting prevents the unit from loading beyond a desired value. The unit % load limit depends on the number of compressors on the unit. The load limit inputs to terminals 13 and 21 work in conjunction with the PWM input to terminals 13 and 20. Heat Pump Kit When the special quotation…
-
CONNECTION DIAGRAM
-
COMMISSIONING
PREPARATION Commissioning of this unit should only be carried out by Johnson Controls Authorised personnel. The unit On/Off switch on the front of the control panel has been set to the Off position at the factory. This switch must remain in the Off position, preventing running of the unit until…
-
Soft Start (Option)
Due to vibration during transport the soft starter internal bypass contactor may be in a undefined state. If the following procedure is not followed this may result in the compressor momentarily starting when the unit power is first turned on. IMPORTANT During commissioning or if the soft start is…
-
FIRST TIME START-UP
During the commissioning period there should be sufficient heat load to run the unit under stable full load operation to enable the unit controls, and system operation to be set up correctly and a commissioning log taken. Read the following section in conjunction with the MBCS Manual, then proceed…
-
таблицы и схемы — в просмотре
-
TECHNICAL DATA
-
OPERATING LIMITATIONS - YCWL
YCWL0240 Min. Max. Standard Efficiency (SE) Models Liquid Outlet Temperature (Water) Liquid Outlet Temperature (Glycol) Liquid Outlet Temperature Range Chilled Liquid Evaporator Flow Rate Evaporator Pressure Drop Maximum Water Side Pressure Liquid Outlet Temperature Liquid Outlet Temperature Range…
-
OPERATING LIMITATIONS - YCRL
YCRL Condenserless Models Liquid Outlet Temperature (Water) Liquid Outlet Temperature Range Chilled Liquid Evaporator Flow Rate Evaporator Pressure Drop Maximum Water Side Pressure Saturated Discharge Temperature Maximum Refrigerant Side Pressure Power Supply Voltage 400V, 3 ~, 50 Hz (nominal)…
-
PHYSICAL DATA - YCWL
Standard Efficiency (SE) YCWL Models Number of refrigerant circuits Circuit 1 / Circuit 2 Refrigerant Charge Oil Charge Circuit 1 / Circuit 2 Number of Compressors Type Compressor Capacity Control Evaporator Condenser Dimensions Weight Number of Evaporator Type Water Volume Water Connections Number…
-
PHYSICAL DATA - YCRL
Condenserless YCRL Models Number of refrigerant circuits Oil Charge Circuit 1 / Circuit 2 Number of Compressors Type Compressor Capacity Control Number of Evaporator Type Water Volume Water Connections Discharge Line (circuit 1 - circuit 2) Connection Sizes Liquid Line (circuit 1 - circuit 2) Length…
-
ELECTRICAL DATA - YCWL/SE MODELS
Standard Efficiency Units Start up Amps Start up Amps (2) (2) Direct Amps Amps on Line at 360V at 400V without Power Factor Correction with Optional Power Factor Correction Fitted Optional Soft Start Nominal Running Conditions Maximum Running Conditions (1) YCWL 0240 0291 0346 0395 kW Amps at 400 V…
-
ELECTRICAL DATA - YCWL/YCRL HE MODELS
High Efficiency Units Start up Amps Start up Amps (2) (2) Direct Amps Amps on Line at 360V at 400V without Power Factor Correction with Optional Power Factor Correction Fitted Optional Soft Start Nominal Running Conditions YCWL/ YCRL 0200 0230 0260 0301/0300 0346/0345 0385 0425 0446/0445 0531/0530…
-
YCWL
-
DIMENSIONS - YCWL0385HE, YCWL0446HE, YCWL0531HE AND YCWL0610HE
-
YCWL
-
RELIEF
VALVE INLET OUTLET DIMENSIONS - YCRL0200HE, YCRL0230HE, YCRL0260HE, YCRL0300HE, YCRL0345HE 46
-
Dim
-
RELIEF
VALVE INLET EE OUTLET DIMENSIONS - YCRL0385HE, YCRL0445HE, YCRL0530HE AND YCRL0610HE 48
-
Dim
-
YCWL WEIGHT DISTRIBUTION & VIBRATION ISOLATOR DATA
-
таблицы и схемы — в просмотре
-
YCRL WEIGHT DISTRIBUTION & VIBRATION ISOLATOR DATA
-
NEOPRENE ISOLATOR INSTALLATION AND ADJUSTMENT
Units shipped before 15 June 2008 "CS" Cap Screw D "MBD" Max. Bolt Dia. Steel Plate - Top & Bottom Neoprene covered to prevent corrosion 6 BC H W L T Dimension (mm) Part No D H L T W BC CS MBD 029-24584-002 85.7 69.9 158.8 7.9 101.6 127.0 1/2 - 13 x 1" 13 029-24584-002 1/2 - 13 x 1" 13 INSTALLATION…
-
DURULENE ISOLATOR SPECIFICATIONS
-
DURULENE ISOLATOR INSTALLATION
Units shipped on or after 15 June 2008 TOP BOLT ("B") D TOP WASHER D ("C") CL 1. Read the following instructions before beginning installation. 2. Isolators are shipped fully assembled and are to be positioned in accordance with the submittal drawings or as otherwise reccomended. 3. Set isolators on…
-
25 MM ISOLATOR INSTALLATION AND ADJUSTMENT
Units shipped before 15 June 2008 Illustration shows single spring CIP-B or CIP-C mount. Mounting may be operated 1/2" above Free & Operating Height. EQUIPMENT BASE A Dowel Pin is 3/8" dia. for CIP-A & 1/2" thereafter NOTECIP Mounts are not to be used in seismic or wind load applications. FERROUS…
-
25 MM ISOLATOR SPECIFICATION
-
25 MM ISOLATOR INSTALLATION
Units shipped on or after 15 June 2008 UPPER HOUSING (D) EQUIPMENT BASE POSITIONING PIN (H) 0.25” min - 0.5” max LOWER HOUSING (C) NON-SKID ELASTOMERIC PAD (C) (B) 1. Read the following instructions before beginning installation. 2. Isolators are shipped fully assembled and are to be positioned in…
-
SEISMIC ISOLATOR INSTALLATION AND ADJUSTMENT
Units shipped before 15 June 2008 TO INSTALL AND ADJUST MOUNTS 1. Supports for mountings must be leveled to installation's acceptable tolerances. 2. Mountings not subjected to seismic or wind forces do not require bolting to supports. 3. Mountings subjected to seismic or wind forces must be bolted…
-
50 MM (SEISMIC) ISOLATOR SPECIFICATIONS
Units shipped on or after 15 June 2008 1-1/8" 5" 5/8" 2-3/4" 2-3/4" 12" 3/8" GAP 5/8-11UNC TYP. (4) Ø3/4" TYP.(4) 3/4" 7/8" 14" 1/2" LIMIT STOP & NUT 8-3/8" OPER. HEIGHT 12-1/4" 3-1/2" 3/8" 5" Weight Range (kgs)* 335 to 463 463 to 652 652 to 1018 *Values de-rated by 15% Type Y2 Y2 Y2 Colour…
-
50 MM (SEISMIC) ISOLATOR INSTALLATION AND ADJUSTMENT
Units shipped on or after 15 June 2008 ("A") ("E") CL ("G") ("E") GROMMET ("A") CL 1/4 - 3/8 GAP WASHER EQUIPMENT ("F") ("E") ("F") ("C") ("B") 1. Read the following instructions before beginning installation. 2. Isolators are shipped fully assembled and are to be positioned in accordance with the…
-
таблицы и схемы — в просмотре
-
UNIT OPERATION
GENERAL DESCRIPTION NORMAL RUNNING AND CYCLING The units are designed to work independently, or in conjunction with other equipment via a YORK ISN building management system or other automated control system. When operating, the unit controls monitor the chilled liquid system temperatures at the…
-
таблицы и схемы — в просмотре
-
MAINTENANCE
GENERAL REQUIREMENTS The units have been designed to operate continuously provided they are regularly maintained and operated within the limitations given in this manual. Each unit should be included in a routine schedule of daily maintenance checks by the operator/customer, backed up by regular…
-
SERVICE SCHEDULE
MINOR SERVICE Unit general: Check thermal insulation. Check vibration isolators. Check relief valves. Check for pipework damage. Check for leaks. Check moisture indicator. Check suction superheat. Check liquid subcooling. Check oil level. Check condition of oil. Check water flow. Check water…
-
TROUBLE SHOOTING
Competent Persons Trouble Shooting Guide PROBLEM No display on panel — Unit will not operate POSSIBLE CAUSE Mains supply to unit off. ACTION Switch on mains supply if safe to do so. Emergency stop device off. Check if remote emergency stop device is in the ‘OFF’ position. Turn to ‘ON’ position if…
-
PROBLEM
SYS X HIGH DSCH PRES displayed SYS X LOW SUCT PRESS displayed POSSIBLE CAUSE Discharge pressure cut-out incorrectly set. Air in refrigerant system. ACTION Adjust in accordance with recommended setting. Check for non-condensables (air) in system. Evacuate and recharge system. Excessive refrigerant…
-
Sensor Calibration Charts
Leaving Liquid Temperature (-BLLT) Temperature °C Resistance ohms -8 -6 -4 -2 14896 13388 12047 10856 9795 8849 8005 7251 6575 5970 5427 4937 Microboard Voltage Vdc 1.57 1.69 1.81 1.93 2.05 2.17 2.30 2.42 2.54 2.66 2.78 2.90 Sensor Voltage Vdc 3.43 3.31 3.19 3.07 2.95 2.83 2.70 2.58 2.46 2.34 2.22…
-
таблицы и схемы — в просмотре
-
SPARE PARTS
RECOMMENDED SPARES It is recommended that the common spare parts listed below are held for preventative of corrective maintenance operations. Details of unit spare parts are given in the Renewal Parts List 035-21977-000. Contact your local Johnson Controls Sales and Service Centre for information…
-
таблицы и схемы — в просмотре
-
DECOMMISSIONING. DISMANTLING AND DISPOSAL
Never release refrigerant to the atmosphere when emptying the refrigerating circuits. Suitable retrieval equipment must be used. If reclaimed refrigerant cannot be reused. It must be returned to the manufacturer. Never discard used compressor oil, as it contains refrigerant in solution. Return used…
-
таблицы и схемы — в просмотре
-
www.johnsoncontrols.com
FORM 201.26 NM2 (0709) Revision 5 Subject to change without notice. ALL RIGHTS RESERVED
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.