ENGINEERING GUIDE Revision 3 PC181-100 (GB 0809) AIR COOLED LIQUID CHILLERS WITH SCROLL COMPRESSORS STYLE A (Cooling Capacities: 180 kW to 520 kW) Tempo R410A
-
Table of Contents
TEMPO Features 3 Dimensions - YLAA0180SE & YLAA0210SE 32 Nominal Data. 4 Dimensions - YLAA0195HE 33 Specification 5 Dimensions - YLAA0240SE 34 Accessories and Options 6 Dimensions - YLAA0260HE, YLAA0285SE & YLAA0320SE. 35 Refrigerant Flow Diagram.. 8 Component Location Diagrams 9 Dimensions…
-
TEMPO Features
Buffer tank not normally required YORK TEMPO is a fully packaged air-cooled liquid chiller, with scroll compressors, designed to be located outside on the roof of a building or at ground level TEMPO requires a minimum water volume to satisfy only one minute of chiller operation at minimum cooling…
-
Nominal Data
YLAA - SE Cooling Capacity kW (1) Energy Efficiency Ratio (EER) (1/1a) Eurovent Class ESEER (2) Cooling Capacity kW (1) Energy Efficiency Ratio (EER) (1/1a) Eurovent Class Fan Speed Normal Low (LS) ESEER (2) Sound Pressure at 10 meters dB(A) (3) YLAA - HE Cooling Capacity kW (1) Energy Efficiency…
-
Specification
YLAA air-cooled chillers are completely factory assembled with all interconnecting refrigerant piping and wiring ready for field installation. The unit is pressure tested, evacuated, and fully factory charged with refrigerant R410A and oil in each of the independent refrigerant circuits. After…
-
The control panel includes
A Liquid Crystal Display (two display lines of twenty characters per line) with Light Emitting Diode backlighting for easy viewing A Colour coded 12-button keypad Customer terminal blocks for control inputs and liquid flow switch. Microprocessor Controls The microprocessor control includes: …
-
Multi-Chiller Sequencer
Dual speed fans The multi-chiller sequencer has been designed to manage up to four chillers, piped in parallel, from a common chilled water sensor. The sequencer is factory mounted in an IP55 panel with viewing window, lockable door and an electrical isolator. To be field fitted and wired to power…
-
Refrigerant Flow Diagram
43.0 bar Air Cooled Condenser Air Cooled Condenser (No Receiver) Receiver Heat Recovery Heat Exchanger DV HPC HPL -BDP PS Compressors 27.6 bar Evaporator -BSP DV LPC -BRLT -BLCT DV DV CHT LTC -YLLSV Components: Pressure Relief Valve Sight Glass Service (Ball) Valve Sensor Pressure or Temperature…
-
Component Location Diagrams
Power Panel Non-Fused Disconnect Switch Control Panel Compressor Evaporator Receiver Condenser Fans 9
-
Pump Body (Single or Dual) 2 Pump Motor (Single or Dual) 3 Flow Switch 10 4 Balancing valve with flow check and shut-off functions 5 Suction Guide with integrated strainer
-
Application Data
Location Requirements To achieve optimum performance and trouble-free service, it is essential that the proposed installation site meet with the location and space requirements for the model being installed. The clearances recommended are nominal for the safe and efficient operation and maintenance…
-
Where cross-winds may occur, any ductwork must be
supported to prevent side loading on the unit. If the ducts from two or more fans are to be combined into a common duct, back-flow dampers should be fitted in the individual fan ducts. This will prevent re-circulation of air when only one of the fans is running. Units are supplied with outlet guards…
-
A4
-
Location Clearances - SE & SELS Models
-
Installation of Vibration Isolators
An optional set of vibration isolators can be supplied loose with each unit. Pipework Connection The following piping recommendations are intended to ensure satisfactory operation of the unit. Failure to follow these recommendations could cause damage to the unit, or loss of performance, and may…
-
Connection Types and Sizes
D5=1.447 x L Standard pipework connections are of the Victaulic groove type. Where: D = minimum pipe internal diameter (cm) L = length of pipe (m). For connection sizes relevant to individual models refer to the physical data tables in this manual. Heat Recovery System If relief pipework is common…
-
Remote Emergency Stop Device
Control Wiring - System Inputs If required, a remote emergency stop device may be wired into the unit. This device should be rated at 20 amps, 110 V, AC-15. The device should be wired into terminals L and 5 in the power panel after removing the factory fitted link. All wiring to the control terminal…
-
Connection Diagram
-XTBC2 -F1 -XTBC1 -ARB -ARB A- A+ YLAA Customer Controls Evaporator pressure drop graph 0440HE 0485SE 120 0180SE 0240SE 0390HE 0515HE 60 Pressure Drop (kPa) 0210SE 15 0195HE 0285SE 10 0260HE 0300HE 0320SE 0360SE 0350HE 0400SE 0435SE 0455HE 10 15 Flow Rate (l/s) FAN SPEED INHIBIT FLOW SWITCH PWM 2nd…
-
Operating Limitations - SE Models
YLAA SE Liquid Outlet Temperature (Water) Liquid Outlet Temperature (Glycol) Chilled Liquid Outlet Temperature Range Liquid Evaporator Flow Rate Evaporator Pressure Drop Maximum Water Side Pressure Air Temperature - Standard Unit Ambient Air Air Temperature - Unit with Low Ambient Kit Maximum…
-
Condenser Coil Entering Air Temperature (ºC)
kWo kWci kWo kWci kWo kWci kWo kWci kWo kWci EER EER EER EER 188 46 3.65 179 52 3.16 169 57 2.71 157 63 2.30 145 70 0180 207 61 3.13 196 68 2.70 185 75 2.31 172 83 1.95 157 91 0210 228 60 3.43 217 66 2.99 205 73 2.57 191 81 2.18 176 89 0240 291 77 3.49 277 85 3.03 261 94 2.60 242 103 2.20 170 75…
-
Condenser Coil Entering Air Temperature (ºC)
kWo kWci kWo kWci kWo kWci kWo kWci kWo kWci EER EER EER EER 205 48 3.90 195 53 3.38 184 59 2.90 172 65 2.47 158 71 0180 225 63 3.31 214 69 2.87 202 77 2.46 187 85 2.09 123 55 0210 249 61 3.67 237 67 3.19 224 75 2.75 209 82 2.34 193 91 0240 317 79 3.69 301 87 3.20 284 96 2.76 263 106 2.34 187 76…
-
0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 YLAA-HE kWo kWci EER 3.96 3.88 3.95 3.94 3.88 3.88 3.89 3.91 4.05 3.96 4.04 4.02 3.96 3.96 3.98 3.99 4.13 4.04 4.12 4.11 4.04 4.04 4.06 4.07 kWo kWci EER 3.43 3.37 3.44 3.43 3.37…
-
0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 YLAA-HE kWo kWci EER 4.21 4.13 4.20 4.19 4.12 4.12 4.15 4.15 4.37 4.29 4.37 4.36 4.28 4.28 4.32 4.31 4.60 4.52 4.61 4.61 4.51 4.52 4.57 4.54 kWo kWci EER 3.65 3.59 3.67 3.66 3.59 3.60 3.63…
-
0180 0210 0240 0285 0320 0360 0400 0435 0485 0180 0210 0240 0285 0320 0360 0400 0435 0485 0180 0210 0240 0285 0320 0360 0400 0435 0485 YLAA-SE LS kWo kWci EER 3.55 3.00 3.39 3.37 3.17 3.31 3.16 3.35 3.19 3.63 3.06 3.46 3.43 3.22 3.38 3.22 3.41 3.24 3.70 3.12 3.53 3.49 3.28 3.43 3.27 3.47 3.29 kWo…
-
0210 0240 0285 0320 0360 0400 0435 0485 0180 0210 0240 0285 0320 0360 0400 0435 0485 0180 0210 0240 0285 0320 0360 0400 0435 0485 YLAA-SE LS kWo kWci EER 3.78 3.17 3.60 3.55 3.33 3.49 3.32 3.53 3.34 3.93 3.28 3.75 3.67 3.43 3.61 3.42 3.65 3.44 4.15 3.44 3.95 3.83 3.56 3.77 3.55 3.81 3.57 kWo kWci…
-
0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 YLAA-HE LS kWo kWci EER 3.85 3.80 3.89 3.89 3.79 3.81 3.86 3.83 3.92 3.88 3.96 3.97 3.87 3.89 3.94 3.90 4.00 3.96 4.04 4.05 3.94 3.97 4.02 3.97 kWo kWci EER 3.32 3.29 3.37 3.38…
-
0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 0195 0260 0300 0350 0390 0440 0455 0515 YLAA-HE LS kWo kWci EER 4.08 4.03 4.12 4.13 4.02 4.04 4.10 4.05 4.23 4.18 4.27 4.29 4.16 4.19 4.25 4.19 4.44 4.39 4.48 4.51 4.37 4.40 4.48 4.39 kWo kWci EER 3.53 3.49 3.57 3.59 3.48 3.51…
-
Fan Power Data
Values for fans used on system 2 on YLAA0180SE, YLAA0210SE and YLAA0195HE Two Speed High Head Slow Fast kW FLA LRA FLA LRA kW FLA LRA @400V @400V kW @400V @400V @400V @400V 0.9 2.8 9.6 0.6 1.3 4.6 0.6 1.3 4.6 0.9 2.8 9.6 1.9 3.4 11.9 Values are for each fan. (FLA: Full Load Amps; LRA: Lock Rotor…
-
Physical Data - SE Models
YLAA - SE Number of refrigerant circuits Refrigerant Charge (1) Circuit 1 / Circuit 2 Oil Charge Circuit 1 / Circuit 2 Number of compressors Compressor Type Number Type Evaporator Water Volume Water Connections Air Cooled Condenser Total Coil Face Area Number of Fans (circuit 1 / circuit 2) Total…
-
Physical Data - HE Models
YLAA - HE Number of refrigerant circuits Refrigerant Charge (1) Circuit 1 / Circuit 2 Oil Charge Circuit 1 / Circuit 2 Number of compressors Compressor Type Number Type Evaporator Water Volume Water Connections Air Cooled Condenser Total Coil Face Area Number of Fans (circuit 1 / circuit 2) Total…
-
Electrical Data SE Models
Nominal Running Conditions (1) YLAA 0180SE 0210SE 0240SE 0285SE 0320SE 0360SE 0400SE 0435SE 0485SE kW Amps @ 400 V Maximum Running Conditions (2) Start up Amps (2) Direct on Line Optional Soft Amps Amps (3) Start (3&4) @360V @ 400V without Power Factor Correction with Optional Power Factor…
-
NB1 Hot water outlet connection to optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2…
-
connection to
optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2 Distance between anti vibration…
-
NB1 Hot water outlet connection to optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2…
-
NB1NB1
HotHot water water outlet outlet connection connection to to optional optional heatheat recovery recovery exchanger exchanger NB7NB7 HotHot water water inletinlet connection connection to to optional optional heatheat recovery recovery exchanger exchanger NB6NB6 Chilled Chilled water water outlet…
-
NB1 Hot water outlet connection to optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2…
-
connection to
optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2 Distance between anti vibration…
-
NB1 Hot water outlet connection to optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2…
-
connection to
optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2 Distance between anti vibration…
-
NB1 Hot water outlet connection to optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2…
-
connection to
optional heat recovery exchanger NB7 Hot water inlet connection to optional heat recovery exchanger NB6 Chilled water outlet connection to evaporator NB5 Chilled water inlet connection to evaporator NB4 Control cable entry NB3 Power cable entry via gland plate NB2 Distance between anti vibration…
-
www.johnsoncontrols.com