Инструкция на Тепловые насосы воздух-вода Unical серии HP OWER 500 RK - 700 RK - 500 RK A400 - 700 RK A 400. Руководство пользователя.
Смотрите также: Руководство по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
ENGLISH
-
22.14 UTILITIES BLOCK ALARM TABLE 29 23.MODBUS VARIABLES 30 5
-
1. PURPOSE AND CONTENT OF THE MANUAL
The purpose of the control manual for HP_OWER RK units is to provide the essential information necessary for the correct use of all the functions of the machine, in particular, it provides the essential information for the setup of unit control. The informations contained in this manual are written…
-
IS PROHIBITED
To remove and/or to manipulating any safety device. Unauthorised access to the electrical panel. To touch the systems if not autorised to do so. To performe any cleaning operation when the master switch in ‘ON’. To pull, detach or twist the appliance’s electric cable. To step on, sit down on and/or…
-
DISPLAY 4.1.1 KEYS Select the operating mode and manually reset any alarms. Each time you press the key you have the following sequence: OFF -> COOL -> COOL+SAN* -> HEAT -> HEAT+SAN* -> OFF During parameter settig has the function of the back key. (*= if sanitary is enabled) Allows to enter the…
-
MENU The items controlled by the main menu are listed below. Some of this are only visible to the installer, who must access to the PSS menu to enter the password and enable higher privilege access. MENU Setpoint Password Alarms Probes Digital inputs Parameters Hours of operation Alarm log Firmware…
-
DIGITAL INPUTS MENU [Id] Entering with the installer password, the status of the digital inputs can be view in this menu: 0 = input disabled 1 = input enabled = input not configured It is strictly PROHIBITED to disable the digital input ID1, corresponding to the flow switch. 4.8 PARAMETERS MENU…
-
5. Power up the unit, setting the main switch to the ON position; Access the firmware update menu and start the procedure through the following sequence: PRG -> PSS -> PRG -> (enter installer password) -> PRG -> USB -> UPPA -> PRG; 6. A countdown advances on the display, at the end of the procedure…
-
• set-point of 7°C with external temperature of 35°C Set Coo = 12 e b08 = 1, while the other parameters will be calculated as follows: • b09 = 7 – 12 = -5 • b11 = 25 • b13 = 35 – 25 = 10 7. SET-POINT MODIFICATION FROM ANALOGUE INPUT Another type of regulation allows the set-point to be modified by…
-
OPERATION ON CALL BY TEMPERATURE CONTROLLER Subsequently, the compressor is also switched on, after a delay time of P01 seconds (default P01 = 30) since the pump was switched on. In the switch-off phase, the pump is switched off with a delay time of P02 minutes (default P02 = 2) from the switch-off…
-
In practice, in cooling mode, if the temperature difference between the inlet and outlet is greater than P09 + P10, the circulator runs at maximum speed, but if the difference is less than P09 - 0.2°C, it runs at minimum speed; in the remaining cases, the pump modulates the speed proportionally. In…
-
RPM
Tw,out,set HzMaxReg HzMin OFF ∆T,set + 2°C b05 Tw,out (outlet water temp.) • The compressor shutdown is regulated by parameter b05: the compressor shutdown when Tw,out > Tw,out,set + b05. • The compressor restart when Tw,out < (Tw,out,set - ∆Tset – b25) EXCEPTION: if ∆T,set > 8°C, the compressors…
-
NOTE: defrosting during winter operation is always performed on the user side, never on the domestic hot water tank. 12.2.1 MEMORISING THE PROBE IN HEATING MODE When switching from the system to DHW, the reference probe changes from "water outlet probe" to "DHW probe". The display on the machine…
-
SYSTEM WATER REMOTE PROBE As an alternative to the HOT SANITARY WATER PRODUCTION function, it is possible to enable a temperature probe of the system, so that the on-board control can process the management correctly. The system remote probe is activated by setting parameter H19 = 41. The system…
-
17. LOGICS THAT CAN BE ACTIVATED WITH GI MODULE - SYSTEM MANAGEMENT (ACCESSORY)
If the System Management kit (optional) is present, a second control is located inside the electrical panel that acts as an I/O resource expansion module. With this second control it is possible to increase the number of logics that can be managed by the main control; in particular, these logics are…
-
VALUE
H129 19.1 Function Function disabled Function configured but not active Enabled only in cooling mode Enabled only in heating mode Enabled in cooling and heating mode SILENCED VENTILATION Configuring a digital input DI9E with parameter H63=25 it is possible to manage the function of silent…
-
have a single integration resistance for the system, DHW and defrosting
20.4 INTEGRATION RESISTANCE SELECTION MODE The resistors can be activated simultaneously if r14 = 0 (default), otherwise the priority of the order of activation of the system-side and DHWside integration resistors can be set, in particular the configurations are: • r14 = 1 for resistance activation…
-
LOGIC OF INTEGRATION
Outside temp. Heat pump STANDARD WORKING r22 Heat pump + Boiler/Heater JOINT OPERATION I ZONE r28 Boiler + Heat pump/Heater JOINT OPERATION II ZONE r08 Boiler/Heater OPERATION IN SUBSTITUTION If it is necessary to change the values of the parameters, the formula r22 ≥ r28 ≥ r08 must be followed.…
-
NOTE: In the event of water-side frost protection, the circulator is still activated (or kept active). 20.9 OPERATING BRACKETS The possible configurations of the integration parameters are listed in tables 1,2,3 and 4 shown below, divided by operating brackets (The boxes for the rXX parameters…
-
TABLE 2. JOINT OPERATION, BRACKET1
INTERVENTION ORDER STATUS OPERATION r10 r15 r12 r16 r23 r24 SANITARY 0/1 1 / Set the minutes 5/6 2/3 HEAT / SANITARY 1 1 Set the minutes Set the minutes 0 3 HEAT / HEAT+SAN HEAT / SANITARY 0/1 0/1/2 Set the minutes Set the minutes 3/6 0 1) Heat pump 2) After r12 minutes, plant/DHW inteHEAT / gration…
-
TABLE 4. OPERATION IN SUBSTITUTION
STATUS OPERATION r10 r15 r12 r16 r23 r24 1) Boiler 2) After r12 minutes, DHW integration HEAT+SAN heater INTERVENTION ORDER SANITARY 0/1 0/1/2 / Set the minutes 5/6 2/3 1) DHW integration heater 2) After r12 minutes, boiler SANITARY 0/1 0/1/2 / Set the minutes 2/3 2/3 1) Boiler HEAT / 2) After r12…
-
• r31 = temperature offset for boiler and domestic hot water heaters (San)
In this way the heat pump will stop at the set point and the thermal jump, according to the set offset, will be borne by the boiler and/or the integration resistors. 22. PERMITTED CONFIGURATION TABLES Below is a table of user and installer parameters including all the permitted configurations. Not…
-
Description
Unit Default Range Visibility Allowed configurations: Description Coo Hea First cooling setpoint First heating setpoint °C °C 7.0 45.0 25÷Coo2 Hea2÷H01 U U San Sanitary setpoint °C 48.0 25÷H01 U Coo2 Hea2 San2 18.0 35.0 48.0 Coo÷25 25÷Hea 25÷H01 U U U 60.0 -50÷80 I 5.0 -50÷80 I 0 0÷6 I 0 0÷49 I See…
-
Description
Unit Default Range Visibility Allowed configurations: Description 25 -127÷127 I See par. 9 15 -127÷127 I See par. 9 -10.0 10.0 -50.0÷80.0 -50.0÷80.0 I I See par. 9 See par. 9 b15 Cooling outdoor tempera- °C ture setting Heating outdoor tempera- °C ture setting Cooling temperature delta °C Heating…
-
*r23
Description Unit *r24 Type of boiler use / Type of use integration re- / sistors *r28 Upper limit for joint opera- °C tion 2nd band L02 Temperature offset for boiler and system resistors first °C set point (HEA) Temperature offset for boiler and system resistors sec- °C ond set point (HEA2)…
-
[E851 ÷E971] INVERTER ALARMS These alarms are related to the compressor driver, each model has its own list of alarms. 23.8 [E00] REMOTE ON/OFF SIGNALLING This message appears on the display when the remote on/off contact is open. 23.9 [E001] HIGH PRESSURE The alarm is activated when the pressure…
-
Alarm code
E891 E901 E911 E921 E931 E941 E951 E961 E971 24. DESCRIPTION Compressor not connected Wrong compressor model Overload protection PFC/POE overcurrent Internal commhunication error PFC fault Heatsink and/or ambient temperature sensor fault Abnormal condition Errore EEPROM Block Compressor Compressor…
-
2 Format INT INT BYTE (H) BYTE (L) BYTE (H) BYTE (L) Bit - R/W R R R R R R Range - 80 ÷ 97 ASCII - R - Serial number 444 INT - R 0 ÷ 800 Water flow rate 1089 INT - R/W 1 ÷ 200 Serial address 200 INT - R R R R R R - 7201 BIT MASK 0 R/W - 7200 INT - W W W W W W 7201 BIT MASK 1 7203 7204 7205 7206 7207…
-
Bit
R/W Range 7202 BIT MASK 7 R/W - 7214 BIT MASK 20422 20433 20434 20435 406 414 20406 20414 7000 7001 628 ora ora ora ora ora ora °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 °C/10 bar/100 bar/100 bar/100 bar/100 %/10 %/10 %/10…
-
BIT MASK Bit R/W Range Name R - Alarms ⁴ ⁵ BIT MASK 953 BIT MASK Description High temperature High discharge temperature of Cp2 Inverted pressure transducers Compressor 3 thermal protection Fan 3 thermal protection Pump 2 thermal protection Incongruent temperatures Poor heat exchange DHW DHW…
-
BIT MASK 955 BIT MASK 956 BIT MASK Bit R/W Range Name R - Alarms ⁴ ⁵ R - Alarms ⁴ ⁵ R - Alarms ⁴ ⁵ Description Module 2 probe 11 error Link inverter 1 Link inverter 2 Link inverter 3 Hardware fault inverter 1 Hardware fault inverter 2 Hardware fault inverter 3 Overcurrent inverter 1 Overcurrent…
-
www.unical.eu AG S.p.A. 46033 casteldario - mantova - italia - tel. +39 0376 57001 - fax +39 0376 660556 info@unical-ag.com - export@unical-ag.com - www.unical.eu Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.