Инструкции на Тепловые насосы воздух-вода Unical серии HP OWER 500-700RK
Тепловые насосы воздух-вода Unical серии HP OWER 500 RK - 700 RK - 500 RK A400 - 700 RK A 400. Руководство по монтажу и эксплуатации.
Смотрите также: Руководство пользователя → Коды ошибок: 30 кодов →
Загружаем документ…
Текст инструкции
-
ENGLISH
-
The manual of the units contains all the indications for the optimal use of the machine under safe conditions for the operator. 1. PURPOSE AND CONTENTS OF THE MANUAL This manual provides basic information as to the selection, installation, operation and maintenance of the unit. It is intended for…
-
3. PERMITTED USE
• The company excludes any contractual and extra contractual liability for damage caused to persons, animals or objects, by incorrect installation, setting and maintenance, improper use of the equipment, and the partial or superficial reading of the information contained in this manual. • These…
-
WORKERS' HEALTH AND SAFETY The European Union has issued some directives regarding the safety and health of workers, including: 89/391/CEE, 89/686/CEE, 2009/104/CE, 86/188/CEE and 77/576/CEE, and subsequent amendments which every employer is obliged to follow and have followed. We observe therefore…
-
Gloves: During maintenance or cleaning operations, appropriate protective gloves must be used
Mask and goggles: Respiratory protection (mask) and eye protection (goggles) should be used during cleaning operations. 4.3 SAFETY SIGNS The unit features the following safety signs, wich must be complied with: Generic hazard. Dangerous electric voltage. Moving parts. Surfaces wich can cause…
-
REFRIGERANT SAFETY DATA SHEET
Dénomination: R32 INDICATION DES DANGERS Dangers principaux: Dangers spécifiques: Informations générales: Inhalation: Contact avec les yeux: Contact avec la peau: Moyens d’extinction: Dangers spécifiques: Méthodes spécifiques: Précautions individuelles: Précautions environnementales: Méthodes de…
-
SPECIFIC R32 GAS WARNINGS The R32 refrigerant gas: • is odourless; • is flammable, but only if there are naked flame; • it may cause an explosion, but only if a given concentration in air is reached. It is a good practice to follow these guidelines: • do not smoke near the unit; • affix a no smoking…
-
CAUTION: The unit must be installed so as to allow free movement for repair and maintenance operations. The warranty does not cover costs for platforms or other lifting equipment needed for any interventions. CAUTION: The unit must be installed so as to allow free movement for repair and maintenance…
-
• forklift truck;
• thick lifting tubes according to EN 355 and EN 10297-1, thick lifting tubes according + ropes/chains; • lifting slings (available as an accessory) + ropes/chains + sling bar. Ensure that the lifting ropes are tensioned gradually and check that they are correctly positioned. Lifting through…
-
C
Model HP_OWER 500RK - 700RK mm A1 A2 B1 B2 1200 1000 1500 1500 A2 B1 A B B2 A1 For strong wind installation place refer to the classification of the area according to the Beaufort table. If the value is > 7 (strong wind, average wind speed = 13,9-17,1 m/s) it is strictly necessary to keep the fan…
-
5.5 DIMENSIONS
5.5.1 Standard version Dimensions A - Lenght mm 1850 B - Depht mm 1110 C - Height mm 1920 IN / OUT inch 1" 1/2 Grooved E - Power supply input 5.5 DIMENSIONS 5.5.2 Version A400 with tank kit Dimensions A - Lenght mm 2460 B - Depht mm 1110 C - Height mm 1920 IN / OUT inch 1" 1/2 Grooved E - Power…
-
IDRONIC KIT
Hydronic kit features 5.6 Tank volume l. 400 Expansion vessel volume l. 24 CENTRE OF GRAVITY AND DAMPERS LOCATION In the following tables, we report the position of the barycentre of each machine, with reference to the dimensions shown in the image. A distinction is made between standard machine…
-
A
C P2 5 Ø 8, D 90 D P1 74 B 5.7 5.7.1 P3 P4 90 Models Version A [mm] B [mm] C [mm] D [mm] HP_OWER 500 RK 700 RK Standard 1410 Hydronic kit with tank A 400 2180 ACCESSING THE INNER PARTS Access to the inside of the unit on the electrical panel side In case of maintenance and/or inspection of the…
-
Access to the inside of the unit on the hydronic kit side In the event of maintenance and/or inspection of the hydronic part and part of the refrigeration circuit, it is necessary to access the inside of the unit from the rear side, near the hydraulic connections. Unscrew the rear panel fixing…
-
The heating system and the safety valves must comply with the requirements of standard EN 12828
The unit is pre-tensioned on the side cover plate in order to provide a suitable passage for the discharge of the safety valve (the installation of which is the responsibility of the user). A 5.8.1 Features of the circuit water To guarantee correct operation of the unit, the water must be…
-
STANDARD HYDRONIC CIRCUIT
-
ATTENTION: It is recommended to connect the safety valve vent in an appropriate conveyor / discharge. Otherwise the discharged water could stagnate around the unit and become a source of danger due to slipping / falling. 5.8.2 Drainage system The units all of them adopt drainage holes on the…
-
It is advisable to use an external tap to fill the system, which is the responsibility
of the installer. There is always a service tap in the unit to be used if it is necessary to top up/ discharge the amount of water in the system or adjust the percentage of glycol. A If the unit must be completely drained,first close the manual inlet and outlet shutters (not supplied) and then…
-
CAUTION: Any devices placed nearby can cause / suffer electromagnetic disturbances to / from the unit. Be aware of this risk at the installation site. It is recommended to electrically power the unit with an adequate line and protections and use an independent cable duct. CAUTION: The remote control…
-
User terminal block The connection terminal block is located under the machine cover. For access, see the instructions. The terminal block must be connected respecting the notes below. The connections shown below are standard. Other connections are given in the MCO manual of the on-machine control…
-
5.9.3 Control logics
-
5.10 FUNCTIONAL DIAGRAMS
LEGEND INVC 1/2 VARIABLE SPEED COMPRESSOR YVOL 1 OIL LINE EQUALIZATION SOLENOID CO / EV EV/CO 1/2 FINNED BATTERY YISV 1 VALVE REVERSE CYCLE 1 PLATE EXCHANGER LR 1 LIQUID RECEIVER SBSV 1 BYPASS LINE SOLENOID VALVE SL 1 LIQUID SEPARATOR SG EVV 1 ELECTRONIC EXPANSION VALVE PEH TC 1 HIGH PRESSURE…
-
6. START UP
Before start-up: 1. Check that the diagrams and manuals of the installed machine are available. 2. Check that the wiring and plumbing diagrams of the plant the machine is connected to are available. 3. Check that the shut-off valves of the water circuits are open. 4. Check that the water circuit was…
-
• Close the water valves
• Set the general residual current device at "OFF" (if installed upstream of the system). Se la temperatura scende sotto lo zero c’è serio pericolo di gelo: prevedere una miscela di acqua e glicole nell’impianto, diversamente svuotare l’impianto idraulico ed i circuiti idraulici della pompa di…
-
warranty and could considerably shorten the service life of your product
OPERATION Filling the water circuit. M/R R Presence of bubbles in the water circuit. R Check the proper working of the safety and control devices. M Check that there are no oil leaks from the compressor. R Check if there is a possible water leakage from the water circuit. R Check that the flow…
-
CAUTION: Do not clean the coil using high-pressure cleaners so as not to apply excessive pressure which could cause irreparable damage. Damage caused by cleaning with unsuitable chemical substances or excessively high water pressure will not be recognised under warranty. CAUTION: The aluminium fins…
-
An incorrect decommissioning of the appliance may create serious environmental damage and endanger people’s safety. Therefore, it is recommended that the unit be disposed only by authorised persons with technical training who have attended training courses acknowledged by the competent authorities.…
-
The correct maintenance
Mechanical: cut / abrasion procedures are indicated in the Failure to comply with the procecaused by the presence of edges user-installer manual under chap- dures and / or failure to use PPE on the external casing of the ma- ter 9. Paragraph 4.2 recommends by the maintenance technician chine and /…
-
No one The use of personal protective equipment is recommended in Generated by materials / subthe user-installer manual under stances: infections caused by paragraph 4.2. The safety data bacteria potentially present in the sheet for the refrigerant (paracarrier fluid (technical water) graph 4.4) and…
-
Failure to comply with the instructions given in the manual. X X Failure to comply with the recommendations regarding the electrical system. Normal unit operation Unit interaction In the user-installer manual under chapter 9 it is recommended to carry out maintenance only in weather conditions…
-
TECHNICAL DATA 12.1 TECHNICAL SHEET HEAT PUMP Performance referring to the following conditions,according to standard 14511:2018: (1) Cooling: outdoor air temperature 35°C; in/out water temperature 12/7°C. (2) Cooling: outdoor air temperature 35°C; in/out water temperature. 23/18°C. (3) Heating…
-
TECHNICAL CHARACTERISTICS
Cooling Heating Compressor Refrigerant External zone fans Internal heat exchanger Hydronic circuit Noise Electrical data 34 Cooling capacity (1) min/nom/max Power input (1) E.E.R. (1) Cooling capacity (2) min/nom/max Power input (2) E.E.R. (2) SEER (5) Water flow (1) Heating capacity (3) min/nom/max…
-
UNIT AND AUXILIARY ELECTRICAL DATA Unit power supply On board controller circuit Remote controller circuit Fan power supply V/~/Hz V/~/Hz V/~/Hz V/~/Hz 400/3PH+PE/50 12/1/50 12/1/50 400/3PH+PE/50 NOTE: The electrical data are subject to change due to updates. It is therefore always necessary to…
-
12.3 OPERATING LIMITS
12.4 EVAPORATOR WATER FLOW RATE The nominal water flow rate refers to a 5°C temperature difference between the evaporator inlet and outlet. The maximum permitted flow rate features a 3°C temperature difference while the minimum one has an 8°C temperature difference at the nominal conditions as shown…
-
HP_OWER 700 RK
200 0,8 197 1,1 193 1,3 188 1,6 181 1,9 173 2,2 164 2,5 154 2,8 143 3,0 130 3,3 116 3,6 101 3,9 85 4,2 67 4,4 48 4,7 Prevalenza utile [kPa] Avaible head unit [kPa] 0,5 Avaible Head [kPa] Flow rate [l/s] 130 Pressure drop Prevalenza utile HP_OWER HP_OWER 700RK 700RK Nominal point HP_OWER 700RKA35W7…
-
OPERATING LIMITS 13.1 EVAPORATOR WATER FLOW RATE The nominal water flow rate refers to a 5°C temperature difference between the evaporator inlet and outlet. The maximum permitted flow rate features a 3°C temperature difference while the minimum one has an 8°C temperature difference at the nominal…
-
Heat pump mode for domestic hot water 700 RK
Room temperature with water at maximum +58 °C Minimum -8 °C Maximum +24 °C Room temperature with water at maximum +50 °C Minimum -12 °C Maximum +39 °C Outlet water temperature Minimum +25 °C Maximum +58 °C Heat pump mode for domestic hot water 500 RK Room temperature with water at maximum +58 °C…
-
CHILLER MODE
DOMESTIC HOT WATER MODE HP_OWER 700RK - 700RK A 400 Pun� estremi envelope UNITÀ - ACS Twater [°C] -20 -15 -10 -5 Tair [°C] DOMESTIC HOT WATER MODE HP_OWER 500RK - 500RK A Twater [°C] -20 -15 -10 -5 0 5 Tair [°C] 40
-
14 USER INTERFACE - CONTROLLER
The unit includes a display placed underneath a hinged polycarbonate transparent door with a protection rating of IP67. The interface has a part with variable text and a series of icons identifying operation of the unit as shown in the table below. Cooling mode led: led ON if unit is in COOL or…
-
several alarms are triggered, the first one is displayed while the second one will be displayed as soon as the first one is reset. In menu mode, the display depends on the current position.attivo. 13.5 MENU The following are the main features for navigating the menus, especially describing functions…
-
PROBLEM
High exhaust pressure CAUSE High outside air temperature High water return temperature Air in the hydraulic circuit Refrigerant gas charge too high SOLUTION Poor air flow Poor water flow rate Check the fan and pump operation High outdoor air temperature Low plant return water temperature Low exhaust…
-
www.unical.eu AG S.p.A. 46033 casteldario - mantova - italia - tel. +39 0376 57001 - fax +39 0376 660556 info@unical-ag.com - export@unical-ag.com - www.unical.eu Unical declines every responsibility for the possible inaccuracies if owed to errors of transcript or press. Also reserves the right to…