Инструкция на Тепловые насосы воздух-вода Unical серии HP OWER ONE R: 70R – 90R – 120R - 120RT – 140R – 160RT – 180R - 70RK – 90RK – 120RK – 140RK – 160RTK – 180RK. Руководство пользователя.
Смотрите также: Руководство по монтажу и эксплуатации →
Загружаем документ…
Текст инструкции
-
ONE R
-
1 CONSERVATION OF THE MANUAL
The manual has to be always kept for future reference. It has to be stored in a safe place, away from dusts and moisture. It has to be also available and accessible to all users who shall consult it any time they are in doubt on how to operate the equipment. The company reserves the right to modify…
-
WORKERS’ HEALTH AND SAFETY The European Community has adopted a number of directives on workplace’s health and safety, which include 89/391/CEE, 89/686/CEE, 2009/104/CE, 86/188/CEE and 77/576/CEE directives. Every employer shall implement such provisions and ensure that their workers to respect…
-
electric heater)
• If not present in the network, we recommend the installation of a differential current device (RCD) that has a rated operating differential current that does not exceed 30mA • A good grounding is required; the manufacturer is not responsible for damage caused in case of lack of good grounding. •…
-
It is used to select the operating mode, and to initialize the manual resetting alarms. The operating mode changes as per the sequence below each time you press the Mode button: off cool heat off If the Domestic Hot Water (DHW) mode is enabled, the sequence is as follows: off cool cool+san…
-
Enter in the password’s menu and insert its “password code” in order to enable an access with a greater privilege. Note that, once you exit completely from the menus, the password permission will be lost and you should to re-enter it in order to get access again. 5.2.1 Setpoint’s menu [SEt] You can…
-
Configuration
Compressor Fan motor* Alarms Regulation Pump Electric heaters Defrosting Maximum Hz Electronic valve Offset *Only for some models GROUP’S IDENTIFICATION CODE CnF CP FAn ALL rE PUP Fro dFr LbH EEu oFF PARAMETER’S INDEX H01C01F01A01b01P01r01DO1L01U01o01- VISIBILITY INSTALLER INSTALLER INSTALLER…
-
5.2.10.2 PARAMETERS UPGRADE [UPPA]
You can update the parameters in case of new ones, using the USB pen-dive via its port on the controller. For the updating: 1. Copy the update files in the main directory of a USB pen-drive; 2. Place the unit in standby mode and turn it off, placing the main switch in OFF position; 3. Introduce the…
-
INPUT/OUTPUT (I/O) PORTS The I/O (inputs and outputs) that can be set to enable the control functions are listed below. In order to set the I/O please enter with service password to the parameters PRGPSSPRG (insert the service password) PRG Par PRG CnF. Ports Parameter Terminals ST6 H17…
-
6 DYNAMIC SET-POINT ADJUSTMENT
The controller allows you to change the set-point by adding a value as a function of the outdoor air temperature sensor detection. In this case, you need to change the values of the parameters from b08 to b14 according to the indications below (the settings are the installer’s responsibility)…
-
7 SET-POINT ADJUSTMENT FROM 0-10V INPUT
Another type of setting that allows to change the set-point by adding (or subtracting) a value in function of the 0-10V analogue input (if enabled). To enable the function, you must use the following setting H22=40, and change the values of the parameter b15 (range 0-10), taking into account that if…
-
If you enable the operation of the unit from the remote "on-off" digital input (see Paragraph 11.5.1) the circulating pump will be activated immediately for a duration of 2 minutes regardless of the on-board controller thermoregulation of the unit (the activation of water recirculation in the plant…
-
In domestic hot water production mode, the pump will operate at the maximum speed
Note: If the parameter r33>0, then the circulator can start operations under call also for the activation of the plant resistance and/or sanitary mode operation, see paragraph 11.9. 8.6 PURGING THE SYSTEM This function allows purging the system using the circulator at the maximum speed. To enable…
-
Inverter compressor control in cooling mode 9.2 Heating function control 10 HEAT DISSIPATION FAN MOTOR CONTROL The control of the dissipation is a function of the condensing pressure in chiller mode and it is a function of the evaporation pressure in heat pump mode. The adjustment of the fan speed…
-
10.1 FAN SILENT MODE
10.2 FAN SPEED CONTROL IN COOLING MODE The fan speed control in cooling mode occurs depending on the diagram shown below, where: F08 = Pressure set to the minimum fan speed in cooling mode =-50.0÷80.0 Bar (based on the model) F09 = Fan proportional band in cooling mode =0.0÷25.5 Bar F10 = Delta…
-
11 CONTROL FUNCTIONS
The functions that can be activated by the on-board unit controller are listed below; note that, these functions are not all selectable at the same time. Other values different than the default can ensure the proper operation of the unit, in case of doubt about the value that to be set please…
-
If the DHW temperature is below than the set point value (fixed at 48°C by default and adjustable by entering the PRG->Set->SAN menu), the unit activates the sanitary valve and the compressor is set at the maximum frequency starting the modulation at one degree before the set value and it stops at…
-
11.3 HEATING MODE ON SANITARY ACCUMULATION
If H130=1, the appliance exploits the accumulation tank for sanitary hot water also for heating the plant side. In these conditions, the command relay of the sanitary valve will be also energized during heating operation and not only in sanitary mode. During defrost cycle and in cooling mode the…
-
11.5 REMOTE FUNCTIONS
The terminal block provides the digital inputs to control the unit via external consent. 11.5.1 ON/OFF The ON/OFF function is enabled by default via the digital input “ID3” (X15.1/X15.2 terminals). Remove the bridge of the terminal block then the unit will be placed in stand-by mode (in such status…
-
The plant circuit remote sensor adjusts the heat pump temperature only during the startup period of the compressor(s), the shutdown is managed by the outlet temperature sensor of the heat pump. For more explanation, herein below is reported an illustrating table concerning the operation process of…
-
Note: The DHW function should be active (see paragraph 11.2)
11.7.4 A single auxiliary electric heater for both plant system/dhw production By configuring the auxiliary electric heater for DHW production, you can use such declared electric heater, also as an auxiliary electric heater for the plant system by selecting the following setting r15=2 and r24=3.…
-
- Boiler
- Plant auxiliary electric heater - DHW (Sanitary) auxiliary electric heater Considering the heating and sanitary mode of operation, you have 4 types of operation: Tout.[°C] r22=7 0 r28=-7 r08=-20 Heat pump Heat pump + [Boiler and/or electricheater] IN JOINT OPERATION I Boiler + [Heat pump and/or…
-
The boiler will be enabled independently than thermoregulation of the heat pump
If the in substitution auxiliary system is a boiler without circulator (r32 = 0 or 2). The circulator of the heat pump will be active when the boiler is enabled. The compressor will be enabled again if the temperature increases above the value of r08+ r09 (°C) (by default r09=1,0°C) 11.12 OPERATION…
-
N°
N° ORDER OF INTERVENTION OF HEATING SYSTEMS (when the setpoint is not achieved) electric heater of plant 1) Heat pump 2) After r15 minutes, auxiliary electric heater of sanitary 1) Heat pump 2) After r15 minutes, boiler 1) Heat pump 2) After r15 minutes, auxiliary electric heater of sanitary 3)…
-
HEAT+SAN
SANITARY 11 1) Boiler 2) After r12 minutes, heat pump 3) After r12 minutes later, auxiliary electric heater of plant/sanitary HEAT / HEAT+SAN IN HEAT OR IN SANITARY 1 12 1) Auxiliary electric heater of plant/sanitary 2) After r12 minutes, heat pump HEAT / HEAT+SAN IN HEAT OR IN SANITARY 1 2) After…
-
The below Table (6) shows the behavior of the auxiliary electric heaters of both sanitary and plant in all cases where the unit is operating. N° MODE 1 HEAT+SAN TABLE 6. OPERATION OF AUXILIARY ELECTRIC HEATERS OPERATION AUXILIARY ELECTRIC HEATER OF PLANT AUXILIARY ELECTRIC HEATER OF SANITARY During…
-
11.13.3 Heat pump lockout
It is possible to configure a voltage output to signalize the presence of heat pump lockout alarm. In order to enable this function, you should enter into parameters PRGPSS(insert the maintainer password) PArCnF. I/O port- Parameter Value Function DO7 activable via H85 H85=47 Alarm signalization…
-
Setpoint
Setpoint (summer/winter) Summer Winter First setpoint (°C) Coo/Hea 7 (5÷18) 45 (35÷60) DIRECT ZONE Second setpoint (°C) Co2/He2 18 (7÷23) 35 (25÷45) MIXED ZONE To set the setpoints from the panel on the machine, use the SET key. The second setpoint is greater than the first setpoint in summer and…
-
11.18.1 Control settings
In order to enable such function, you should enter into the parameters as follow: press PRGPSSPRG (then insert the service password) PRG PAr PRG CnF: I/O Ports - Parameter H129 “ID9” digital input activable via H53 H76 “DO7” digital output activable via H85 Value H53=26 H76=1 H85=25…
-
In presence of a direct zone (Hea, Coo) and a mixed zone (He2 Co2), the consents of both thermal zones must be connected to the remote ON-OFF input (terminals X-15.1 and X-15.2) of the heat pump. The digital input must be enabled (terminals X-20.1 and X-20.2) to acquire direct zone consent as…
-
The allowed configurations are shown in the below table, note that, some multiple configurations cannot be selected simultaneously. All the operations that are described below must be carried out only by QUALIFIED PERSONNEL. Some of the listed parameters are visible and accessible only through the…
-
Unit
Default Range Visibility Coo HEA First setpoint in cooling mode First setpoint in heating mode °C °C 7.0 45.0 H03÷Co2 He2÷H01 U U SAn Domestic water temperature Setpoint °C 48.0 H02÷H01 U Coo2 HEA2 H01 H02 H03 H04 Second setpoint in cooling mode Second setpoint in heating mode Maximum setpoint in…
-
H53
H75 H76 H81 Description Configuration of the digital input “ID9” Digital inputs polarity Digital inputs polarity Configuration of DO3 under-voltage output Unit / / / / Default Range 0÷30 0÷255 0÷255 0÷47 Visibility I Allowed configuration Value I H82 Configuration of the under-voltage output “DO4” /…
-
Unit
Default Range Visibility H84 Configuration of the under-voltage output DO6 / 6 0÷47 I H85 Configuration of the under-voltage output “DO7” / 25 0÷47 I H126 Serial address / 1 1÷200 I H129 Second setpoint activation / 0 0÷3 I H130 Heating with sanitary accumulation / 0 0÷1 I H138 Second sanitary…
-
Unit
Default Range A27 Low pressure set in heating Bar Depending on the model 0.0÷25.5 b01 Cold band °C 1,0 0÷255 I b02 Hot band °C 1,0 0÷255 I b03 Sanitary Differential °C 3,0 0÷255 I sec 30 0÷600 °C 0.2 0.0÷25.5 sec sec / °C °C °C 3.0 -3.0 25 0÷255 0÷255 0÷1 -50.0÷80.0 -50.0÷80.0 -127÷127 I I I I I I…
-
P18
P19 r02 r03 r06 r08 r09 r10 r11 r12 Description Enabling of unique pump operation in network Unique pump operation in network in presence of offline machines Set point of anti-freeze heaters in heating Set point of anti-freeze heaters in cooling Anti-freeze electric heaters differential Upper limit…
-
Unit
Default Range Visibility r28 Upper limit for joint operation band II Temperature offset for boiler and heaters of the plant, first setpoint (HEA) Temperature offset for boiler and heaters of the plant second setpoint (HEA2) Temperature offset for boiler and sanitary circuit heaters (SAN) °C -7…
-
14 ALARMS
14.1 WATER FLOW SWITCH ALARM [E006] The water side flow switch is already installed inside the unit and DOES NOT HAVE to be tampered with or by-passed in any way. The flow switch is by-passed for 10 seconds after the unit’s start up. The alarm signal occurs after 5 seconds of the error appearance…
-
14.12 4-WAY VALVE [E041]
Manual re-arm alarm, identifies a malfunctioning of the 4‐way valve due to inversion. The alarm is not active for a bypass time of approximately 180 seconds from the compressor startup. • In heating or DHW mode, the alarm is active when the bypass time has expired with water supply temperature less…
-
Error code
E921 E931 E941 E951 E961 E971 Error description PFC-POE overcurrent protection Communication error with main controller PFC converter fault Heatsink and/or room temperature sensor error Abnormal condition EEPROM not initialize Lockout Compressor Compressor Compressor Compressor Compressor Compressor…
-
Format BIT MASK Bit INT Range R/W - Name Description R/W - (6) Heating + *Sanitary - Remote enabling of machine status writing R/W - W - - W - (1) Cooling W - (2) Heating W - (3) Sanitary W - (4) Cooling + *Sanitary (5) Heating + *Sanitary - W Note (5) Cooling + *Sanitary 0 7200 R/W (0) Stand by…
-
Format
Bit R/W Range 313 ora - R - compressor 1 circuit 2 315 ora - R - compressor 2 circuit 2 317 ora - R - compressor 3 circuit 2 253 °C/10 - R - Evaporation 254 °C/10 - R - 626 °C/10 - R - 627 °C/10 - R - Condensation circuit 2 400 °C/10 - R - Water inlet temp. 401 °C/10 - R - Water outlet temp. 405…
-
Format
Bit R/W Range BIT MASK BIT MASK BIT MASK Description ALARM – E014 Fan thermal 3 Note 9 ALARM – E026 * Thermal protection of pomp 2 11 ALARM – E041 Incongruous temperature 12 ALARM – E042 Poor heat exchange 13 ALARM – E050 Sanitary tank high temperature 14 ALARM - E101 GI 1 module is disconnected 15…
-
956 Format BIT MASK BIT MASK Bit Name Description 11 ALARM - E872 High temperature inverter 2 12 ALARM - E873 High temperature inverter 3 13 ALARM - E881 Bad voltage inverter 1 14 ALARM - E882 Bad voltage inverter 2 15 ALARM - E883 Bad voltage inverter 3 0 ALARM - E891 Phase sequence inverter 1 1…
-
00338956EN - ed. 4 - 05/2022
www.unical.eu AG S.p.A. 46033 casteldario - mantova - italia - tel. +39 0376 57001 - fax +39 0376 660556 info@unical-ag.com - export@unical-ag.com - www.unical.eu Unical will not be held responsible for possible inaccuracies if due to transcription or printing errors. It also reserves the right to…