ENGLISH
HP_QOR 70 - 90 - 120 - 140 140 T - 160 T INSTALLATION AND USER MANUAL
-
CONTENTS
1 SAFETY PRECAUTIONS 02 2 GENERAL INTRODUCTION 05 3 ACCESSORIES 06 3.1 Accessories supplied with the unit 3.2 Accessories avaliable from supplier BEFORE INSTALLATION 07 5 IMPORTANT INFORMATION FOR THE REFRIGERANT 07 6 INSTALLATION SITE 08 Selecting a location in cold climates Selecting a location in…
-
11 MENU STRUCTURE: OVERVIEW
11.1 Setting parameters FINAL CHECKS AND TEST RUN 52 12.1 Final checks 12.2 Test run operation(manually) MAINTENANCE AND SERVICE 53 14 TROUBLESHOOTING 54 14.1 General guidelines 14.2 General symptoms 14.3 Error codes TECHNICAL SPECIFICATIONS 59 15.1 General 15.2 Electrical specifications INFORMATION…
-
Please remove the hollow
plate after installation. NOTE Picture in this manual for reference only, please refer to the actual product. The backup heater can be customized outside the unit in accordance with demands,which contains 3kW(1-phase) , 4.5kW(1-phase), 4.5kW(3-phase), 6kW(3-phase) and 9kW(3-phase)(Please refer to…
-
1 SAFETY PRECAUTIONS
The precautions listed here are divided into the following types.They are quite important, so be sure to follow them carefully. Meanings of DANGER, WARNING, CAUTION and NOTE symbols. i INFORMATION Read these instructions carefully before installation. Keep this manual in a handy for future…
-
DANGER
Before touching electric terminal parts, turn off power switch. When service panels are removed, live parts can be easily touched by accident. Never leave the unit unattended during installation or servicing when the service panel is removed. Do not touch water pipes during and immediately after…
-
Do not install the unit in the following places
- Where there is mist of mineral oil, oil spray or vapors. Plastic parts may deteriorate, and cause them to come loose or water to leak. - Where corrosive gases (such as sulphurous acid gas) are produced. Where corrosion of copper pipes or soldered parts may cause refrigerant to leak. - Where there…
-
2 GENERAL INTRODUCTION
These units are used for both heating and cooling applications and domestic hot water tanks.They can be combined with fan coil units, floor heating applications, low temperature high efficiency radiators, domestic hot water tanks and solar kits, which are all field supplied. A wired controller is…
-
In cooling mode, the water flowing temperature
(TW_out) range in different outdoor temperature(T4) is listed below: 3 ACCESSORIES 3.1 Accessories supplied with the unit T4 Installation Fittings 43 Name Shape Quantity Installation and owner’s manual(this book) 1 Technical data manual 1 Y-shape filter 1 Wired controller 1 Thermistor(10m) for Tbt…
-
4 BEFORE INSTALLATION
Before installation Be sure to confirm the model name and the serial number of the unit. Transport Due to relatively large dimensions and heavy weight, the unit should only be hoised by lifting tools with slings, please refer to the following picture. CAUTION Foam To avoid injury, do not touch the…
-
Frequency of Refrigerant Leakage Checks
For unit that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent or more,but of less than 50 tonnes of CO2 equivalent,at least every 12 months, or where a leakage detection system is installed, at least every 24 months. For unit that contains fluorinated greenhouse…
-
In normal condition,refer to the figures below for installation of
the unit: A If you install the unit on a building frame, please install a waterproof tray (field supply) (about 100mm, on the underside of the unit) in order to avoid drain water dripping. (See the picture in the right). Unit A(mm) 5~16kW 6.1 Selecting a location in cold climates In case of strong…
-
7 INSTALLATION PRECAUTIONS
7.1 Dimensions I H J K E F G D C B M A L (unit:mm) Model A B C D E F G H I J K L M 5-16kW 1040 1068 450 7.2 Installation requirements Check the strength and level of the installation ground so that the unit may not cause any vibrations or noise during its operation. In accordance with the foundation…
-
7.3 Drain hole position
Drain hole This drain hole is covered by rubber plug. If the small drain hole can not meet the drainage requirements, the big drain hole can be used at the same time. NOTE It's necessary to install an electrical heating belt if water can't drain out in cold weather even the big drain hole has…
-
7.4.2 In case of multiple-row installation (for roof top use, etc.)
-
8 TYPICAL APPLICATIONS
The application examples given below are for illustration only. 8.1 Application 1 Indoor 6.2 6.1 Outdoor AHS FHL1 FHL2 FHLn 4.1 18 4.3 4.2 Modbus 14 11.2 15 12 1416 11.3 16 11.1 13 Assembly unit Code Assembly unit 1 Main unit 11 2 User interface 11.1 Domestic hot water tank (Field supply) TBH…
-
Space heating
The ON/OFF signal and operation mode and temperature setting are set on the user interface. P_o keeps running as long as the unit is ON for space heating, SV1 keeps OFF. Domestic water heating The ON/OFF signal and target tank water temperature (T5S) are set on the user interface. P_o stops running…
-
8.2 Application 2
ROOM THERMOSTAT control for space heating or cooling need to be set on the user interface. It can be set in three ways: MODE SET/ONE ZONE/DOUBLE ZONE. The unit can be connected to a low voltage room thermostat. 8.2.1 One zone control Outdoor 2 RT 10 4.1 Modbus 14 4.2 15 12 1416 FHL1 16 Assembly unit…
-
8.2.2 Mode set control
Outdoor FCU1 FCU2 FHL1 FHL2 19 FCUn M 22 RT 10 FHLn 4.1 Assembly unit Code 1 4.2 15 Main unit Code 15 Assembly unit Filling valve (Field supply) Drainage valve (Field supply) 2 User interface 16 4 Buffer tank (Field supply) 19 Collector/distributor 4.1 4.2 Automatic air purge valve Drainage valve 20…
-
8.2.3 Double zone control
2 Outdoor RAD.1 ZONE1 RAD.2 RT 10 RAD.n 1 4.1 Tw2 ZONE2 23.1 23.2 4 Modbus 14 4.2 15 12 1416 FHL1 16 Assembly unit Code Code FHL2 FHLn Assembly unit 16 19 Drainage valve (Field supply) Collector/distributor (Field supply) 23 23.1 Mixing station (Field supply) SV3: Mixing valve (Field supply)…
-
Drainage valve must be installed at the lowest position of the piping system
8.3 Cascade system : ( Buffer tank Automatic air purge valve Tbt: Buffer tank upper 18 )
-
r manometer
n r d e d The space only operates in heating mode Auxiliary heating source(Field supply) d n d The space operates in cooling or heating mode r d Automatic air purge valve All slave units can operate in space heating mode. The operation mode and setting temperature are set on the user interface. Due…
-
1. In cascade system, Tbt sensor must be connected to master unit and set Tbt vaild on user interface,otherwise all slave units will not work. 2. If outside circulation pump need to be connected in series in system when the head of internal water pump is not enough, outside circulation pump is…
-
9.2 Control board
9.2.1 Hydraulic module board CN5 CN28 CN8 CN6 CN24 CN23 12 CN13 CN37 CN15 CN29 27 CN42 26 CN22 CN4 S3 2 13 SW9 CN11 CN31 19 CN35 20 CN36 21 Port Code 1 CN21 POWER Port for power supply CN30 24 25 Order 18 CN33 S2 CN17 1 17 CN66 S1 28 CN64 CN27 CN25 CN19 CN32 29 CN38 CN18 CN21 Assembly unit Order…
-
9.2.2 Main control board
COMM H-SEN 7 22 POWER-I 23 S6 OUT1 CN45 16 PEQ Code Assembly unit Code 1 Power input port from Main control board (CN1) 15 Reserved(CN42) 2 Port for communication with Inverter module (CN43) 16 Reserved(CN41) 3 Port for high pressure switch (CN18) 17 OUT1 (CN40) 4 Port for low pressure switch (CN17)…
-
9.2.3 1-phase for 5-16kW units
1 1) 5/7/9kW, Inverter module 2 3 CN32 CN2 CN1 CN10 CN13 9 Code CN12 6 Assembly unit 5 Assembly unit Code 1 Compressor connection port U 6 2 Compressor connection port V 7 Port for power supply(CN13) 3 Compressor connection port W 8 Input port L for rectifier bridge(CN501) 4 Port for fan(CN32) 9…
-
9.2.4 3-phase for 12/14/16 kW units
1) Inverter module 9 CN1 CN16 CN12 13 CN3 12 8 CN5 7 CN22 6 CN7 11 5 CN15 4 CN39 3 CN17 2 CN18 1 CN19 CN10 10 Code Assembly unit Code 1 Compressor connection port W(CN19) 8 Power Input port L1(CN16) 2 Compressor connection port V(CN18) 9 Input port P_in for IPM module(CN1) 3 Compressor connection…
-
2) Filter board
CN204 CN205 CN206 9 5 CN30 CN214 PE1 10 CN202 CN203 CN200 CN201 PCB C 3-phase 12/14/16kW Code Assembly unit Code Assembly unit 1 Power supply L1(CN202) 6 3RZHU¿OWHULQJRXWSXW/¶ &1 2 Power supply L2(CN201) 7 3RZHU¿OWHULQJ/¶ &1 3 Power supply L3(CN200) 8 3RZHU¿OWHULQJ/¶ &1 4 Power supply N(CN203) 9…
-
9.3 Water piping
All piping lengths and distances have been taken into consideration. Requirements The maximum allowed thermistor cable length is 20m. This is the maximum allowable distance between the domestic hot water tank and the unit (only for installations with a domestic hot water tank).The thermistor cable…
-
Before continuing installation of the unit, check the following
7KHPD[LPXPZDWHUSUHVVXUHEDU 7KHPD[LPXPZDWHUWHPSHUDWXUH&DFFRUGLQJWRVDIHW\GHYLFHVHWWLQJ Always use materials that are compatible with the water used in the system and with the materials used in the unit. Ensure that components installed in the field piping can withstand the water pressure and…
-
9.3.3 Water circuit connection
Water connections must be made correctly in accordance with labels on the outdoor unit, with respect to the water inlet and water outlet. 9.3.4 Water circuit anti-freeze protection All internal hydronic parts are insulated to reduce heat loss. Insulation must also be added to the field piping. In…
-
When the unit is not running for a long time, make sure the unit is powered on all the time. If you want to cut off the power, the water in the system needs to be drained clean to avoid the unit and piping system be damaged by freezing. Also the power of the unit needs to be cut off after water in…
-
9.5 Water piping insulation
The complete water circuit including all piping, water piping must be insulated to prevent condensation during cooling operation and reduction of the heating and cooling capacity as well as prevention of freezing of the outside water piping during winter. The insulation material should at least of…
-
S1
-
Please use H07RN-F for the power wire, all the cable are connect to high voltage except for thermistor cable and cable for user interface. Equipment must be grounded. All high-voltage external load, if it is metal or a grounded port, must be grounded. All external load current is needed less than…
-
9.6.4 Safety device requirement
1. Select the wire diameters( minimum valve) individually for each unit based on the table 9-1 and table 9-2, where the rated current in table 9-1 means MCA in table 9-2. In case the MCA exceeds 63A, the wire diameters should be selected according to the national wiring regulation. 2. Maximum…
-
9.6.5 Remove the switch box cover
1-phase 5-16kW standard and 3-phase 12-16kW standard Unit Maximum overcurrent protector(MOP)(A) 2 Wiring size(mm ) 7kW 9kW 12kW 14kW 16kW 4.0 4.0 4.0 6.0 6.0 6.0 2.5 2.5 2.5 N FUSE L1 L2 L3 FUSE L 5kW LPS LPS 12kW 3-PH 14kW 3-PH 16kW 3-PH N L N L1 L2 L3 N UNIT POWER SUPPLY UNIT POWER SUPPLY 1-phase…
-
SW9
OFF Slave unit ON Master unit ;+$<+% Please use the shielded wire, and the shield layer must be grounded. LN LN Master unit On/Off switch LN H1 H2 Slave unit 1 H1 H2 Slave unit 2 Fuse Fuse Fuse Distribution box Distribution box Distribution box LN Fuse H1 H2 Slave unit x Only the last IDU requires…
-
When connecting to the power supply terminal, use the circular wiring terminal with the insulation casing (see Figure 9.1). Use power cord that conforms to the specifications and connect the power cord firmly. To prevent the cord from being pulled out by external force, make sure it is fixed…
-
9.6.6 Connection for other components
unit 5-16kW See 9.2.1for detailed port description. Port provide the control signal to the load.Two kind of control signal port: Type 1:Dry connector without voltage. Type 2:Port provide the signal with 220V voltage. If the current of load is <0.2A, load can connect to the port directly. If the…
-
Control signal port of hydraulic module: The CN11contains
terminals for 3-way valve, pump,booster heater , etc. The parts wiring is illustrated below: 2) For 3-way valve SV1 SV2 and SV3: 3 4 1ON 1OFF 17 C1 1) For additional heat source control(AHS): CN11 1 2 AHS1 AHS2 CN11 FUSE L Power supply A1 KM1 A2 SV1 N Additional heat source 5 6 2ON 2OFF 18 C1 CN11…
-
3) For outside pump
-
5) For tank booster heater(TBH):
-
CN8
CN5 CN28 CN23 CN13 CN38 CN18 CN21 CN27 CN33 CL COM HT CN31 S2 CN29 CN17 CN11 3 7 The wiring of the thermostat should correspond to the settings of the user interface. CN19 CN36 SW9 CN22 2 NOTE CN35 CN4 S3 CN42 13 C.4 when HT-COM and CL-COM are detected as 12VDC, both zone1 and zone2 turn on. CN64…
-
10) For smart grid
-
10.3 Failure diagnosis at first installation
10 START-UP AND CONFIGURATION If nothing is displayed on the user interface, it is necessary to check for any of the following abnormalities before diagnosing possible error codes. The unit should be configured by the installer to match the installation environment (outdoor climate, installed…
-
10.4.3.2 Wiring
CAUTION D1 D2 E X1/HB X2/HA Do not place the wired remote controller near the lamps, to avoid the remote signal of the controller to be disturbed. (refer to the right figure) L1 A B X/HA Y/HB E P Q E1 H1 H2 Hydraulic module H1 H2 10.4.2 Other Precautions Wired Controller 10.4.2.1. Installation…
-
Screw hole installed on the
three M4X20 Putty Putty Trap Trap Screw hole installed on 86 Electrician box, use two M4X25 Putty Trap Avoid the water enter into the wired remote controller, use trap and putty to seal the connectors of wires during wiring installation. 10.4.4 Front cover installation After adjusting the front…
-
11 MENU STRUCTURE : OVERVIEW
MENU OPERATION MODE PRESET TEMPERATURE DOMESTIC HOT WATER(DHW) OPERATION MODE HEAT COOL AUTO SCHEDULE OPTIONS CHILD LOCK SERVICE INFORMATION PRESET TEMPERATURE PRESET TEMP. WEATHER TEMP. SET ECO MODE OPERATION PARAMETER FOR SERVICEMAN WLAN SETTING SN VIEW DOMESTIC HOT WATER(DHW) DISINFECT FAST DHW…
-
FOR SERVICEMAN
1 DHW MODE SETTING 2 COOL MODE SETTING 3 HEAT MODE SETTING 4 AUTO MODE SETTING 5 TEMP. TYPE SETTING 6 ROOM THERMOSTAT 7 OTHER HEATING SOURECE 8 HOLIDAY AWAY SETTING 9 SERVICE CALL 10 RESTORE FACTORY SETTINGS 11TEST RUN 12 SPECIAL FUNCTION 13 AUTO RESTART 14 POWER INPUT LIMITATION 15 INPUT DEFINE 16…
-
11.1 Setting parameters
The parameters related to this chapter are shown in the table below. Order number Code State Default Unit 1.1 DHW MODE Enable or disable the DHW mode:0=NON,1=YES 1 / 1.2 DISINFECT Enable or disable the disinfect mode:0=NON,1=YES 1 / 1.3 DHW PRIORITY Enable or disable the DHW priority…
-
Code
State The maximum ambient operating temperature for heating Default Unit 25 °C -15 °C 3.3 T4HMAX 3.4 T4HMIN 3.5 dT1SH The temperature difference between T1 and T1S(the set water temperature) for starting the heat pump 5 °C 3.6 dTSH The temperature difference between actual room temperature Ta and…
-
Code
State Default Unit 7.14 GAS_COST Price of gas 0.85 €/m3 7.15 ELE_COST Price of electricity 0.20 €/kWh 7.16 MAX_SETHEATER Maximum setting temperature of additional heating source 80 °C 7.17 MIN_SETHEATER Minimum setting temperature of additional heating source 30 °C 7.18 MAX_SIGHEATER The voltage…
-
Code
State Default Unit 15.1 M1M2 Define the function of the M1M2 switch:0= REMOTE ON/OFF,1= TBH ON/OFF,2= AHS ON/OFF 0 / 15.2 SMART GRID Enable or disable the SMART GRID:0=NON,1=YES 0 / 15.3 T1T2 Control options of Port T1T2:0=NON,1=RT/Ta_PCB 0 / 15.4 Tbt Enable or disable the Tbt:0=NON,1=YES 0 / 15.5…
-
12 FINAL CHECKS AND TEST RUN
11 TEST RUN 3/3 TBH OFF The installer is obliged to verify correct operation of unit after installation. 12.1 Final checks ON/OFF Before switching on the unit, read following recommendations: When the installation and parameter setting are completed, cover all the sheet metal of the unit well. Press…
-
Ÿ
ź 11 TEST RUN Press to scroll the cursor to YES and press test run will turn off. TEST RUN IS ON. COOL MODE IS ON. LEAVING WATER TEMPERATURE IS 15°C. . The 11 TEST RUN(AIR PURGE) AIR PURGE PUMPI OUTPUT 70% AIR PURGE RUNNING TIME 20min CONFIRM ENTER During COOL MODE test running, the default target…
-
The following checks must be performed at least once a year by qualified person
Water pressure -Check the water pressure, if it is below 1 bar,fill water to the system. Water filter -Clean the water filter. Water pressure relief valve -Check for correct operation of the pressure relief valve by turning the black knob on the valve counter-clockwise: If you do not hear a clacking…
-
14.2 General symptoms
Symptom 1: The unit is turned on but the unit is not heating or cooling as expected CORRECTIVE ACTION POSSIBLE CAUSES The temperature setting is not correct. Check the parameters (T4HMAX, T4HMIN in heating mode; T4CMAX, T4CMIN in cooling mode; T4DHWMAX, T4DHWMIN in DHW mode). For the parameter…
-
Symptom 6: Space heating capacity shortage at low outdoor temperatures
POSSIBLE CAUSES CORRECTIVE ACTION Backup heater operation is not activated. Check if that the "OTHER HEATING SOURCE/ IBH FUNCTION" is enabled. Check whether or not the thermal protector of the backup heater has been activated. Check if booster heater is running, the backup heater and booster…
-
14.3 Error codes
A series of error codes and corresponding meaning can be found in the table below. Reset the unit by turning the unit ON or OFF. If Resetting the unit is invalid, contact your local dealer. UPPER UNIT ERROR DISPLAY No. CODE UPPER UNIT ERROR DISPLAY No. CODE MALFUNCTION OR PROTECTION 1 Water flow…
-
UPPER UNIT ERROR
DISPLAY No. CODE MALFUNCTION OR PROTECTION 33 High temperature protection of air side heat exchanger temperature(T3). 65 High temperature protection of inverter module 116 DC bus low voltage protection 134 Inverter or compressor protection 135 DC bus low voltage protection. 136 DC bus high voltage…
-
15 TECHNICAL SPECIFICATIONS
15.1 General Model 1-phase 1-phase 3-phase 5/7/9 kW 12/14/16 kW 12/14/16 kW Nominal capacity Refer to the Technical Data Dimensions HxWxD 865×1040×410mm 865×1040×410mm 865×1040×410mm Packing Dimensions HxWxD 970×1190×560mm 970×1190×560mm 970×1190×560mm Net weight 87kg 106kg 120kg Gross weight 103kg…
-
16 INFORMATION SERVICING
1) Checks to the area Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minmised. For repair to the refrigerating system, the following precautions shall be complied with prior to conducting work on the system. 2)…
-
10) Repairs to sealed components
a) During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak…
-
16) Charging procedures
In addition to conventional charging procedures, the following requirements shall be followed: Ensure that contamination of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to minimize the amount of refrigerant contained in them.…
-
Water outlet
F Water inlet Ŀ ŀ Ŀ ĺ Ĺ Ľ ĸ ļ ľ ķ Ļ Description Item Cooling Heating Description Item 1 Compressor 14 Plate heat exchanger 2 Discharge temperature sensor 15 Gas refrigerant temperature sensor 3 High pressure switch 16 Pressure sensor 4 4-way valve 17 Suction temperature sensor 5 Ambient temperature…
-
ANNEX B: To install the E-heating tape at the drainage outlet
(by client) Connect the heating tape wire at the drainage outlet to the wire joint XT3. To the heating tape of drainage outlet XT3 The picture is for reference only, please refer to the actual product. The power of the E-heating tape shall not exceed 40W/200mA, supply voltage 230VAC. 64
-
00339595EN -1 ed. 03/2022