FILE NO. SVM-13050-6
-
SAFETY CAUTION
Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them. Generic Denomination: Air Conditioner Definition of Qualified Installer or Qualified Service Person The air…
-
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to…
-
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original. Warning indication Description WARNING WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies…
-
Precaution for Safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. DANGER Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result.…
-
Electrical wiring work shall be conducted according to law and regulation in the community and
Installation manual. Failure to do so may result in electrocution or short circuit. To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric…
-
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then
apply a water-cut method, otherwise a leak or production of fire is caused at the users' side. Insulating measures No fire When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn. When repairing the refrigerating…
-
When the refrigerant gas leaks, find up the leaked position and repair it surely
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas…
-
Only a qualified installer or service person is allowed to do installation work. Inappropriate
installation may result in water leakage, electric shock or fire. Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner. If the unit is installed in a small room, take appropriate measures to prevent…
-
Declaration of Conformity
Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Amphur Muang, Pathumthani 12000, Thailand Authorized Representative/TCF holder: Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd. Porsham Close, Belliver Industrial Estate…
-
FILE NO. SVM-13050-3
-
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has…
-
4. Tools
1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional…
-
1. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
1-1. Indoor Unit RAV-SM567CTP* – 15 – SVM-13050.indb 15 6/27/13 10:35 AM
-
RAV-SM807CTP*
– 16 – SVM-13050.indb 16 6/27/13 10:35 AM
-
RAV-SM1107CTP*, RAV-SM1407CTP*, RAV-SM1607CTP*
– 17 – SVM-13050.indb 17 6/27/13 10:35 AM
-
2. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
2-1. Indoor Unit • Single type (Combination of 1 indoor unit and 1 outdoor unit) (Indoor unit) Distributor (Strainer incorporated) TCJ sensor Strainer Heat exchanger TC sensor Heating Cooling Liquid side (Outer dia : ØB) Gas side (Outer dia : ØA) Capillary tube specifications To outdoor unit To…
-
Triple type (3 indoor units and 1 outdoor unit)
Heating Cooling (Indoor unit A) (Indoor unit B) TCJ sensor Distributor (with strainer) Strainer (Indoor unit C) TCJ sensor Distributor (with strainer) Strainer Heat exchanger TCJ sensor Distributor (with strainer) Strainer Heat exchanger Heat exchanger TC sensor TC sensor Liquid-side Gas-side (outer…
-
Double-twin type (4 indoor units and 1 outdoor unit)
Heating Cooling (Indoor unit A) TCJ sensor Distributor (with strainer) (Indoor unit B) TCJ sensor Distributor (with strainer) Strainer Strainer Heat exchanger Heat exchanger TC sensor TC sensor Liquid-side (outer diameter: ϕ A) Gas-side (outer diameter: ϕ B) Liquid-side (outer diameter: ϕ A)…
-
3. WIRING DIAGRAM
3-1. Indoor Unit 3-1-1. Ceiling Type L1 L2 L3 N RAV-SM567CTP*, RAV-SM807CTP*, RAV-SM1107CTP*, RAV-SM1407CTP*, RAV-SM1607CTP* – 21 – SVM-13050.indb 21 6/27/13 10:35 AM
-
4. SPECIFICATIONS OF ELECTRICAL PARTS
-
5. INDOOR CONTROL CIRCUIT
5-1. Indoor Controller Block Diagram 5-1-1. Connection of Wired (Simple) Remote Controller Wired (simple ) master remote controller (Max. 2 units) Display LCD Display LED Schedule timer Function setup CPU Display LCD LCD driver Key switch Function setup CN2 CPU CN1 Key switch DC5V Remote controller…
-
5-1-2. Connection of Wireless Remote Controller Kit
Indoor unit #1 (Header) Wireless remote controller kit Receiver P.C. board Display LED Receive circuit Function setup SW Buzzer CPU DC5V Power circuit Remote controller communication circuit A #2 (Follower) A B B #3 (Follower) A B Indoor control P.C. board (MCC-1643) DC20V Remote controller…
-
5-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote Controller Kit
Indoor unit #1 (Header) Wired (simple) master remote controller (Max. 2 units) Wireless remote controller kit Display LED Receiver P.C. board Display LCD Function setup SW Display LED Receive circuit Function setup Schedule timer Display LCD LCD driver Key switch CPU CPU Function setup CN2 Buzzer…
-
5-2. Control Specifications
No. Item 1 When power supply is reset 2 Operation mode selection Outline of specifications Remarks 1) Distinction of outdoor unit When the power supply is reset, the outdoors are distinguished and the control is selected according to the distinguished result. 2) Setting of indoor fan speed and…
-
Item Room temp. control (Continued) Remarks Outline of specifications 2) Using the CODE No. 06, the setup temperature in heating operation can be corrected. Setup data Setup temp. correction +0°C +2°C +4°C +6°C Shift of suction temperature in heating operation Setting at shipment Setup data 4…
-
Remarks
No. Item Outline of specifications 6 Air speed selection 1) Operation with (HH), (H), (L) or [AUTO] mode is carried out by the command from the remote controller. 2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts. HH > H+ > H > L+ > L > UL <COOL>…
-
Item Cool air discharge preventive control Outline of specifications Remarks 1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor. As shown below, the upper limit of the revolution frequency is restricted. However B zone is assumed as C…
-
Item
Outline of specifications 9 High-temp. release control 1) The heating operation is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. • When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded…
-
Item
Outline of specifications 12 Louver control 1) Louver position setup • When the louver position is changed, the position moves necessarily to downward discharge position once to return to the set position. • The louver position can be set up in the following operation range. In cooling/dry operation…
-
Item
13 14 Outline of specifications Remarks HA control 1) This control is connected to telecontrol system or remote start/stop I/F, etc, and start/stop are available by HA signal input from the remote position. 2) This control outputs start/stop status to HA output terminal. 3) I/O specifications…
-
Item
Outline of specifications 16 Central control mode selection 1) Setting at the centerl controller side enables to select the contents which can be operated on the remote controller at indoor unit side. 2) Setup contents • 64 line central controller (TCB-SC642TLE2) [Individual]: Operated on the remote…
-
Item DC motor Outline of specifications Remarks 1) The motor operates according to the command from the indoor controller. Notes) • When the fan rotates while the air conditioner stops due to entering of outside air, etc, the air conditioner may operate while the fan motor stops. • When a fan lock…
-
Item
Outline of specifications 22 8°C heating/ Frost protective operation 1) This functional is intended for the cold latitudes and performs objective heating operation (8°C heating operation). 2) This function is valid only for combination with the outdoor units (Super Digital Inverter (SDI) 4-series…
-
SVM-13050.indb 37
TA sensor CN104 TC sensor CN101 TCJ sensor CN102 Float SW CN34 Remote controller CN41 Drain pump kit CN504 DISP(CN72) External input/output (UART) CN521 CHK(CN71) “1:1 model” Connection inter CN50 HA CN61 Louver CN510 EEPROM IC503 Ventilation output CN32 DC fan output CN210 Optional power supply…
-
SVM-13050.indb 38
CN32 CN61 CN71 CN72 CN521 HA CHK Operation check DISP Exhibition mode Option control kit Connector No. Ventilation output Function Specifications Operation output (Open collector) DC12V Warning output (Open collector) Transmission Receive 0V 12V 5V 1 3 0V 0V Remote controller prohibited input 2 1…
-
6. TROUBLESHOOTING
6-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The…
-
<Wireless remote controller type>
1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. • Is not 3-minutes…
-
6-2. Troubleshooting
6-2-1. Outline of judgment The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method. Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of the receiving part) The…
-
Lamp indication
Operation Timer Ready Alternate flash Operation Timer Ready Alternate flash Operation Timer Cause of trouble occurrence Check code F01 Heat exchanger sensor (TCJ) error F02 Heat exchanger sensor (TC) error F10 Heat exchanger sensor (TA) error F04 Discharge temp. sensor (TD) error F06 Temp. sensor…
-
6-2-2. Others (Other than Check Code)
Lamp indication Operation Timer Check code Cause of trouble occurrence Ready — During test run — Disagreement of cool/heat (Automatic cool/heat setting to automatic cool/heat prohibited model, or setting of heating to cooling-only model) Simultaneous flash Operation Timer Ready Alternate flash – 43…
-
SVM-13050.indb 44
ALT ALT ALT SIM SIM SIM SIM SIM SIM SIM ALT ALT ALT ALT ALT No communication from remote controller and network adapter (Also no communication from central control system) There is error on serial communication between indoor and outdoor units Same address as yours was detected. Communication error…
-
Error mode detected by indoor unit
Operation of diagnostic function Check code Cause of operation E03 No communication from remote controller (including wireless) and communication adapter E04 The serial signal is not output from outdoor unit to indoor unit. • Miswiring of inter-unit wire • Defective serial sending circuit on outdoor…
-
Error mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function Check code Cause of operation Status of air conditioner — Power supply error of remote controller, Indoor EEPROM error 1. Check remote controller inter-unit wiring. 2. Check remote controller. 3. Check indoor power wiring. 4. Check indoor P.C. board. 5. Check indoor…
-
6-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit)
Check code [E01 error] Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller YES Correct connection of connector. Check circuit wiring. NO Check power connection of indoor unit. (Turn on power again.) NO Check indoor P.C. board (MCC-1643). Defect → Replace YES…
-
[E04 error]
NO Does outdoor operate? YES Is group address setup of remote controller correct? NO Check CODE No. [14]. YES Are wiring in indoor unit and 1, 2, 3 inter-unit cables correct? NO Correct wiring and inter-unit cables. NO Correct wiring of connector and terminal blocks. NO Check indoor P.C. board.…
-
[E11 error]
Is the connection for the UART communication connector (Internal board CN521 red/Optional board CN1 red) normal? Yes Repair of connector connection. No Is connector lead wire for the UART communication cut? Yes Replacement of the connector’s lead wire. No Red LED (LD1) of external output board not…
-
[E18 error]
Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller. YES Correct connection of connector. Check circuit wiring. NO Check power connection status of indoor unit (Connect again). YES Is there no disconnection or contact error of connector on harness from terminal…
-
[L20 error]
Are wiring connections to communication lines U3 and U4 normal? NO Correct wiring connection. YES Is not the multiple same central control system addresses connected? YES Correct central control system address. NO Check central controller (including network adapter) and indoor P.C. board (MCC-1643).…
-
[P10 error]
Is connection of float switch connector (Indoor control board CN34) normal? NO Correct connection of connector. YES NO Check indoor P.C. board (MCC-1643). Defect → Replace YES Does float switch work? Is circuit wiring normal? YES NO Check and correct wiring and wire circuit. NO Does drain pump work?…
-
[P12 error]
Power off. Is not connection error or disconnection on the connector CN210 of indoor unit P.C. board? YES Repair the connector connection. NO Disconnect the connector CN210 to the indoor P.C. board Does the fan turn smoothly when turned by hand? NO Replace the indoor fan motor. NO Replace the indoor…
-
[P19 error]
Is operation of 4-way valve normal? (Check the pipe temp., etc. during cooling/heating operation. NO Are 1.3 to 1.6kΩ applied to resistance value of 4-way valve coil ? NO Replace 4-way valve coil. YES YES Defective Check outdoor P.C. board. Defective → Replace Check outdoor P.C. board operation.…
-
[F02 error]
Is connection of TC sensor connector (CN101 on Indoor P.C. board) correct? NO Correct connection of connector. YES Are characteristics of TC sensor resistance value normal? YES NO Replace TC sensor. ∗ Refer to Characteristics-2. Check indoor P.C. board (MCC-1643). Defect → Replace [F01 error] Is…
-
[C06 error] (“1:1 model” connection interface)
NO Are U3 and U4 communication lines normal? Correct communication line. YES NO ∗1 Correct connection of connector. Is connection of connector normal? YES ∗1 TCC-LINK central: CN51 of “1:1 model” connection interface (TCC-LINK adapter) P.C. board (MCC-1440) and CN050 of indoor P.C. board NO Are A…
-
[E03 error] (Header indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal from the remote controller (also central controller). Check A and B remote controllers and communication lines of the central control system U3 and U4. As communication is impossible, this check code [E03] is not displayed on the…
-
Temperature sensor
Temperature – Resistance value characteristic table TD, TL sensors TA, TC, TCJ, TE, TS, TO sensors Representative value Representative value Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard value) (Maximum value) Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard…
-
7-1. Indoort Unit CAUTION <Model name: RAV-SM∗∗∗CTP∗> For the above models, set the CODE No. “ ” and the setting data “0000” (initial) to “0001”. <Note: when replacing the P.C. board for indoor unit servicing> The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P.C. board…
-
[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out. Step 1 Push SET , CL and TEST button on the remote controller simultaneously for more than 4 seconds. ∗ When the group operation control is performed, the unit No. displayed for the first…
-
b) Group operation (including twin triple and double twin system)
Turn on the indoor unit(s) with its P.C. board replaced to the P.C. board for indoor unit servicing, according to either methods 1 or 2 shown below. 1. Turn on only the indoor unit with its P.C. board replaced. (Be sure to confirm the remote controller is surely connected. If not, the operation [3]…
-
Step 4
Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above again. Step 5 Change the CODE No. (DN) to “ ” by pushing (this is the setting for the filter sign lighting time.) Step 6 Check the setting data displayed at this time with the setting data put…
-
Table 1. Setting data (CODE No. table (example))
DN Item Setting data Factory-set value 01 Filter sign lighting time Depending on Type 02 Filter pollution leve 0000: standard 03 Central control address 0099: Not determined 06 Heating suction temperature shift 0002: +2°C (flooring installation type: 0) 0F Cooling only 0000: Heat pump 10 Type…
-
8. SETUP AT LOCAL SITE AND OTHERS
8-1. Indoor Unit 8-1-1. Test Run Setup on Remote Controller <Wired remote controller> TEST 1. When pushing button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. ON / OFF Then push button. • “TEST” is displayed on LC display during operation of Test Run. • During…
-
8-1-2. Forced Defrost Setup of Remote Controller (For wired remote controller only)
(Preparation in advance) 1 Push TEST SET CL + + buttons simultaneously for 4 seconds or more on the remote controller. (Push buttons while the air conditioner stops.) The first displayed unit No. is the master indoor unit address in the group control. 2 Every pushing UNIT button, the indoor unit No.…
-
8-1-4. Function Selection Setup
<Procedure> Perform setting while the air conditioner stops. 1 Push TEST SET CL + + buttons simultaneously for 4 seconds or more. The first displayed unit No. is the master indoor unit address in the group control. In this time, fan and louver of the selected indoor unit operate. 2 Every pushing…
-
Function selection CODE No. (DN) list
DN Item 01 Filter sign lighting time 0000: None 0002: 2500H 0004: 10000H 02 Filter stain level 0000: Standard 0001: Heavy stain (Half of standard time) 0000: Standard 03 Central control address 0001: No.1 unit 0099: Undecided 0099: Undecided 06 Heating suction temp. shift 0F Cooling-only 0000: Heat…
-
DN
Item 42 Self-clean operation time C2 Current demand X% to outdoor unit Contents 0000: None 0001: 0.5 h ~ 0012: 6.0 h Set when compressor-ON time is 10 to 60 minutes. When ON-time is 60 minutes or more, the double of this operation time setting is set. 0050: 50% to 0100: 100% At shipment from factory…
-
8-1-5. Wiring and Setting of Remote Controller Control
2-remote controller control (Controlled by 2 remote controllers) This control is to operate 1 or multiple indoor units are operated by 2 remote controllers. (Max. 2 remote controllers are connectable.) • When connected 2 remote controllers operate an indoor unit Remote controller switch (Master)…
-
<Wireless remote controller>
Remote controller address (A-B selection) setting • When two or more signal receiving units are installed in a room, a unique address can be set for each signal receiving unit to prevent interference. • Address (A-B selection) must be changed on both signal receiving unit and wireless remote…
-
Wireless remote controller (A-B selection)
Using 2 wireless remote controllers for the respective air conditioners, when the 2 air conditioners are closely installed. Wireless remote controller B setup 1. Start the air conditioner. 2. Point the wireless remote controller at the indoor unit. 3. Push and hold CHK button on the wireless remote…
-
8-1-6. Monitor Function of Remote Controller Switch
Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller. <Procedure> 1 Push CL TEST + buttons simultaneously for 4 seconds to call the service monitor mode. The…
-
Calling of error history
<Contents> The error contents in the past can be called. <Procedure> 1 Push TEST SET + buttons simultaneously for 4 seconds or more to call the service check mode. Service Check goes on, the CODE No. is displayed, and then the content of the latest alarm is displayed. The number and error contents…
-
Indoor unit power-ON sequence
• The unit without power feed waits entirely → Waiting status is released by system start • Reboot when power is fed on the way Power ON <By indoor unit which receives power feed from outdoor unit> <Automatic address judgment> Not normal NO 3 minutes elapse Gr construction check YES Normal ∗ Gr…
-
8-2. Setup at Local Site / Others
Model name: TCB-PCNT30TLE2 8-2-1. 1:1 Model Connection Interface (TCC-LINK adapter) 1. Function This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface. 2. Microprocessor block diagram Indoor unit Central controller 1:1 model connection interface P.C. board…
-
4. Wiring Specifications
• Use 2-core with no polar wire. No. of wires Size • Match the length of wire to wire length of the central control Up to 1000m: twisted wire 1.25mm2 system. If mixed in the SMMS system, the wire length is 2 Up to 2000m: twisted wire 2.0mm2 lengthened with all indoor/outdoor inter-unit wire length…
-
Terminator (SW01) 52 85 7. Address setup In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual. 8-3. How to Set up Central Control Address Number When…
-
9. ADDRESS SETUP
9-1. Address Setup <Address setup procedure> When an outdoor unit and an indoor unit are connected and they are twin-triple, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup…
-
9-2. Address Setup & Group Control
<Terminology> Indoor unit No. Group address : N – n = Outdoor unit line address N (Max. 30) – Indoor unit address n (Max. 64) : 0 = Single (Not group control) 1 = Header unit in group control 2 = Follower unit in group control Header unit (= 1) : The representative of multiple indoor units in group…
-
4. Single group operation
• Each indoor unit controls the outdoor unit individually. 2-1 Header/Sub 1-1 Header/Sub 4-1 Header/Master 3-1 Header/Sub 8-1 Header/Sub 5. Multiple groups operation (Manual address setting) 2-1 Header/Sub 1-1 Header/Sub 1-2 Follower/Sub 3-1 Header/Master 3-2 Follower/Sub 3-3 Follower/Sub • Master…
-
9-2-2. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit) 1-1 Individual 1-2 Header/Sub 1-1 Follower/Sub 1-2 Header/Master (1-2) (1-3) 1-3 Follower/Master 1-1 Follower/Sub (1-1) (1-2) (1-1) (Header/Master) Only turning on source power supply (Automatic completion) 2. Group operation (Multiple outdoor units = Multiple indoor…
-
9-3. Address Setup (Manual Setting from Remote Controller)
In case that addresses of the indoor units will be determined prior to piping work after wiring work • Set an indoor unit per a remote controller. • Turn on power supply. 1 Push (Example of 2-lines wiring) (Real line: Wiring, Broken line: Refrigerant pipe) Outdoor Outdoor Indoor Indoor Indoor Indoor…
-
9-4. Confirmation of Indoor Unit No. Position
1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure> 1 Push 2 Push ON / OFF button if the unit stops. UNIT LOUVER button.…
-
<Maintenance/Check list>
Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner. It is also recommended to maintain the units once a year regularly when operating…
-
10. DETACHMENTS
10-1. Ceiling Type DANGER CAUTION Before carrying out the repair or removal work, be sure to set the circuit breaker to the OFF position. Otherwise, electric shocks may result. No. 1 Part name Air intake grille Be sure to put on the gloves at disassembling work; otherwise an injury will be caused by…
-
Part name
3 Electric parts box Procedure Remarks 1. Detachment 1) Perform works of 1 of 2 . 2) Remove the screws of electric parts box. 3) Draws out forward after the electric box is moved in the direction of the arrow, and the back of the part electric part boxis hung on the edge of the main body. Screws 2.…
-
Part name Fan, Fan case, Shaft, Bearing Procedure Remarks Quantity of fan Model 56 80 QTY Installation Fan motor both sides One of shafts is bearing. The shaft middle part is supported in the bearing. 1. Detachment NOTE It explains the following content by 110 to 160 type. 1) The hanging claw on…
-
Part name
Procedure Remarks 3) When the bearing is installed in the shaft, perform work of 1) . The coupling side is set to the ditch and the fan is fixed with the hexagonal screw hole. NOTE Be sure to use a torque wrench for fixing and tighten with 2.5 to 3.4N.m. The ditch of shaft The ditch of shaft 4) The…
-
Part name Procedure Remarks Fan motor 1. Detachment 1) Perform works of 1 of 5 . 2) Remove connectors for fan motor wiring from control P.C. board. CN210 : Fan motor (7P, White) NOTE First unlock the housing and then remove the connectors. 3) Remove the fixing screws of the fixing plate (2 pcs.) at…
-
Part name Procedure Remarks Side cover 1. Detachment 1) Perform works of 1 of 1 . 2) Remove the screws of the side cover. (One side: Ø4 x 10, 1 pcs.) 3) Slide to the air discharge side, remove the side cover. Screw 2. Attachment 1) Insert hooking claw of the side cover in the square hole on the main…
-
Part name
8 Under panel Procedure Remarks 1. Detachment 1) Perform works of 1 of 7 . 2) Remove the support plate. (80-160 type only) (Ø4 x 10, 1 pcs.) The screw on a front side is removed, and it detaches it from the square hole on the back side. 3) The screw on both sides is removed. (Ø4 x 10, 2 pcs.) 4) The…
-
Part name Procedure Remarks Drain pan 1. Detachment 1) Perform works of 1 of 8 . 2) Remove the drain cap and then extract the drain water accumulated in the drain pan. NOTE When removing the drain cap, be sure to receive drain water using a bucket, etc. Drain cap Heat insulator 3) The drain hose is…
-
No. Part name
10 Heat exchanger Procedure Remarks 1. Detachment 1) Recover the refrigerant gas and then remove the refrigerant pipe of the indoor unit. 2) Perform works of 1 of 9 . Pull out sensor wires from the holder. 3) The screw that is the fixing of the piping support is removed, and the piping support is…
-
SVM-13050.indb ! ! ! ! 034 ! ! 035 ! 036 ! 037 FILE NO. SVM-13050 11. EXPLODED VIEWS AND PARTS LIST 11-1. RAV-SM567CTP-E, RAV-SM567CTP-TR – 94 – 6/27/13 10:36 AM
-
Ref.No
-
таблицы и схемы — в просмотре
-
Parts No
-
Ref.No
-
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or…
-