FILE NO. A06-005
SERVICE MANUAL SPLIT TYPE <DIGITAL INVERTER> INDOOR UNIT RAV-SM562MUT-E This Service Manual describes contents of the new indoor unit. For the outdoor unit, refer to the Service Manual with FILE NO. A05-001. R410A PRINTED IN JAPAN, Aug.,2006 ToMo
-
1. SPECIFICATIONS
1-1. Indoor Unit 1-1-1. Compact 4-way Cassette Type DI DI TWIN SDI SDI TWIN SM562MUT-E SM562MUT-E SM562MUT-E SM562MUT-E RAV- — SM562MUT-E — SM562MUT-E RAV- SM562AT-E SM1102AT-E SP562AT-E SP1102AT-E Cooling capacity (kW) 5.0 10.0 5.0 10.0 Heating capacity (kW) 5.6 11.2 5.6 11.2 Indoor unit Model…
-
1-2. Combination Specifications of Indoor Units with Outdoor Units
Indoor Unit RAV-SM562MUT-E Outdoor Unit RAV-SP562AT-E Cooling Heating Standard capacity (Note 1) (kW) 5.30 (2.20-5.60) 5.60 (2.20-7.10) Energy consumption effect ratio (W/W) 3.46 4.67 Power supply 1 phase 230V (220-240V) 50Hz Running current (A) 7.17-6.57 5.62-5.15 Power consumption (kW) 1.53 1.20…
-
1-3. Operation Characteristic Curve
-
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Indoor Unit 595 to 660 Ceiling open dimension 1000 or more Check port ( 450) Stand-up 850 or less Indoor unit Bottom face of ceiling Note) As ABS is used for the drain discharge port of the main unit, the vinyl chlor paste cannot be used. Use the flexible hose (Band fix) included in the…
-
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Indoor Unit/Outdoor Unit • Single type (Combination of one indoor unit and one outdoor unit) Heating time Cooling time RAV-SM562MUT-E Distributor (Strainer incorporated) Indoor unit TCJ sensor Air heat exchanger TC sensor Refrigerant pipe at liquid side Outer diameter Ø6.4 Refrigerant pipe at…
-
Indoor unit TCJ sensor Air heat exchanger TC sensor Outer diameter of refrigerant pipe Gas side ØA Liquid side ØB 12.7mm 6.4mm * The refrigerating cycle of the indoor units differs according to the models to be combined. For the refrigerating cycles of the other indoor units, refer to the…
-
Indoor unit TCJ sensor Air heat exchanger TC sensor Outer diameter of refrigerant pipe Gas side ØA Liquid side ØB 12.7mm 6.4mm Refrigerant pipe at gas side Ø12.7 Packet valve Packed valve Outer dia. ØA Refrigerant pipe at liquid side Ø6.4 Packet valve Outdoor unit PMV (Pulse Motor Valve)…
-
4. WIRING DIAGRAM
4-1. Indoor Unit 4-1-1. Compact 4-way Cassette Type TA FS CN34 (RED) LM1 TC Connection interface (option) CN104 (YEL) CN102 (RED) CN101 (BLK) CN80 (GRN) CN73 (RED) CN70 (WHI) (EXCT) MCC-1402 CN33 (WHI) LM2 TCJ Control P.C. Board for Indoor Unit FM CN68 (BLU) CN304 (GRY) 2 2 CN001 1 1 (WHI) – ~ WHI 1…
-
• Single type
Power supply 220-240V Single phase 50Hz Outdoor unit L N Indoor unit Notes) A B A B Wired remote controller RBC-AMT31E 1. : indicates a terminal block 2. Broken line and chain line indicate wiring at local site. 3. For the inner wiring diagram of the outdoor unit and the indoor unit, refer to the…
-
5. SPECIFICATIONS OF ELECTRICAL PARTS
-
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful…
-
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.70 0.80 0.80 5/8 15.88 1.00 1.00 2) Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to…
-
c) Insertion of Flare Nut
d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a…
-
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal diameter Outer diameter (mm) Thickness (mm) 1/4 6.35 3/8 Dimension (mm) Flare nut width (mm) A B C D 0.8 9.0 9.2 6.5 13 17 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.4 19.0 16.0 23 27 3/4 19.05 1.0 23.3 24.0 19.2 34 36 6˚ to 4 45˚ B A C 43˚ D to 4 5˚…
-
6-3. Tools
6-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7…
-
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the…
-
Be sure to make setting so that liquid can be charged
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment…
-
2) Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy to remove slag after brazing. • The corrosive action to the treated metal and brazing filler is minimum. • It excels in coating performance and…
-
6-6. Tolerance of Pipe Length and Pipe Head
Model (RAV-) Pipe length (One Direction) Height Difference 1102AT Full length L + a or L + b Below 50m (actual length) Branch piping a, b Below 15m (actual length) Difference of branch piping length b – a, or a - b Below 10m Outdoor unit installed above Indoor unit Below 30m Outdoor unit installed…
-
6-7. Additional Refrigerant Amount
<Formula for Calculating Additional Refrigerant Amount> Do not remove the refrigerant even if the additional refrigerant amount becomes minus result as a result of calculations by the following formula and operate the air conditioner as it is. Additional refrigerant amount (kg) = Main piping…
-
6-8. Piping Materials and Sizes
Use copper tube of Copper and copper alloy seamless pipes and tubes, with 40mg/10m or less in the amount of oil stuck on inner walls of pipe and 0.8mm in pipe wall thickness for diameters for diameters 6.4, 9.5 and 12.7mm and 1.0mm, for diameter 15.9mm. Never use pipes of thin wall thickness such as…
-
7. CONTROL BLOCK DIAGRAM
7-1. Indoor Control Circuit Main (Sub) master remote controller *1 Connection Interface is attached to master unit. (In case of group control operation) Display LCD Weekly timer LCD driver Function setup CPU *2 Weekly timer is not connectable to the sub remote controller. Function setup CPU Display…
-
7-2. Control Specifications
No. Item Outline of specifications 1 When power supply is reset 1) Distinction of outdoor units When the power supply is reset, the outdoors are distinguished, and control is exchanged according to the distinguished result. 2) Setting of speed of the indoor fan/setting whether to adjust air…
-
Room temperature control Outline of specifications Remarks 1) Adjustment range Remote controller setup temperature (°C) COOL/ DRY Heating operation Auto operation Wired type 18 to 29 18 to 29 18 to 29 Wireless type 18 to 30 16 to 30 17 to 27 2) Using the item code 06, the setup temperature in…
-
Air speed selection (Continued) Remarks Outline of specifications <HEAT> Ta (˚C) L(L) L(H) H(H) (-0.5) –1.0 (0) Tsh (+0.5) +1.0 (+1.0) +2.0 (+1.5) +3.0 E H (HH) D HH (HH) C B (+2.0) +4.0 A Value in the parentheses indicates one when thermostat of the remote controller works. Value without…
-
Cool air discharge preventive control Outline of specifications Remarks 1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor. As shown below, the Tc (˚C) Tcj upper limit of the HH 32 revolution frequency H 30 L is determined. E zone In D…
-
Outline of specifications
9 Drain pump control 1) In cooling operation (including Dry operation), the drain pump is usually operated. 2) If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output. 3) If the float switch operates while drain…
-
Outline of specifications
12 Frequency fixed operation (Test run) <In case of wired remote controller> 1. When pushing [CHECK] button for 4 seconds or more, [TEST] is displayed on the display screen and the mode enters in Test run mode. 2. Push [ON/OFF] button. 3. Using [MODE] button, change the mode from [COOL] to [HEAT]. •…
-
Outline of specifications
14 Central control mode selection 1) Setting at the central controller side enables to select the contents which can be operated on the remote controller at indoor unit side. 2) RBC-AMT31E [Last push priority] : The operation contents can be selected from both remote controller and central…
-
Connection interface
DC fan output Indoor/Outdoor inter-unit cable Optional power supply – 32 – Remote controller power supply LED DC fan return *1 Drain pump output Float SW Fan output HA (T10) TA sensor Optional output Louver (Used only for 4-way Air Discharge Cassette Type, Under Ceiling type) TCJ sensor EXCT DISP…
-
8. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
8-1. Indoor Control Circuit 8-1-1. Outline of Main Controls 1. Pulse Motor Valve (P.M.V.) control 1) PMV is controlled with 50 to 500 pulses during operation, respectively. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor. 3) In heating…
-
8-1-2. Indoor P.C. Board Optional Connector Specifications
Function Option output Outside error input Filter option error Connector No. Pin No. CN60 1 DC12V (COM) 2 Defrost output ON during defrost operation of outdoor unit 3 Thermo. ON output ON during Real thermo-ON (Comp ON) 4 Cooling output ON when operation mode is in cooling system (COOL, DRY, COOL in…
-
9. TROUBLESHOOTING
9-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The…
-
<Wireless remote controller type>
1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. • Is not 3-minutes…
-
9-2. Check Code List
Error mode detected by indoor and outdoor units Wireless sensor lamp display Diagnostic function Wired remote controller Operation Timer Ready Check code ¥ l l E03 – 37 – l l ¥ E04 ¥ l l E08 ¥ l l E10 ¥ l l E18 ¥ ¥ ¥ ¥ l l ¥ ¥ ¥ F01 ¥: Flash, ¡: Go on, l: Go off Cause of operation No communication…
-
Wireless sensor lamp display Diagnostic function Wired remote controller Operation Timer Ready Check code ¥ l ¥ L09 l ¥ l L29 ¥ ¡ ¥ L30 ¥ ¡ ¥ L31 Cause of operation Unset indoor capacity Outdoor unit and other errors • Communication error between CDB and IPDU (Coming-off of connector) • Heat sink…
-
Error mode detected by remote controller
¥: Flash, ¡: Go on, l: Go off Wireless sensor lamp display Diagnostic function Wired remote controller Judgment and measures Cause of operation Operation — Timer Ready — ¥ — l l Status of air conditioner Condition Check code No communication with master indoor unit • Remote controller cable is not…
-
9-3. Error Mode Detected by LED on Outdoor P.C. Board
RAV-SM562AT-E / RAV-SP562AT-E <SW801: LED display in bit 1, bit 2 OFF> • When multiple errors are detected, the latest error is displayed. • When LED display is ¡ (Go on), there is the main cause of trouble on the objective part of control at CDB side and the unit stops. • When LED display is ¥…
-
9-4. Troubleshooting Procedure for Each Check Code
9-4-1. Check Code [E01 error] NO Correct inter-unit cable of remote controller. Is inter-unit cable of A and B normal? YES Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? YES Correct connection of connector. Check circuit cables. NO Check power…
-
[E04 error]
NO Does outdoor unit operate? YES NO Is setup of group address correct? Check item code [14]. YES NO Correct inter-unit cable. Are 1, 2, 3 inter-unit cables normal? YES Are connections from connectors of inter-terminal blocks (1, 2, 3) of indoor/outdoor units normal? NO Correct connection of…
-
[E10 error]
® Check indoor control P.C. board (MCC-1402). Defect Replace [E18 error] NO Correct inter-unit cable of remote controller. Is inter-unit cable of A and B normal? YES Is there no disconnection or contact error of connector on harness from terminal block of indoor unit? YES Correct connection of…
-
[L20 error]
NO Correct cable connection Are cable connections to communication line U3, U4 normal? YES YES Are not multiple same central control network addresses connected? Correct central control network address. NO ® Check central controller (including connection interface) indoor P.C. board. Defect Replace.…
-
[P12 error]
<Only for 4-way air discharge cassette type models> Turn off the power. Are not there connections errors or disconnection on connectors CN333 and CN334 of indoor unit P.C. board (MCC-1402)? YES Correct connection of connector. NO Remove connectors CN333 and CN334 of indoor unit P.C. board…
-
[P22 error]
Are connections of CN301 and CN300 of P.C. board correct? YES Does the fan rotate without trouble when handling the fan with hands under condition of removing CN301 and CN300 from P.C. board? CN301, * CN303 NO YES The status that the resistance values between leads below are 50 to 80W for 40W motor…
-
[P19 error]
Is operation of 4-way valve normal? NO Is voltage applied to 4-way valve coil terminal in heating operation? YES NO NO YES Is flow of refrigerant by electron expansion valve normal? ® Check 4-way valve Defect Replace YES Check and replace electron expansion valve. NO Is circuit cable normal? YES NO…
-
[F01 error]
Is connection of TCJ sensor connector (Indoor P.C. board CN102) normal? NO Correct connection of connector. YES Are characteristics of TCJ sensor resistance value normal? YES NO Replace TCJ sensor. * Refer to Characteristics-2. Check indoor P.C. board (MCC-1402). Defect Replace ® [P26 error] NO…
-
[P29 error]
NO Are connections of cable/connector normal? Check and correct circuit cabling such as cabling to compressor. YES NO Is compressor normal? YES YES Compressor error ® Replace Is not earthed? NO Is not winding shorted? (Is resistance between windings 0.6 to 1.2W?) YES Compressor error ® Replace NO…
-
[F06 error]
-
[L29 error]
In the case of SUPER DIGITAL INVERTER Are connections of CDB CN800 and CDB IPDU CN06 connectors normal? NO Correct connection of connector. YES Was the error just after power ON determined? YES NO Are cabling/connector normal? Check cabling between IPDU and CDB and connector. YES NO ® IPDU P.C.…
-
[P03 error]
Is protective control such as discharge temprelease control normal? NO Are connections of cable/connector normal? YES NO Correct the cabling and connection of connector. YES Check parts. Defect NO ® Replace Check and correct the charged refrigerant amount. Is charged refrigerant amount normal? YES…
-
[P04 error]
Is high-voltage protective operation by TE sensor normal? NO YES NO Is connection of cabling connector normal? Correct connection of cabling connector. YES ® Check TE sensor. Defect Replace NO Does cooling outdoor fan normally operate? YES NO Is connection of connector normal? Correct connection of…
-
[C06 error] (Central controller)
NO Is U3, U4 communication line normal? Correct communication line. YES Are connections between connectors CN51 of connection interface P.C. board and connectors CN51 of indoor P.C. board normal? NO Correct connection of connector. YES NO Is A, B communication line normal? Check connections of A, B…
-
[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal sent from the main remote controller (and central controller). In this case, check the communication cables of the remote controllers A and B, the central control system X and Y. As communication is disabled, [E03] is not displayed…
-
9-4-2. Relational Graph of Temperature Sensor Resistance Value and Temperature
-
[Requirement when replacing the service indoor P.C. board assembly] In the non-volatile memory (Hereinafter said EEPROM, IC10) installed on the indoor P.C. board before replacement, the type and capacity code exclusive to the corresponding model have been stored at shipment from the factory and the…
-
r1 Readout of the setup data from EEPROM
(Data in EEPROM contents, which have been changed at the local site, are read out together with data in EEPROM set at shipment from the factory.) TEST CL SET buttons of the remote controller at the same time for 4 seconds or more. 1 1. Push , , and (Corresponded with No. in Remote controller) When…
-
r3 Writing of the setup contents to EEPROM
(The contents of EEPROM installed on the service P.C. board have been set up at shipment from the factory.) TEST CL SET 1. Push , , and buttons of the remote controller at the same time for 4 seconds or more. 1 (Corresponded with No. in Remote controller ) In group operation control, the master…
-
Memorandum for setup contents (Item code table (Example))
DN Item Memo 01 Filter sign lighting time According to type 02 Dirty state of filter 0000: Standard 03 Central control address 0099: Unfixed 06 Heating suction temp shift 0002: +2°C (Floor type: 0) 0F Cooling only 0000: Shared for cooling/heating 10 Type According to model type 11 Indoor unit…
-
11. SETUP AT LOCAL SITE AND OTHERS
11-1. Indoor Unit 11-1-1. Test Run Setup on Remote Controller RAV-SM562MUT-E <Wired remote controller> TEST 1. When pushing button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. ON / OFF button. Then push • “TEST” is displayed on LC display during operation of…
-
<In case of wireless remote controller>
Procedure Description Turn on power of the air conditioner. 1 The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and 1 minute when power has been turned on at the next time and after. After the specified time has passed, perform a test…
-
DN Description Item At shipment 01 Filter sign lighting time 0000 : None 0002 : 2500H (4-Way/Duct/Ceiling Type) 0002 for D.I. and S.D.I. models 02 Dirty state of filter 0000 : Standard 0001 : High degree of dirt (Half of standard time) 0000 : Standard 03 Central control address 0001 : No.1 unit 0099…
-
11-1-2. Cabling and Setting of Remote Controller Control
2-remote controller control (Controlled by two remote controllers) One or multiple indoor units are controlled by two remote controllers. (Max. 2 remote controllers are connectable.) • 1 indoor unit is controlled by 2 remote controllers <Wired remote controller> How to set wired remote controller as…
-
11-1-3. Monitor Function of Remote Controller Switch
n Call of sensor temperature display <Contents> Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling the service monitor mode from the remote controller. <Procedure> 1 Push CL TEST + buttons simultaneously for 4 seconds or more to call the…
-
n Calling of error history
<Contents> The error contents in the past can be called. <Procedure> SET DATA UNIT No. 1 Push CL TEST R.C. + buttons simultaneously for 4 seconds or more to call the service check mode. Service Check goes on, the item code 01 is displayed, and then the content of the latest alarm is displayed. The…
-
11-2. Setup at Local Site / Others
Model name: TCB-PCNT30TLE2 and TCB-PX30MUE 11-2-1. TCC-LINK Adapter (For TCC-LINK Central Control) 1. Function This model is an optional P.C. board to connect the indoor unit to TCC-LINK (Central controller). 2. Microprocessor Block Diagram Indoor unit TCC-LINK adapter P.C. board CN050 Indoor…
-
3) Install the spacers and P.C. board that are attached to TCB-PCNT30TLE2, on the Connection Interface Kit. Spacers (Attached to the TCB-PCNT30TLE2) P.C. board (Attached to the TCB-PCNT30TLE2) 4) Remove the 2P terminal block for the communication cable of the electric parts box on the unit, and then…
-
6) Setting for Central Control
For Central Control setting, refer to the Installation Manual of the TCB-PCNT30TLE2. 7) After the installation work has been completed, install the Connection Interface Kit cover to the Connection Interface Kit tightened with the two screws (4 ×10). Screw (4 ×10) Connection Interface Kit cover Hook…
-
5. Wiring Specifications
• Use 2-core with no polar wire. Size No. of wires • Match the length of wire to wire length of the central Up to 1000m: twisted wire 1.25mm2 control system. 2 Up to 2000m: twisted wire 2.0mm2 If mixed in the system, the wire length is lengthened with all indoor/outdoor inter-unit wire length at…
-
Terminator (SW01) 52 85 8. Address Setup In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to TCC-LINK Adapter Installation Manual. 11-3. How to Set up Central Control Address Number When connecting…
-
12. ADDRESS SETUP
12-1. Address Setup <Address setup procedure> When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of…
-
12-2. Address Setup & Group Control
<Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Individual (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group…
-
12-3. Address Setup
In case that addresses of the indoor units will be determined prior to piping work after cabling work (Manual setting from remote controller) <Address setup procedure> • Set an indoor unit per a remote controller. • Turn on power supply. 1 Push SET CL (Example of 2-lines cabling) (Real line…
-
1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure> 1 Push 2 Push ON / OFF button if the unit stops. UNIT No. UNIT button.…
-
13. DETACHMENTS
13-1. Indoor Unit Ceiling panel: RBC-UM11PG(W)E Preparing work: 1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply breaker. (Otherwise an electric shock may be caused.) 2. Be sure to put on the gloves when working; otherwise an injury may…
-
Adjust corner cover Procedure Remarks 1. Detachment 1) Perform work of procedure of 1 -1. 2) Turn clockwise screws (4 positions) at the suction port corner until adjust corner cover rises up. NOTE) 1 When you work, keep the torque at below 12N•m. Do not use an electric screwdriver; otherwise the…
-
Control P.C. board Procedure Remarks 1. Detachment 1) Perform works of procedure 1 -1- and 2 -1. 2) Remove the connectors connected from the control P.C. board to other parts. CN33 : Flap motor (5P, White) CN34 : Float switch (3P, Red) CN41 : Terminal block of remote controller (3P, Blue) CN40…
-
Part name Electric parts box Procedure Remarks 1. Detachment 1) Perform works of procedure 1 -1-and 2 -1. 2) Remove connectors of the lead wire connected to the following connectors of the control P.C. board. CN33 : Flap motor (5P, White) CN34 : Float switch (3P, Red) CN68 : Drain pump (3P, Blue)…
-
Bell mouth Procedure Remarks 1. Detachment 1) Perform work of procedure 1 -1. 2) Take off the lead wires of the drain pump, float switch, and fan motor from the bell mouth. 3) Take off fixing screws of the bell mouth. (Ø4 × 10, 4 pcs.) Fixing claws for lead wires Bell mouth 2. Attachment 1) Mount…
-
Fan motor Procedure Remarks 1. Detachment 1) Perform work of procedure 8 . 2) Take off screws fixed with lead holding bracket of the fan motor. (Ø4 × 10, 2 pcs.) 3) Open wiring holding part of the fan motor lead holding bracket and then take off the fan motor lead wire from the bracket. 4) Take off…
-
Drain pan Procedure Remarks 1) Perform works of procedure 4 -1 and 7 -1. 2) Remove the drain cap and extract drain water accumulated in the drain pan. 2 screws 1. Detachment NOTE) Soc Socket et of drain drain pan When removing the drain cap, be sure to receive drain water with a bucket, etc. 3) Take…
-
Heat exchanger Procedure Remarks 1. Detachment 1) Recover refrigerant gas. 2) Remove the refrigerant pipe at indoor unit side. 3) Perform work of procedure 10 -1. 4) Take off screws (Ø4 × 10, 3 pcs.) fixing the piping cover to remove the piping cover. 5) While holding the heat exchanger, remove…
-
14. EXPLODED VIEWS AND PARTS LIST
14-1. Ceiling Panel RBC-UM11PG(W)E Location No. Part No. 43109414 4302C059 43180332 43497012 43100322 43107259 43122089 43122090 Description Location No. Part No. 43122091 43122092 43122093 43107261 43100369 43107262 43107263 43160580 Grille, Air Inlet Motor, Louver Air Filter Screw Cover, Panel…
-
14-2. Compact 4-way Air Discharge Cassette Type
-
Location
No. Part No. Description 43120225 43122094 43172185 43121738 4314J329 4314Q034 43047685 43149351 43047688 43149353 43147195 43049697 43170244 43079249 43060029 43163052 43119482 43170248 43119483 43097212 43019904 43179135 43139137 43162056 43177001 43151289 43179126 43166002 239 43166004 240…
-
WARNINGS ON REFRIGERANT LEAKAGE
Important Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity…
-