FILE NO.SVM-05053-1
SERVICE MANUAL HI WALL TYPE (INDOOR UNIT) RAV-SM562KRT-E RAV-SM802KRT-E R410A Rev. Mar, 2006
-
1. SPECIFICATIONS
1-1. High-Wall Type (Indoor Unit) Model name RAV-SM562KRT-E Standard capacity (Note 1) (kW) Cooling Heating 5.1 (1.5 – 5.6) 5.6 (1.5 – 6.3) Heating low temp. capacity (Note 1) (kW) 2.93 [D] (A) 8.33–7.63 8.138–7.46 Power consumption (kW) 1.74 1.7 (Low temp.) (kW) Power factor (%) Main unit Outer…
-
Operation characteristic curve
<Cooling> <Heating> RAV-SM802KRT-E RAV-SM802KRT-E 12 10 Current (A) Current (A) RAV-SM562KRT-E 4 RAV-SM562KRT-E 4 •Conditions Indoor : DB27 C/WB19°C Outdoor : DB35°C Air flow : High Pipe length : 7.5m 230V Compressor speed (rps) Capacity ratio (%) 90 Capacity ratio (%) 40 <Heating> Compressor speed…
-
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
High-Wall Type RAV-SM562KRT-E/RAV-SM802KRT-E Back body 998 Air inlet Air outlet Front panel Grille inlet Knock out system 50 Knock out system Drain hose (0.54 m) Connection pipe (0.49 m) (Flare ∅6.35) Connection pipe (0.39 m) ∅15.88) ∅12.7) 998 763.5 (For stud bolt ∅6) 450 20 (For stud bolt ∅8 -∅10)…
-
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Hi Wall type RAV-SM562KRT-E/SM802KRT-E Indoor unit TCJ sensor Air heat exchanger Model Outer diameter of refrig erant pipe RAV-SM Gas side ØA Liquid side ØB 562KRT-E 12.7 mm 6.4 mm 802KRT-E 15.9 mm 9.5 mm TC sensor Pd Refrigerant pipe at gas side Outer dia. ØA Refrigerant pipe at liquid side…
-
4. WIRING DIAGRAM
4-1. Hi Wall type (Indoor unit) RAV-SM562KRT-E/SM802KRT-E TERMINAL BLOCK 654321 654321 6543 6543 1 1 CN33 (WHI) CN210 (WHI) BLU RED F301 FUSE T3.15A 250V BLU YEL WHI BLK CN22 11 54321 F S U3U4 BLU PNK YEL ORN RED BRW BLK F A N M O T O R BLU LOUVER MOTOR BUS EMG 1 2 CN50 (WHI) DC15V 33 55 CN67 (BLK)…
-
5. SPECIFICATIONS OF ELECTRICAL PARTS
-
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful…
-
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/4 6.35 0.80 0.80 3/8 9.52 0.80 0.80 1/2 12.70 0.80 0.80 5/8 15.88 1.00 1.00 (2) Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to…
-
c) Insertion of Flare Nut
d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a…
-
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal diameter Outer diameter (mm) Thickness (mm) 1/4 6.35 3/8 Dimension (mm) Flare nut width (mm) A B C D 0.8 9.0 9.2 6.5 13 17 9.52 0.8 13.0 13.5 9.7 20 22 1/2 12.70 0.8 16.2 16.0 12.9 20 24 5/8 15.88 1.0 19.4 19.0 16.0 23 27 3/4 19.05 1.0 23.3 24.0 19.2 34 36 6° to 4 45° B A C D 43° to 4 5°…
-
6-3. Tools
6-3-1. Required Tools The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7…
-
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the compound gauge's pointer has indicated - 0.1 Mpa (- 76 cmHg), place the handle Low in…
-
Be sure to make setting so that liquid can be charged
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment…
-
(2) Characteristics required for flux
1.Activated temperature of flux coincides with the brazing temperature. 2.Due to a wide effective temperature range, flux is hard to carbonize. 3.It is easy to remove slag after brazing. 4.The corrosive action to the treated metal and brazing filler is minimum. 5.It excels in coating performance and…
-
7. INDOOR UNIT CONTROL
7-1. Indoor Control Circuit Main (Sub) master remote controller (Wired) Weekly timer Display LCD Max. 8 units are connectable.*1 *1 When group and twin combination. main remote controller shal be connected follower indoor unit *2 Weekly timer is not connectable to the sub remote controller. LCD…
-
Control Specifications NO. Item 1 Control at power-on reset 2 Operation mode switching Overview of specifications (1) Identification of outdoor unit Identifies outdoor unit at power-on reset, and switches control according to the identification result. (2) Setting of indoor unit fan speed and…
-
Overview of specifications
Room temperature (2) The set temperature for HEAT operation can be corrected by code 3 control No. 06. Set data Correction of set temp. +0°C +2°C +4°C +6°C Remarks Heat intake temperature shift (When unit’s temperature sensor is used) Factory setting Set data 2 * When use of remote controller sensor…
-
Fan speed control Remarks Overview of specifications COOL HH H+ HEAT HH AP40-56 1220 AP63 1360 AP71-80 1480 H+ 1180 1140 1300 1240 1340 1320 H 1120 1060 1200 1120 1300 1200 L+ L 1060 990 1120 1020 1200 1100 UL 1040 500 H L+ L UL (3) When thermo sensor turns OFF during heating, the fan speed mode…
-
Freezing prevention control (low-temp. release) Overview of specifications (1) Performs the following operation control in the COOL or DRY mode according to the Tc (or Tcj) sensor detect temperature. When zone J in the figure below is detected for 6 minutes, the specified operating frequency is…
-
11 Flap control
Overview of specifications (1) During the first operation after power on, flap position is controlled automatically according to operation mode (COOL/HEAT). Remarks Louver angle: 0 °C (full close) Cooling Heating Full close 45° 103° 0° (2) When louver position is controlled by remote controller, the…
-
12 HA control
Overview of specifications (1) When connected to a remote control system (tele-control or remote on/off interface), operation ON/OFF can be controlled by the HA signal input. (2) Outputs operation ON/OFF status to the HA output terminal. (3) HA signal input/output specifications conform to the JEMA…
-
14 Central control
mode switching Overview of specifications (1) The scope of operation by remote controller on the indoor unit side can be switched by the setting of remote controller. (2) Scope of operation by remote controller on the indoor unit side [Individual] : All settings and ON/OFF operations are available.…
-
SW01
CN32 CN61 CN60 CN80 CN71 CN72 CN73 Ventilation output HA Option output External alarm input CHK Operation check DISP DISP mode EXCT Demand Connector No. Terminating resistor Remote controller A/B Function DC12V Output ON/OFF input OV (COM) R/C prohibition input Operation ON output DC12V (COM) Alarm…
-
8. Troubleshooting
9 1. Guide to Troubleshooting [Wired Remote Controller Type] (1) Before starting troubleshooting (a) Necessary tools/measuring equipment • Phillips screwdrivers, flat-blade screwdrivers, wrenches, pliers, nipper, etc. • Multimeter, thermometer, pressure gauge, etc. (b) Precheck A The following…
-
3) Outdoor unit fan does not work or its fan speed changes
• Is high-temp. release operation control working during heating? • Is low outside air temperature operation control working during cooling? • Is defrosting operation going? 4) Operation ON/OFF by remote controller is disabled. • Is forcible operation OFF mode set? • Is any remote controller or…
-
Outline of judgment (Contenued)
Lamp indication Check code P03 P04 Possible causes (*) Protection device Abnormal outdoor unit discharge of outdoor unit is temperature activated. Outdoor unit high-pressure system error OPERATION TIMER PREPARING P19 P22 Alternate blinking P26 P29 P31 OPERATION TIMER PREPARING F01 F02 F10 Four-way…
-
Others (Excluding check code)
Lamp indication OPERATION TIMER PREPARING Check code – Possible causes Trial operation in progress Simultaneous blinking OPERATION TIMER PREPARING – Invalid setting (Auto cooling/heating setting for auto cooling/heating unavailable unit or heating setting for cool only unit) Alternate blinking Error…
-
Blinking,
– 31 – Communication error between indoor unit MCUs Communication error between header and follower indoor units Indoor unit heat exchange sensor TCJ Alternate Alternate Alternate Simultaneous Simultaneous Simultaneous Simultaneous Simultaneous Simultaneous Simultaneous Alternate Alternate Alternate…
-
Blinking,
– 32 – Alternate P29 Position detect error Inverter Idc activated Outdoor unit fan alarm High-pressure system error Abnormal outdoor unit discharge temperature When compressor motor position error is detected When short-circuit prevention control for compressor drive circuit devices (G,Tr, IGBT) is…
-
Check Code Table
Failure mode detected by indoor unit Diagnosis function Check code Possible causes E03 No signal reception from remote controller Air conditioner status Conditions OFF Indicated when an (auto reset) error is detected Judgment and action 1. Check remote controller wiring. • No indication on remote…
-
Failure mode detected by outdoor unit (Representative codes)
• The check code used varies depending on the combination with the outdoor unit. Check code H01 H02 Diagnosis function Possible causes Air conditioner status Conditions OFF Compressor breakdown • Compressor stops due to operating frequency decrease. OFF Compressor does not work. • Overcurrent…
-
Troubleshooting by Remote Controller Check Indication Main Remote Controller (RBC-AMT31E) (1) Checking When an error occurs in the air conditioner, a check code and an indoor unit number appear on the LCD of remote controller. Check code is displayed only during operation. If indication disappears…
-
TCC-LINK Central Control Remote Controller (TCB-SC642TLE)
(1) Checking When an error occurs in the air conditioner, a Indication of unit number check code and an indoor unit number appear on UNIT No. the LCD of remote controller. Check code is displayed only during operation. Alternate blinking R.C. No. If indication disappears, check errors following…
-
3. Troubleshooting for Each Check Code
-
[E02]
(New code) R/C transmission error Possible causes Signal transmission to indoor unit is disabled. * Not indicated on the central controller and outdoor unit 7-segment. Com. cable between R/C and I/U connected properly? NO Correct communication cable. YES Failure of R/C transmitter → Replace R/C.…
-
[E04]
(New code) I/U - O/U communication error (detected by I/U) Does O/U work? YES NO Possible causes AImproper connector connection between I/U and O/U BImproper wire connection between I/U and O/U CFailure of I/U or O/U board DCase thermo sensor ON EInvalid I/U board switch setting Is group address set…
-
[E09]
(New code) Duplication of R/C header Are 2 headers set by double R/C? Possible causes R/C header setting is duplicated. YES Correct one header/one follower. (R/C address connector) NO Check R/C board. → Replace it if necessary. Check code Check code name [E18] (New code) Communication error between…
-
[F01]
(New code) I/U sensor TCJ error Is TCJ connector CN102 connected normally? Possible causes I/U sensor TCJ error NO Correct connector connection. YES Is TCJ resistor characteristic normal? NO Replace sensor TCJ. * See I/U temp. sensor characteristics-2. YES Check I/U main board. → Replace it if…
-
[F10]
(New code) I/U sensor TA error Is TA connector CN104 connected normally? Possible causes Sensor TA open or short-circuit NO Correct connector connection. YES Is TA resistor characteristic normal? NO Replace sensor TA. * See I/U temp. sensor characteristics-1. YES Check MCC-1510 board. Replace it if…
-
[F31]
(New code) O/U EEPROM error Is O/U free from power fluctuation? Possible causes AFailure of O/U power supply (voltage, noise, etc.) BFailure of O/U CDB board. Check power voltage. Improve power lines. Check external noise. NO YES Check CDB board. Check code [E08][L03][L07][L08] (New code/old code)…
-
[L20]
(New code) Duplication of central control address Are U3/U4 communication cables connected normally? Possible causes Central control address is duplicated. NO Correct cable connection. YES When a unit connected to U3/U4 is in a group, is it set to header unit? NO Set the connected unit to header…
-
[P12]
(New code) Malfunction of I/U fan motor Possible causes A Failure of fan motor connector B Failure of fan motor C Failure of I/U board D Failure of cross flow fan shaft Turn OFF the breaker. Turn it ON 10 seconds after. Does fan stop with operation OFF? NO YES NO Replace I/U fan motor. YES Start…
-
[P12]
(New code) Malfunction of I/U fan motor Possible causes A Failure of fan motor connector B Failure of fan motor C Failure of I/U board D Failure of cross flow fan shaft When AC cord is plugged in, I/U fan starts rotating. P. C. board Check the fan motor output DC voltage on the I/U board. Check…
-
[P31]
(New code) Other I/U errors (Group follower I/U error) Possible causes When an error occurs with other units in the group When header unit detects E03, L03, L07 or L08 during group operation, “P31” is indicated on follower units in the group and their operation stops. No code or alarm log is…
-
[C05], [C06]
(Central controller) TCC-LINK central control communication error Is I/U powered ON? Possible causes TCC-LINK central control communication error NO Power ON. YES Is harness from I/U terminal block connected properly? NO Correct connector connection. YES Can I/U be operated by R/C individually? NO…
-
Relationship Between Temperature Sensor Resistance and Temperature
-
9. HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT
Requirements When Replacing Service Board of Indoor Unit The non-volatile EEPROM (IC10) on the board of indoor unit stores important data such as model-specific type and capacity code (written during factory shipping) as well as system/indoor unit/group addresses set automatically/manually (written…
-
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)
*1 Reading EEPROM Data (Read EEPROM data that was updated at site in addition to factory setting.) , , and on the R/C simultaneously for 4 seconds or more. 1 (see page 52) 1) Press * In the group control mode, the header unit number is displayed first. is displayed, and the fan of the selected…
-
*3 Writing Setting Data in EEPROM
(The data of the EEPROM on the service board is the factory setting data.) , , and on the R/C simultaneously for 4 seconds or more. 1 (see page 52) 1) Press * In the group control mode, the header unit number is displayed first. is indicated.) (If auto address setting mode is canceled in 2-2) a) ii)…
-
HOW TO REPLACE SERVICE BOARD OF INDOOR UNIT (Continued)
Example of Setting Contents to be Written Down (Code Table) DN 01 Filter sign ON time 02 03 Item Memo Factory setting 0001: 150 hours Filter contamination level Central control address 0000: Average 0099: Not determined 06 HEAT intake temp. shift 0C PREPARING indication selection 0002: +2°C 0000…
-
10. ON-SITE SETTING AND OTHERS
11 1. Indoor Unit 1.1 Trial Operation Setting by Remote Controller only. The lamps on the unit blink during trial operation. <Wired remote controller> Press on the R/C for 4 seconds. When “TRIAL OPERATION” appears on the LCD, press . • “TRIAL OPERATION” appears on the LCD during trial operation. •…
-
1.2 Forcible Defrost Setting by Remote Controller (wired R/C only)
Preliminary operation 1 Press , , and at the same time for 4 seconds or more in the OFF mode. In the group control mode, the header unit number is displayed first. 2 Each pressing of indicates indoor unit number in the group sequentially. Choose the main indoor unit (connected to the outdoor unit)…
-
1.4 JRA Capacity Measurement Mode (wired R/C only)
Preliminary operation 1 Press , , and at the same time for 4 seconds or more in the OFF mode. In the group control mode, the header unit number is displayed first. 2 Each pressing of indicates indoor unit number in the group sequentially. Choose the main indoor unit (connected to the outdoor unit)…
-
Function Select Code (DN) Table
Factory setting Description 0001: 150H 0001: 150H 0003: 5000H 0005: Clogging sensor used DN 01 Item Filter sign ON time 02 Filter contamination level 0000: Average 0001: Heavy (half of standard time) 0000: Average 03 Central control address 0001: No. 1 0099: Not determined 0064: No. 64 0099: Not…
-
1.6 Wiring and Setting for Remote Controller
Double R/C control (when controlling by two remote controller switches) This control is provided to control one or more indoor units by two remote controllers. Up to 2 remote controllers can be installed. No setting is required when using in combination with a wireless remote controller .…
-
1.7 Monitoring Function of Remote Controller Switch
■ Calling indication of sensor temperature <Description> Calls the service monitor mode from the remote controller to monitor sensor temperatures of the remote controller, indoor units, and outdoor unit. <Procedure> 1 Press and on the R/C simultaneously for 4 seconds or more to call the service…
-
■ Calling error log
<Description> Calls past errors. <Procedure> 1 Press and on the R/C simultaneously for 4 seconds or more to call the service check mode. “Service check” lights up and code is displayed first to display the latest error. The faulty indoor unit number and error content are displayed. 2 To monitor…
-
<Group Control Operation>
Group control allows operation control of up to 8 indoor units using one remote controller. It includes twin, triple, and double twin controls with one outdoor unit. The indoor unit connected to outdoor unit controls room temperature according to the R/C setting. <An example of system> O/U I/U O/U…
-
Indoor Unit Power ON Sequence
Power ON <By power supply unit> • Indoor units that are not supplied with power are in waiting mode continuously. →System start resets the waiting mode. • Rebooted if power is supplied halfway <Auto address judgment> * Checking group configuration Incorrect Correct * Correct group configuration…
-
3. Connections for Central Control
3.1 Connections for TCC-LINK Central Control 3.1.1 Functions Connect an indoor unit to the TCC-LINK central controller. 3.1.2 Connection Diagram Indoor unit Central controller Terminal block (U3/U4) TCC-LINK CN40 CN41 Number of units : 64 Communication length : 2km Terminal block (A/B) Remote…
-
3.1.4 Wiring Specifications
Number of wires 2 Size Up to 1000m: 1.25mm2 stranded wires Up to 2000m: 2.0mm2 stranded wires Specification MVVS • A 2-wire non-polarity cable is used. • The cable length depends on each central control system. When used in a system including multiple air conditioners, the length includes the length…
-
3.1.5 Setting Onboard Switches
Setting of terminating resistors is necessary for central control of custom indoor units only. • Use SW01 to set terminating resistors. • Set terminating resistors for the indoor unit only with the smallest refrigerant line address. Central controller Central controller U1 U2 U3 U4 U1 U2 U3 U4…
-
3.1.6 Onboard Switch Setting Procedure
1. Detach the front panel. 2. Remove the drain guide, ground line, sensor TCJ, sensor TC, and motor leads. 3. Remove the screws to detach the electric parts box. Sensor TCJ insertion position (Insert the sensor drawn from above electric parts.) Sensor TC insertion position (Insert the sensor drawn…
-
ON-SITE SETTING AND OTHERS
3.1.7 Setting Addresses Overview To connect custom air conditioners to the TCC-LINK central control system for central control/monitoring, addresses of connected indoor units must be set in the following procedure. Connections/wiring completed System power ON Auto address setting Manual…
-
Manual setting/change of indoor unit refrigerant line addresses [In the case of 29 refrigerant systems or less (when multiple air conditioners are included, their number of refrigerant systems is also included)] Refrigerant address “1” is assigned to all indoor units except for group control by the…
-
ON-SITE SETTING AND OTHERS
(2) Manual setting/change of indoor unit refrigerant line addresses [In the case of 30 refrigerant systems or more (when multiple air conditioners are included, their number of refrigerant systems is also included)] Regarding refrigerant systems up to No. 29, manual setting/change is the same as…
-
3.1.8 Central Control Address Number Setting
To connect an indoor unit to the central control remote controller, an address number for central control must be set. An address number for central control is indicated as the refrigerant line number of the remote controller. 1. Setting by Remote Controller on Indoor Unit Side <Procedure> Perform…
-
11. ADDRESS SETTING
1. Address Setting Address Setting Procedure When twin or triple operation is selected with one indoor unit and one outdoor unit or when one outdoor is connected to each indoor unit even with multiple refrigerant systems in group operation, auto address setting is completed during the power on…
-
2. Address Setting and Group/Twin/Triple Control
<Definition of terms> Indoor unit No. Group address : N-n=O/U refrigerant line address N (30 max.) -I/U address n (64 max.) : 0=Individual (without group control) 1=Header unit under group control 2=Follower units under group control Header indoor unit (=1) : A representative unit of multiple indoor…
-
[2] Examples of Auto Address Setting from No Address Setting
-
3. Address Setting
When determining indoor unit addresses with wiring completed without piping construction (Manual setting by remote controller) <Address setting procedure> Connect a remote controller to the indoor unit whose address you want to set one to one. Turn ON the power. 1 Wiring example of 2 refrigerant…
-
ADDRESS SETTING (Continued)
■ Checking location of indoor unit number (1) To find the address of indoor unit whose location is clear In case of independent operation (1:1 connection of wired R/C and I/U) Perform the procedure during operation of indoor unit. <Procedure> 1 When the indoor unit is not working, press the R/C. on…
-
12. EXPLODED VIEWS AND PARTS LIST
High-Wall Type RAV-SM562KRT-E/RAV-SM802KRT-E Location No. Part No. 43T00409 43T09375 43T80306 43T80312 43T03010 43T03011 43T03012 43T09345 43T70001 43T21367 43T44373 213 43T44374 216 43T49021 Description FRONT PANEL ASSY GRILLE ASSY AIR FILTER (L) AIR FILTER (R) BODY; RIGHT BODY; LEFT HIDE; CLAW…
-
Location No. Part No. 43T60047 43160508 43T60321 43T50308 43T50306 43T69320 Description Location No. Part No. 43T60361 43T09343 43T69536 43T69500 43T09344 TERMINAL TERMINAL TERMINAL SENSOR HEAT EXCHANGER TEMPERATURE SENSOR TEMPERATURE SENSOR – 77 – Description FUSE E-PARTS BASE PC BOARD DISPLAY UNIT…
-