Полупромышленные кондиционеры Digital Inverter. Наружные блоки RAV-SM2244AT8-E, RAV-SM2804AT8-E, RAV-SM2244AT8Z-E, RAV-SM2804AT8Z-E, RAV-SM2244AT8ZG-E, RAV-SM2804AT8ZG-E, RAV-SM2244AT7, RAV-SM2804AT7, RAV-SM2244AT7Z, RAV-SM2804AT7Z, RAV-SM2244AT7ZG, RAV-SM2804AT7ZG. Инструкция по обслуживанию и ремонту.
Смотрите также: Инструкция по обслуживанию и ремонту →
Загружаем документ…
Текст инструкции
-
FILE NO. A09-004
-
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. [Explanation of indications]…
-
WARNING
Check earth wires. Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Do not modify the…
-
WARNING
Insulator check After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is…
-
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has…
-
4. Tools
1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional…
-
n Combination Pattern (Indoor Unit / Outdoor Unit)
-
1. SPECIFICATIONS
1-1. Indoor Unit 1-1-1. 4-Way Cassette Type <Twin type> Model Indoor unit 1 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E Indoor unit 2 RAV-SM 1104UT-E 1404UT-E 1104UT-E 1404UT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4…
-
1-1-2. Duct Type
<Twin type> Model Indoor unit 1 RAV-SM 1102BT-E 1402BT-E 1102BT-E 14002BT-E Indoor unit 2 RAV-SM 1102BT-E 1402BT-E 1102BT-E 1402BT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380…
-
1-1-3. Ceiling Type
<Twin type> Model Indoor unit 1 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E Indoor unit 2 RAV-SM 1102CT-E 1402CT-E 1102CT-E 1402CT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW) 22.4 27.0 22.4 27.0 Power supply 3 phase 380…
-
1-1-4. 4-Way Cassette Type
<Triple type> Indoor unit 1 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E Indoor unit 2 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E Indoor unit 3 RAV-SM 804UT-E 804UT-E 804UT-E 804UT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Model Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW)…
-
1-1-5. Duct Type
<Triple type> Indoor unit 1 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E Indoor unit 2 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E Indoor unit 3 RAV-SM 802BT-E 802BT-E 802BT-E 802BT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Model Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW)…
-
1-1-6. Ceiling Type
<Triple type> Indoor unit 1 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E Indoor unit 2 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E Indoor unit 3 RAV-SM 802CT-E 802CT-E 802CT-E 802CT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Model Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating capacity (kW)…
-
1-1-7. High Wall Type
<Triple type> Indoor unit 1 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E Indoor unit 2 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E Indoor unit 3 RAV-SM 802KRT-E 802KRT-E 802KRT-E 802KRT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Model Cooling capacity (kW) 20.0 23.0 20.0 23.0 Heating…
-
1-1-8. 4-Way Cassette Type
<Double twin type> Model Indoor unit 1 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Indoor unit 2 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Indoor unit 3 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Indoor unit 4 RAV-SM 564UT-E 804UT-E 564UT-E 804UT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling…
-
1-1-9. Compact 4-Way Cassette (600 × 600) Type
<Double twin type> Model Indoor unit 1 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 2 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 3 RAV-SM562MUT-E RAV-SM562MUT-E Indoor unit 4 RAV-SM562MUT-E RAV-SM562MUT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7 Cooling capacity (kW) 20.0 20.0 Heating capacity (kW)…
-
1-1-10. Slim Duct Type
<Double twin type> Model Indoor unit 1 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 2 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 3 RAV-SM564SDT-E RAV-SM564SDT-E Indoor unit 4 RAV-SM564SDT-E RAV-SM564SDT-E Outdoor unit RAV-SM2244AT8-E RAV-SM2244AT7 Cooling capacity (kW) 20.0 20.0 Heating capacity (kW)…
-
1-1-11. Duct Type
<Double twin type> Model Indoor unit 1 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Indoor unit 2 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Indoor unit 3 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Indoor unit 4 RAV-SM 562BT-E 802BT-E 562BT-E 802BT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling…
-
1-1-12. Ceiling Type
<Double twin type> Model Indoor unit 1 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E Indoor unit 2 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E Indoor unit 3 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E Indoor unit 4 RAV-SM 562CT-E 802CT-E 562CT-E 802CT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7 2804AT7 Cooling…
-
1-1-12. High Wall Type
<Double twin type> Model Indoor unit 1 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E Indoor unit 2 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E Indoor unit 3 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E Indoor unit 4 RAV-SM 562KRT-E 802KRT-E 562KRT-E 802KRT-E Outdoor unit RAV-SM 2244AT8-E 2804AT8-E 2244AT7…
-
1-2. Outdoor Unit
Model Outdoor unit RAV-SM 2804AT8-E 2244AT7 2804AT7 3 phase 380–415V 50Hz 3 phase 380V 60Hz (Power exclusive to outdoor is required.) Power supply Type Compressor 2244AT8-E Hermetic compressor Motor (kW) Pole Refrigerant charged (kg) Refrigerant control Hermetic compressor 3.75 3.75 3.75 3.75 5.9…
-
1-3. Operation Characteristic Curve
-
• Capacity variation ratio according to temperature
-
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Outdoor Unit – 27 –
-
RBC-DTWP101E (Simultaneous Double Twin)
-
RBC-TRP100E (Simultaneous Triple)
<Gas side> Header assembly 300 80 Inner diameter Ø15.9 80 100 Inner diameter Ø25.4 100 1 pc. <Liquid side> Branch pipe assembly Inner diameter Ø9.52 100 Inner diameter Ø12.7 100 1 pc. Insulator Gas side socket Liquid side socket Ø15.9 Outer diameter Ø25.4 Ø12.7 (External diameter) (External…
-
RBC-TWP101E (Simultaneous Twin)
-
3. OUTDOOR UNIT REFRIGERANTING CYCLE DIAGRAM
-
Systematic diagram of refrigerating cycle
RAV-SM2244 series Pressure (MPa) Cooling Heating Pipe surface temperature (°C) (kg/cm²g) Discharge Suction Indoor heat exchanger Compressor Outdoor heat drive revolution frequency exchanger (rps) (TE) ∗ Pd Ps Pd Ps (TD) (TS) (TC) Standard 3.14 0.88 32.0 9.0 Overload 3.54 1.14 36.1 11.6 Low load 1.65…
-
4. WIRING DIAGRAM
-
5. SPECIFICATIONS OF ELECTRICAL PARTS
-
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful…
-
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/4 6.4 0.80 0.80 3/8 9.5 0.80 0.80 1/2 12.7 0.80 0.80 5/8 15.9 1.00 1.00 1. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect…
-
c) Insertion of Flare Nut
d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a…
-
to 4 45˚ A B C 43˚ D to 4 5˚ Fig. 6-2-2 Relations between flare nut and flare seal surface 2. Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten…
-
6-3. Tools
6-3-1. Required Tools Refer to the “4. Tools” (Page 8) 6-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the…
-
1) Be sure to make setting so that liquid can be charged
2) When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment…
-
2. Characteristics required for flux
6-5-3. Brazing • Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy to remove slag after brazing. • The corrosive action to the treated metal and brazing filler is minimum. • It excels in coating…
-
Instruction of Works: The existing R22 and R407C piping can be reused for our digital inverter R410A products installations. WARNING Confirming the existence of scratches or dents on the existing pipes and confirming the reliability of the pipe strength are conventionally referred to the local site.…
-
6-6-5. Final Installation Checks
Is there no scratch or dent on the existing pipes? Existing pipe: NO * Use a new pipes. NO Is it possible to operate the existing air conditioner? YES ∗ After the existing air conditioner operated in cooling mode for approx. 30 minutes or longer*, recover the refrigerant. ∗ For cooling the pipes and…
-
6-6-6. Handling of Existing Pipe
When using the existing pipe, carefully check it for the following: • Wall thickness (within the specified range) • Scratches and dents • Water, oil, dirt, or dust in the pipe • Flare looseness and leakage from welds • Deterioration of copper pipe and heat insulator • Before recovering the…
-
7. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
7-1. Outdoor Unit Control 7-1-1. Print Circuit Board, MCC-1596 (Compressor IPDU) CN851 (Red) Connector for MCC-1597 (CN505) CN07 (Blue), CN08 (Blue) Terminal for reactor CH44 CN101 (White) Connector for MCC-1597 (CN502) CN03 (Black) Terminal for power relay F02 Electric circuit protective fuse…
-
7-1-2. Print Circuit Board, MCC-1597 (Fan Motor IPDU)
CN750 (White) Fan motor output (Upper side) CN504 (Blue) Connector for MCC-1599 (CN802) P501 (Black) Lead wire for grounding CN700 (Blue) Connector for MCC-1436 (CN03 or CN07) CN602 (Black) Connector for MCC-1600 (CN51) CN505 (Red) Connector for MCC-1596 (CN851) – 46 – CN500 (Red) Connector for…
-
7-1-3. Print Circuit Board, MCC-1599 (Interface (CDB))
CN708 (Blue) Connector for power relay coil CN702 (White) 2-way valve connector CN608 (White) Connector for MCC-1600 (CN50) CN02 (Red) Connector for MCC-1600 (CN10 and CN19) CN802 (White) Connector for MCC-1597 (CN504) F01 CN700 (Yellow) 4-way valve connector Power supply protective fuse (250V…
-
7-1-4. Print Circuit Board, MCC-1600 (Noise Filter)
CN05 (Red) Power supply terminal (L1) CN10 (Red) Terminal for MCC-1599 (CN02) and Terminal for PTC thermistor CN16 (Red) Terminal for power relay F01 Varistor protective fuse (250V, 6.3A) CN06 (White) Power supply terminal (L2) CN17 (White) Terminal for F02 Varistor protective fuse MCC-1596 (CN02)…
-
7-2. Outline of Main Controls
1. PMV (Pulse Motor Valve) control 1) The aperture of the PMV (1, 2) is controlled between 88 (44 + 44) to 1000 (500 + 500) pulses during operation. 2) During cooling and heating operations, the PMV aperture is controlled by the temperature difference between a detected temperature from a TS sensor…
-
3. Outdoor fan revolution number control
-
4. Defrost control
1) During heating operations, defrost operations are performed when the temperature from the TE sensor satisfies any of the conditions in the A to D zones. 2) During defrosting operations, defrost will be terminated if the temperature from the TE sensor continues at 12°C or higher for 3 seconds or…
-
7. Heat sink temperature detection control
1) IGBT overheating prevention is protective control performed by a thermistor (TH sensor) in proximity to IGBT. 2) When a temperature of TH ≥ 83°C is detected, the fan tap is moved by 1 step up. Thereafter step-up is performed at a rate of +1 tap/5 seconds until a maximum fan tap is reached. 3)…
-
12. SV2 valve control
The conditions for opening and closing the SV2 valve are shown in the table below. SV2 Valve “Open” Conditions SV2 Valve “Close” Conditions (1) When operation stopped after operating (2) When power placed “ON” (3) When 30 second elapses after first startup operation when power ON at TO ≤ 5° C When 8…
-
14. Coil heating control
1) This control has the function of heating the compressor by applying a current to the compressor when not operating instead using a case heater. This control is for the purpose of preventing stagnation of the refrigerant inside the compressor. 2) Malfunction in the compressor may result if a…
-
8. TROUBLESHOOTING
8-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The…
-
<Wireless remote controller type>
1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. • Is not 3-minutes…
-
8-2. Troubleshooting
8-2-1. Outline of judgment The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method. Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of the receiving part) The…
-
Lamp indication
Operation Timer Ready Check code F01 F02 Alternate flash P10 Cause of trouble occurrence Heat exchanger sensor (TCJ) error Heat exchanger sensor (TC) error Heat exchanger sensor (TA) error Indoor unit sensor error F04 F06 Operation Timer Ready F07 F08 Alternate flash F12 F13 Discharge…
-
8-2-2. Others (Other than Check Code)
Lamp indication Operation Timer Check code Cause of trouble occurrence Ready — During test run — Disagreement of cool/heat (Automatic cool/heat setting to automatic cool/heat prohibited model, or setting of heating to cooling-only model) Simultaneous flash Operation Timer Ready Alternate flash – 59…
-
8-2-3. Monitor Function of Remote Controller Switch
n Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller. <Procedure> 1 Push CL TEST + buttons simultaneously for 4 seconds to call the service monitor mode.…
-
8-2-4. Check Code List (Outdoor)
ALT (Alternate): Alternate flashing when there are two flashing LED Remote controller indication F04 Sensor lamp part Block indication Operation Timer Ready Flash ALT ¥ ¥ ¡ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¡ L29 ¥ P03 E01 ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ E02 ¥ F06 F08 F07 F12 F13 F15 F31 H01 H02 H03 H04 H06 L10 – 61…
-
ALT (Alternate): Alternate flashing when there are two flashing LED
Remote controller indication F01 F02 F10 F29 P01 P10 P12 P31 — Sensor lamp part Block indication Operation Timer Ready Flash ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ SIM ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ l l l — l By unit with warning No. — L20 l l l l ALT — ¥ ¡ — Representative defective position Detection Indoor…
-
Error mode detected by indoor unit
Operation of diagnostic function Check code Cause of operation E03 No communication from remote controller (including wireless) and communication adapter E04 The serial signal is not output from outdoor unit to indoor unit. • Miswiring of inter-unit wire • Defective serial sending circuit on outdoor…
-
Error mode detected by outdoor unit
The check code has been ramified from 4 series and after. The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after. (Ex. Combination of RAV-SM1404UT-E with RAV-SM2804AT8-E) When the indoor unit is 3 series and before, the conventional check code…
-
Check code
Indoor unit before 3 series Cause of operation after 4 series Status of air conditioner Condition H03 Current detection circuit error Stop Displayed when error is detected P05 Open phase of 3-phase power supply Stop Displayed when error is detected H03 Judgment and measures 1. Check outdoor P.C.…
-
Error mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function Check code Cause of operation Status of air conditioner Judgment and measures Condition — Power supply error of remote controller, Indoor EEPROM error 1. Check remote controller inter-unit wiring. 2. Check remote controller. 3. Check indoor power wiring. 4. Check…
-
8-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)
1) This section describes the diagnostic method for each check code displayed on the remote controller. 2) In some cases, a check code indicates multiple symptoms. In this case, confirm LED display on the outdoor P.C. board to narrow the contents to be confirmed. 3) The check code on the remote…
-
Outdoor
LED display [F04] <Display 1> <Display 2> ¡ ¡ l l ¡ ¡ [Discharge temp. sensor (TD) error] ¡ l l ¥ l l [F06] NO Is CN603 connection normal? Is resistance value of TD sensor normal? Correct connector. Sensor error → Replace YES Check outdoor P.C. board (MCC-1599). Defect → Replace • There is a…
-
Outdoor
LED display [F08] <Display 1> <Display 2> ¡ ¡ l l ¡ ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Outside air temp. sensor (TO) error] ¡ l ¥ l l l Is CN602 connection normal? Is resistance value of TO sensor normal? NO Correct connector. Sensor error →…
-
Outdoor
LED display [F23] <Display 1> <Display 2> ¡ ¡ ¡ ¥ ¡ ¡ ¥ ¥ ¥ l l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [PS sensor error] Is connector of Ps sensor correctly connected? YES Correct connection of connector. Connector: CN606, White Are the output…
-
Outdoor
LED display [H02] <Display 1> <Display 2> ¡ ¡ l ¡ l l ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Compressor lock] l l l Is power supply voltage normal? AC342 to 457V l Is wire connection normal? Compressor lead (Board side, Compressor side), Reactor…
-
Outdoor
LED display [H06] <Display 1> <Display 2> ¡ ¡ ¡ ¡ ¥ ¥ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Low pressure protective operation] l l l l l Are gas pipe, liquid pipe and service valve of the outdoor unit fully opened? NO Open the service valve fully.…
-
Outdoor
LED display Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) ∗ There is a possibility that it is one of the following errors. Confirm LED on outdoor P.C. board to judge which error it is. Communication error between MCU, Heat sing temp. sensor (TH) error…
-
Outdoor
LED display [P03] <Display 1> <Display 2> ¡ ¡ ¡ ¡ ¡ ¡ ¥ ¥ l l l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Discharge temp. error] Is there no gas leak? Is refrigerant charge amount adequate? NO Repair defective position. Recharge refrigerant. NO…
-
Outdoor
LED display Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [P04] C Heating operation Does the heating indoor fan normally operate? NO Are connections of connectors,capacitors and fan motor normal? YES NO YES Is there any element which blocks indoor heat…
-
Outdoor
LED display [P05] <Display 1> <Display 2> ¡ ¡ ¡ ¡ ¡ ¡ ¥ l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Power supply error (Voltage error)] l l Is there no open phase of the power supply? l Is there no down or up of power supply voltage? (AC342 to 457V) ¥…
-
Outdoor
LED display [P20] <Display 1> <Display 2> ¡ ¡ ¡ ¥ ¡ ¡ ¡ ¥ l l l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [High pressure protective operation] NO Is valve fully opened? Open valve fully. YES Reset the power supply and then perform test run matching to…
-
Outdoor
LED display [P22] <Display 1> <Display 2> ¡ ¡ ¡ ¥ ¡ ¡ ¡ ¥ ¥ l l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Fan system error] NO Is there no problem on power supply voltage? (342 to 457V) Check wiring construction. Ask repair of power supply. YES Does…
-
Temperature sensor
Temperature – Resistance value characteristic table TD, TL sensors TA, TC, TCJ, TE, TS, TO sensors Representative value Representative value Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard value) (Maximum value) Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard…
-
9. SETUP AT LOCAL SITE AND OTHERS
9-1. Calling of Error History <Contents> The error contents in the past can be called. <Procedure> 1 Push TEMP. SET ON / OFF TEST + buttons simultaneously for 4 seconds or more to call the service check mode. Service Check goes on, the CODE No. 01 is displayed, and then the content of the latest…
-
n Indoor unit power-ON sequence
Power ON • The unit without power feed waits entirely → Waiting status is released by system start • Reboot when power is fed on the way <By feed unit> <Automatic address judgment> Not normal NO 3 minutes elapse Gr construction check YES Normal ∗ Gr normal 1) There is no duplicated indoor unit…
-
9-3. Outdoor Unit
9-3-1. Various Setting on Outdoor Unit (Existing piping, Power save, Cooling-only, etc.) The following settings are available by DIP switch setup and jumper line setup. Function Set position Existing piping setup Turn the switch to ON when Ø19.1 is used for the existing pipe. In this case, the…
-
9-3-2. Service Support Function (LED Display, Switch Operation)
1. Outline A various setup and operation check can be performed by DIP switches at 3 positions (SW802, SW803, SW804) and the pushdown button switches (SW800, SW801) at 2 positions. Operation part Part No. Specifications SW800 Pushdown button switch SW803 DIP switch SW801 Pushdown button switch SW804…
-
9-3-3. Others
1. Selection of LED display (SW800, SW803 operation) 1) Display selection list The displayed contents of LED D800 to D804 on the outdoor control P.C. board can be exchanged by operation of SW803. Switch Function / Contents SW803 ON SW803 TD SW803 TS SW803 TA SW803 ON Current display The current…
-
2) Error display
The error which is generating at present and the latest error (Latest error information including present) can be confirmed by lighting LED D800 toD804 on the outdoor control P.C. board. a) When all DIP switch SW803 are OFF, the status of error which is generating at present is displayed. b) <1>…
-
3) Sensor, current, compressor operation frequency, PMV opening display
-
4) Specific operation for maintenance check (SW801, SW804)
The following specific operations for the maintenance check are performed by operation of SW801 or SW804. a) Select DIP switch SW804. (See table below) b) Push the pushdown button switch SW801 for approx. 1 second. c) The following functions start. While each function starts, LED D805 (Green)…
-
SW804
4 4-way valve relay operation (For RY700, CN70 check) Turn on 4-way valve power relay (RY700). When pushing SW801 again or when 2 minutes elapsed, the operation returns to the normal control. 4 SV valve relay operation (For RY702, CN702 check) Turn on SV valve relay (RY702). When pushing SW801 again…
-
10. ADDRESS SETUP
10-1. Address Setup Procedure When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.…
-
10-2. Address Setup & Group Control
<Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group…
-
10-2-2. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit) 1) Single 1-1 Individual (Master/Sub) 2) Group operation (Twin, Triple operation) (Multiple outdoor units = Miltiple indoor units only with serial communication) 2-1 Sub/Header 1-1 Sub/Header 1-2 Sub/Follower 3-1 Master/Header 3-2 Sub/Follower 3-3 Sub/Follower Only…
-
10-2-3. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit) 1) Single 2) Twin 3) Triple (1-1) 1-2 Master/Header 1-1 Individual (1-1) (1-2) 1-2 Sub/Header 1-1 Sub/Follower (1-2) (1-3) 1-3 Master/Follower 1-1 Sub/Follower (Master/Header) Only turning on source power supply (Automatic completion) 2. Group operation (Multiple…
-
10-3. Remote Controller Wiring
• Strip off approx. 9 mm the wire to be connected. • For single system, use non polarity, 2 core wire is used for wiring of the remote controller. (0.5 mm² to 2.0 mm² wires) • For the synchronous twin, triple system, use 2-conre shield wire (Vinyl cord for microphone 0.5 to 2.0 mm²) to conform to…
-
10-4. Address Setup (Manual setting from remote controller)
In case that addresses of the indoor units will be determined prior to piping work after cabling work • Set an indoor unit per a remote controller. • Turn on power supply. (Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe) Outdoor Outdoor Indoor Indoor Indoor Indoor A B…
-
10-5. Confirmation of Indoor Unit No. Position
1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure> 1 Push 2 Push ON / OFF UNIT LOUVER button if the unit stops. button.…
-
<Maintenance/Check list>
Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner. It is also recommended to maintain the units once a year regularly when operating…
-
2 SAFETY PRECAUTIONS
• • • • • • Ensure that all Local, National and International regulations are satisfied. Read these “SAFETY PRECAUTIONS” carefully before installation. The precautions described below include important items regarding safety. Observe them without fail. After the installation work, perform a trial…
-
Required Tools/Equipment and Precautions for Use
Prepare the tools and equipment listed in the following table before starting the installation work. Newly prepared tools and equipment must be used exclusively. 4 INSTALLATION CONDITIONS Before installation Legend Earthing Be sure to prepare to the following items before installation. WARNING…
-
Necessary Space for Installation
(Unit: mm) CAUTION Do not install the outdoor unit in a location that is subject to combustible gas leaks. Accumulation of combustible gas around the outdoor unit may cause a fire. 500 mm Above unit is free 1. Single unit installation Obstacle at rear side Upper side is free 1. Single unit…
-
Serial installation in front and rear
NO GOOD Open above and to the right and left of the unit. The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit. Do not support the outdoor unit only with the fixing leg. If only the end of the fixing leg is supported, it may deform. 5…
-
Connecting the Gas Side Pipe
Flaring 1. Cut the pipe with a pipe cutter. Be sure to remove burrs that may cause a gas leak. 2. Insert a flare nut into the pipe, and then flare the pipe. Use the flare nuts supplied with the air conditioner or those for R410A. Insert a flare nut into the pipe, and flare the pipe. As the flaring…
-
6 AIR PURGING
Refrigerant Pipe Length Simultaneous twin, triple Outdoor unit SM2244 SM2804 Outdoor unit SM2244 SM2804 Allowable pipe length (m) Branch piping Branch piping • 2 • 3– 2 • 3 • 4– 2 • 4 • 4– 3 Maximum Maximum Total length • 1+ 2 • 1+ 3 • 1+ 4 Maximum 70 70 Indoor unit: Upper Outdoor unit: Upper…
-
How to Open the Valve
Insulating the Pipes Open or close the valve. • Liquid side Open the valve with a 4 mm hexagon wrench. • Gas side • Valve unit • • Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open) Charge port Adding additional refrigerant The temperatures at both…
-
7 ELECTRICAL WORK
• WARNING 1. Using the specified wires, ensure that the wires are connected, and fix wires securely so that the external tension to the wires does not affect the connecting part of the terminals. Incomplete connection or fixation may cause a fire, etc. 2. Be sure to connect the earth wire (grounding…
-
Stripping length power cord and connecting wire
Indoor/outdoor connecting wire Power supply wire Earth screw Earth screw L1 L2 L3 10 After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, cover them with finishing tape and clamp them to the wall with off-the-shelf support brackets or their equivalent. Keep the power…
-
13 FUNCTIONS TO BE IMPLEMENTED LOCALLY
14 TROUBLESHOOTING • • • • Do not reuse a flare nut to prevent gas leaks. Replace it with the supplied flare nut and then process it to a flare. Blow nitrogen gas or use an appropriate means to keep the inside of the pipe clean. If discolored oil or much residue is discharged, wash the pipe. Check…
-
Display mode 1
Cause Display mode 2 15 APPENDIX D800 D801 D802 D803 D804 D800 D801 D802 D803 D804 1 Normal Work instructions 2 Discharge (TD) sensor error 3 Heat exchanger (TE) sensor error The existing R22 and R407C piping can be reused for our digital inverter R410A product installations. 4 Heat exchanger (TL)…
-
Are there scratches or dents on the existing pipes?
YES Existing pipes: Cannot be used. • Use new pipes. NO Is it possible to operate the existing air conditioner? NO YES • After the existing air conditioner is operated in cooling mode for approx. 30 minutes or longer,* recover the refrigerant. • For cleaning the pipes and recovering oil •…
-
1. Setting the jumper wires and DIP switches Part name Setting Function J800 to J803 Model switching Cut these jumper wires according to the following table. J804 to J811 Settings Set these jumper wires to the settings of the P.C. board before replacement SW802 Settings Set SW802 to the setting of…
-
13. HOW TO EXCHANGE COMPRESSOR
13-1. Exchanging Procedure of Compressor (Outline) START Has refrigerant recovery work been done? NO Open PMV forcedly and then recover refrigerant using a refrigerant recovery unit. YES Turn off the leakage breaker. Remove the defective compressor. Mount a service compressor. Never recover the…
-
14. DETACHMENTS
14-1. Outdoor Unit RAV-SM224, RAV-SM280 series No. Part name Procedure 1 Common procedure WARNING Remarks Service panel Stop operation of the air conditioner and turn off breaker switch. CAUTION Ensure wearing of gloves when performing any work in order to avoid injury from parts, etc. 1. Detachment…
-
Discharge port cabinet Remarks Procedure 1. Detachment 1) Carry out the operation in 1. of Q and 1. of R above. 2) Remove the screws fixing the inverter assembly, the discharge port cabinet and the partition board. (ST1T Ø4 × 8, 4 pcs.) 3) Remove the screws for the discharge port cabinet and the…
-
Side cabinet Remarks Procedure 1. Detachment 1) Carry out the operation in 1. of Q and 1. of R above. 2) Remove the screws fixing the inverter assembly and the side cabinet. (ST1T Ø4 × 10, 3 pcs.) 3) Remove the screws for the side cabinet and the valve fixing plate. (ST1T Ø4 × 10, 2 pcs.) 4) Remove…
-
Inverter assembly Remarks Procedure 1. Detachment 1) Carry out the operation in 1. of Q, 1. of R and 1. of T above. 2) Remove the connectors connected to the fan motor relay board and the Fan IPDU board, the connector connected to other components from the control board (Interface board). CN600 : TS…
-
Interface board (Control board) MCC-1599 Procedure Remarks 1. Detachment 1) Carry out the operation in 1. of Q, 1. of R and 1. of T above. 2) Remove lead wires and connectors to other components from the interface board (control board). CN603 : TD sensor (3P: White, tube: Red) CN602 : TO sensor (2P…
-
Fan-IPDU board MCC-1597 Procedure Remarks 1. Detachment FAN-IPDU board 1) Carry out the operation in 1. of Q, 1. of R and 1. of T above. 2) Remove lead wires and connectors to other components from the Fan-IPDU board. CN700 : Relay connector (3P, Blue) CN750 : Outdoor fan motor (3P, White) CN500…
-
Noise filter board MCC-1600 Remarks Procedure 1. Detachment 1) Perform the operation in 1. of Q, 1. of R, 1. of T, 1.-2 of V and 1.-2 of W. 2) Remove the screws (4 positions) fixing the inverter assembly (front) to remove the lead wires from the upper left clamp. Then slide the inverter assembly…
-
Compressor IPDU board MCC-1596 Procedure Remarks 1. Detachment 1) Carry out the operation in 1. of Q, 1. of R, 1. of T, 1. of V, 1. of W and 1. of X. 2) Pull the compressor lead from the space in the partition plate. 3) Remove the screw (1 position) fixing the discharge port cabinet and the screws…
-
Fan motor Procedure Remarks 1. Detachment 1) Carry out the operation in 1. of Q , 1. of R and 1. of S above. 2) Remove the flange nut fixing the fan motor and the propeller fan. • The flange nut is loosened by turning to the right. (When tightening, turn it to the left) 3) Remove the propeller fan.…
-
Compressor Procedure Remarks 1. Detachment 1) Recover the refrigerant gas. 2) Carry out the operation in 1. of Q and T above. 3) Remove the piping panel (front). Remove the piping panel (front) and screws of the bottom plate. (Hexagonal screw Ø4 × 10, 2 pcs.) Remove screw of the piping panel (front)…
-
Compressor (continued) Procedure Remarks 2. Attachment 1) Mount the compressor by reversing the procedure for removal. CAUTION The fixing torque for the hexagonal bolts fixing the compressor is 19.6N•m (200kgf•cm). 3. Vacuuming 1) Connect the vacuum pump to the charge port and the high-pressure…
-
Fan guard Remarks Procedure 1. Detachment 1) Carry out work of item 1. of Q and 1. of S above. Remover screw (2 pcs.) CAUTION To prevent scratches to the product, carry out the work on cardboard, cloth, etc. 2) Remove the discharge port cabinet and place the fan guard side facing upwards. 3) Remove…
-
15. EXPLODED VIEWS AND PARTS LIST
-
Part No
Description 43120224 43122065 43191651 43100323 43050407 43151301 4312C037 4316V135 43146680 43146725 43146700 37546847 43146722 43146698 43146734 43148208 43148209 43100345 43111337 43122095 43122105 4314G187 4314G188 4314G189 4314G191 4314G192 4314G193 4301P703 4301P729 43146676 43119390 43100347…
-
15-2. Inverter Assembly
-
Model name
-
15-3. Outdoor Unit
-
Part No
Description 43120224 43122065 43191651 43100323 43050407 43151301 4312C037 4316V135 43146680 43146725 43146700 43146716 43146706 43146698 43146734 43148208 43148209 43100345 43111337 43122095 43122105 4314G187 4314G188 4314G189 4314G191 4314G192 4314G193 4301P703 4301P729 43146676 43119390 43100347…
-
15-4. Inverter Assembly
-
Model name
-
WARNINGS ON REFRIGERANT LEAKAGE
Important Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity…
-