Инструкция на Полупромышленные кондиционеры Digital Inverter
Полупромышленные кондиционеры Digital Inverter . Кассетные блоки RAV-SM564UT-E ... RAV-SM1604UT-E. Инструкция по обслуживанию и ремонту.
Смотрите также: Инструкция по обслуживанию и ремонту →
Загружаем документ…
Текст инструкции
-
FILE NO. A07-003
-
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them. [Explanation of indications]…
-
WARNING
Check earth wires. Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs. If the earth wire is not correctly connected, contact an electric engineer for rework. Do not modify the…
-
WARNING
Insulator check Ventilation After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric…
-
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to New Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has…
-
4. Tools
1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional…
-
1. SPECIFICATIONS
1-1. Indoor Unit 1-1-1. 4-Way Air Discharge Cassette Type <Single type> Indoor unit RAV-SM 564UT-E 804UT-E 1104UT-E Outdoor unit RAV-SP 562AT(Z)(ZG)-E 802AT(Z)(ZG)-E 1404UT-E Model 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E Cooling capacity (kW) 5.3 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power…
-
Indoor unit
-
Indoor unit 1
RAV- SM564UT-E SM804UT-E Indoor unit 2 RAV- SM564UT-E SM804UT-E Outdoor unit RAV- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0 Model Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics (A)…
-
таблицы и схемы — в просмотре
-
1-1-2. Concealed Duct Type
<Single type> Model Indoor unit RAV-SM 562BT-E 802BT-E Outdoor unit RAV-SP 1102BT-E 1402BT-E 562AT(Z)(ZG)-E 802AT(Z)(ZG)-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics…
-
Indoor unit 1
RAV- SM562BT-E SM802BT-E Indoor unit 2 RAV- SM562BT-E SM802BT-E Outdoor unit RAV- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0 Model Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics (A)…
-
1-1-3. Under Ceiling Type
<Single type> Indoor unit RAV-SM 562CT-E 802CT-E 1102CT-E Outdoor unit RAV-SP 562AT(Z)(ZG)-E 802AT(Z)(ZG)-E 1402CT-E Model 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E Cooling capacity (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A)…
-
Indoor unit 1
RAV- SM562CT-E SM802CT-E Indoor unit 2 RAV- SM562CT-E SM802CT-E Outdoor unit RAV- SP1104AT(Z)(ZG)-E SP1404A(Z)(ZG)-E Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0 Model Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics (A)…
-
1-1-4. High Wall Type
<Single type> Indoor unit RAV- SM562KRT-E SM802KRT-E Outdoor unit RAV- SP562AT(Z)(ZG)-E SP802AT(Z)(ZG)-E Cooling capacity (kW) 5.0 6.9 Heating capacity (kW) 5.6 8.0 Model Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 8.33 – 7.63 13.15 – 12.05 Power consumption (kW) 1.39 2.4 Power…
-
Indoor unit 1
RAV- SM562KRT-E SM802KRT-E Indoor unit 2 RAV- SM562KRT-E SM802KRT-E Outdoor unit RAV- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E Cooling capacity (kW) 10.0 12.3 Heating capacity (kW) 11.2 14.0 Model Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics…
-
1-1-5. Compact 4-Way Cassette (600 × 600) Type
<Single type> Indoor unit RAV-SM562MUT-E Outdoor unit RAV-SP562AT(Z)(ZG)-E Model Cooling capacity (kW) 5.0 Heating capacity (kW) 5.6 Power supply 1 phase 230V (220 – 240V) 50Hz Running current (A) 6.6 – 7.15 Power consumption (kW) 1.53 Power factor (%) 97 Cooling Electrical characteristics EER 3.27…
-
Indoor unit 1
RAV- SM562MUT-E Indoor unit 2 RAV- SM562MUT-E Outdoor unit RAV- SP1104AT(Z)(ZG)-E Cooling capacity (kW) 10.0 Heating capacity (kW) 11.2 Model Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics (A) 12.51 – 11.47 Power consumption (kW) 2.67 Power…
-
1-1-6. Slim Duct Type
<Single type> Model Indoor unit RAV-SM 404SDT-E 454SDT-E 564SDT-E Outdoor unit RAV-SP 404AT(Z)(ZG)-E 454AT(Z)(ZG)-E 562AT(Z)(ZG)-E 4.0 5.0 4.5 5.6 Cooling capacity (kW) 3.6 Heating capacity (kW) 4.0 Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling (A) 5.20 – 4.77 5.87 – 5.38 7.26…
-
Model
Indoor unit RAV-SM 564SDT-E Outdoor unit RAV-SM 563AT-E Cooling capacity (kW) 5.0 Heating capacity (kW) 5.6 Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling (A) 7.94 – 7.28 Power consumption (kW) 1.66 Power factor (%) 95 EER Electrical characteristics Energy efficiency class ∗ B…
-
Model
Indoor unit 1 RAV-SM 564SDT-E 564SDT-E Indoor unit 2 RAV-SM 564SDT-E 564SDT-E Outdoor unit RAV-SP 1104AT(Z)(ZG)-E 1102AT(Z)(ZG)-E Cooling capacity (kW) 10.0 10.0 Heating capacity (kW) 11.2 11.2 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics…
-
Model
Indoor unit 1 RAV-SM 564SDT-E Indoor unit 2 RAV-SM 564SDT-E Outdoor unit RAV-SM 1103AT-E Cooling capacity (kW) 10.0 Heating capacity (kW) 11.2 Indoor unit Power supply 1 phase 230V (220 – 240V) 50Hz Running current Cooling Electrical characteristics (A) 16.47 – 15.09 Power consumption (kW) 3.55…
-
1-2. Outdoor Unit
-
Model name
Outdoor unit RAV-SP 404AT(Z)(ZG)-E 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.) Power supply Type Compressor Hermetic compressor Motor (kW) Pole Refrigerant charged (kg) 1.1 1.1 4 4 1.0 1.0 Refrigerant control Inter connecting pipe Pulse motor valve Standard length (m)…
-
1-3. Operation Characteristic Curve
-
• Capacity variation ratio according to temperature
-
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Indoor Unit RAV-SM564UT-E 15 or more 1000 or more An obstacle 1000 or more 15 or more 860 to 910 Ceiling open dimension 1000 or more 860 to 910 Ceiling open dimension Standing 661 or less The space that is necessary for equipping and service Refrigerant pipe connecting port Ø6.4 (Liquid side)…
-
15 or more 1000 or more An obstacle 1000 or more 15 or more 860 to 910 Ceiling open dimension 1000 or more 860 to 910 Ceiling open dimension Standing 661 or less The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling 105 397.5 263 157 106.5 72 241.5…
-
15 or more 1000 or more An obstacle 1000 or more 15 or more 860 to 910 Ceiling open dimension 1000 or more 860 to 910 Ceiling open dimension Standing 661 or less The space that is necessary for equipping and service Take-in port of wiring Bottom face of ceiling 30 Refrigerant pipe connecting port…
-
21 803 (inside) 21 Refrigerant piping 103 Air filter 4-Ø4 (inside) Ø9 Fresh air inlet (knock-out hole) Drain-up port Hung-up plate – 32 –
-
2 Power supply inlet hole Ø38 Kockout hole A legs Air outlet 70 383 port 17.5 Note Name Refrigerant piping hole Indoor/Outdoor unit connecting wire inlet hole Mounting bolt hole (Ø12 × 17 long hole) Drain hole (Ø25) B legs 46 128 17.5 365 Air inlet port 60 Mounting bolt hole (Ø12 × 17 U-shape hole)…
-
Drain hole (2-Ø20 × 88 long hole) Drain hole (Ø25) 600 90 A legs 54 306 Ø6 hole pitch 290 Connecting pipe port (Gas flare side: Ø12.7) Connecting pipe port (Liquid flare side: Ø6.4) 30 8-Ø6 hole (For fixing outdoor unit) 20 320 (Long hole pitch For anchor bolt) 2-Ø11-14 U-shape hole (For Ø8-Ø10…
-
RAV-TWP30E2, RAV-TWP50E2 (Simultaneous Twin)
-
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Indoor Unit • Single type (Combination of 1 indoor unit and 1 outdoor unit) (Indoor unit) Distributor (Strainer incorporated) TCJ sensor Strainer Air heat exchanger TC sensor Heating Cooling Refrigerant pipe at liquid side (Outer dia : ØB) Refrigerant pipe at gas side (Outer dia : ØA) To…
-
3-2. Outdoor Unit
RAV-SP1104AT-E, SP1104ATZ-E, SP1104ATZG-E, RAV-SP1404AT-E, SP1404ATZ-E, SP1404ATZG-E TO sensor TS sensor PMV TL sensor Strainer TE sensor Check joint Capillary Ø4 ר3 (6 pcs.) Cooling: High pressure Heating: Low pressure Heat exchanger Ø8, 2 rows, 52 stages FP1.45, flat fin TD sensor Distributor…
-
Packed valve Outer dia. ØA Packed valve Outer dia. ØB TO sensor PMV (Pulse Motor Valve) (CAM-B30YGTF-2) TS sensor 2-step muffler Ø19.05 × 200L TD sensor Strainer 4-way valve (STF-0108Z) TE sensor Heat exchanger Ø8 ripple, 2 rows, 14 steps FP1.3 flat fin Muffler Ø19 × L160 Rotary compressor…
-
4. FAN CHARACTERISTICS
4-1. Slim Duct (Filter Attached) RAV-SM404SDT-E, RAV-SM454SDT-E Standard air volume : 690m³/h 60 High (50Pa) Upper limit of external static pressure(50Pa) 50 High (35Pa) External static pressure(Pa) Upper limit of external static pressure(35Pa) Lower limit of external static pressure (50Pa) 40 Lower…
-
5. WIRING DIAGRAM
-
5-1-2. Slim Duct Type
RAV-SM404SDT-E, RAV-SM454SDT-E, RAV-SM564SDT-E FM DM FS CN333 (WHI) CN504 (WHI) CN34 (RED) CN510 (WHI) Motor drive circuit CN334 (WHI) CN104 (YEL) CN102 (RED) CN101 (BLK) TA TCJ RED WHI BLK Fuse, F01 T6.3A, 250V~ BLK 1 2 CN67 (BLK) ~ + ~ – Fuse, F02 T3.15A, 250V~ TC DC20V DC15V DC12V DC7V Power…
-
5-2. Outdoor Unit
RAV-SP1104AT-E, SP1104ATZ-E, 1104ATZG-E RAV-SP1404AT-E, SP1404ATZ-E, 1404ATZG-E CM Reactor Reactor (GRY) (GRY) (WHI) P04 P05 FM01 CN400 (WHI) FM02 CN300 (WHI) CN609 (BLU) CN610 (YEL) TL CN604 (WHI) TD CN603 (WHI) TO CN602 (YEL) TE CN601 (WHI) TS CN600 (WHI) 49C (RED) U (WHI) P06 P07 (WHI) V (BLK) W…
-
49C
2 2 ORN 1 1 ORN Compressor CN300 P04 P05 P06 Q200~205 IGBT P.C. Board (MCC-5009) R221 P25 P24 P23 R220 R320 YEL R219 R319 BRN P22 P21 YEL P20 P35 F03 Fuse T3.15A AC250V C13 Varistor L01 DB01 CN603 CN602 Power relay DB02 Relay P08 PUR P30 BLK Coil for 4-WAY VALVE SW802 Reactor MCC-1530 Sub P.C. Board…
-
6. SPECIFICATIONS OF ELECTRICAL PARTS
-
6-2. Outdoor Unit (Parts Ratings)
-
7. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer. The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful…
-
Table 7-2-1 Thicknesses of annealed copper pipes
Thickness (mm) Nominal diameter Outer diameter (mm) R410A R22 1/4 6.4 0.80 0.80 3/8 9.5 0.80 0.80 1/2 12.7 0.80 0.80 5/8 15.9 1.00 1.00 1. Joints For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints Flare joints used to connect…
-
c) Insertion of Flare Nut
d) Flare Processing Make certain that a clamp bar and copper pipe have been cleaned. By means of the clamp bar, perform the flare processing correctly. Use either a flare tool for R410A or conventional flare tool. Flare processing dimensions differ according to the type of flare tool. When using a…
-
to 4 45˚ B A C 43˚ D to 4 5˚ Fig. 7-2-2 Relations between flare nut and flare seal surface 2. Flare Connecting Procedures and Precautions a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten…
-
7-3. Tools
7-3-1. Required Tools Refer to the “4. Tools” (Page 8) 7-4. Recharging of Refrigerant When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps. Recover the refrigerant, and check no refrigerant remains in the equipment. When the…
-
1) Be sure to make setting so that liquid can be charged
2) When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down. It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment…
-
2. Characteristics required for flux
7-5-3. Brazing • Activated temperature of flux coincides with the brazing temperature. • Due to a wide effective temperature range, flux is hard to carbonize. • It is easy to remove slag after brazing. • The corrosive action to the treated metal and brazing filler is minimum. • It excels in coating…
-
Instruction of Works: The existing R22 and R407C piping can be reused for our digital inverter R410A products installations. NOTE) Confirmation of existence of scratch or dent of the former pipes to be applied and also confirmation of reliability of the pipe strength are conventionally referred to…
-
7-6-5. Final Installation Checks
Is there no scratch or dent on the existing pipes? Existing pipe: NO * Use a new pipes. NO Is it possible to operate the existing air conditioner? YES ∗ After the existing air conditioner operated in cooling mode for approx. 30 minutes or longer*, recover the refrigerant. ∗ For cooling the pipes and…
-
7-6-6. Handling of Existing Pipe
RAV-SP1104AT-E, RAV-SP1404AT-E • To use an existing Ø19.1 mm pipe, set bit 3 of SW802 (switch for existing pipe) on the P.C. board of the outdoor unit to ON. In this case, the heating performance may be reduced depending on the outside air temperature and room temperature. When using the existing…
-
7-6-7. Recovery Method of Refrigerant
RAV-SP1104AT-E, RAV-SP1404AT-E RAV-SM1603AT-E • Use the refrigerant recovery switch SW801 on the P.C. board of the outdoor unit to recover refrigerant when the indoor unit or outdoor unit is moved. • Use the refrigerant recovery switch SW802 on the P.C. board of the outdoor unit to recover…
-
7-6-8. Recovery method of refrigerant for
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E • When recovering refrigerant in case of reinstallation of the indoor or outdoor unit, etc., use the refrigerant recovery switch on the terminal block of the outdoor unit. Refrigerant recovery switch ON…
-
8. INDOOR CONTROL CIRCUIT
8-1. Indoor Controller Block Diagram 8-1-1. Connection of Main (Sub) Remote Controller Main (sub) master remote controller (Max. 2 units) Display LCD Display LED Weekly timer Function setup MCU Display LCD LCD driver Key switch Function setup CN2 MCU CN1 Key switch DC5V Remote controller…
-
8-1-2. Connection of Wireless Remote Controller Kit
Indoor unit #1 (Master) Wireless remote controller kit Receiver P.C. board (MCC-1504) Display LED Receive circuit Function setup SW Buzzer Grille up/down SW MCU DC5V Power circuit Remote controller communication circuit A Temporary operation SW #2 (Follower) A B #3 (Follower) B A B Indoor control…
-
8-1-3. Connection of Both Main (Sub) Remote Controller and Wireless Remote Controller Kit
Indoor unit #1 (Master) Main (sub) master remote controller (Max. 2 units) Wireless remote controller kit Receiver P.C. board (MCC-1504) Display LED Receive circuit MCU Function setup Display LCD Function setup SW Display LED Display LCD LCD driver Key switch MCU Function setup CN2 Grille up/down SW…
-
8-2. Control Specifications
No. Item 1 When power supply is reset 2 Operation mode selection Outline of specifications Remarks 1) Distinction of outdoor unit When the power supply is reset, the outdoors are distinguished and the control is selected according to the distinguished result. 2) Setting of indoor fan speed and…
-
Item Room temp. control (Continued) Outline of specifications Remarks 2) Using the Item code 06, the setup temperature in heating operation can be corrected. Setup data Setup temp. correction +0°C +2°C +4°C +6°C Shift of suction temperature in heating operation Setting at shipment Setup data 4…
-
Outline of specifications
6 Air speed selection 1) Operation with (HH), (H), (L) or [AUTO] mode is carried out by the command from the remote controller. 2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts. HH > H+ > H > L+ > L > UL <COOL> Ta (˚C) HH (HH) A B C H+ (HH) D…
-
Item Cool air discharge preventive control Outline of specifications Remarks 1) In heating operation, the indoor fan is controlled based on the detected temperature of Tc sensor or Tcj sensor. As shown below, the upper limit of the revolution frequency is restricted. However B zone is assumed as C…
-
Outline of specifications
9 High-temp. release control 1) The heating operation is performed as follows based on the detected temperature of Tc sensor or Tcj sensor. • When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds…
-
Outline of specifications
Remarks 12 Louver control: In case of 4-way Discharge Cassette type 1) Louver position setup • When the louver position is changed, the position moves necessarily to downward discharge position once to return to the set position. • The louver position can be set up in the following operation range.…
-
Outline of specifications
12 Louver control (Continued): In case of 4-way Discharge Cassette type <<Selection of Swing mode>> • For the Swing mode, the following three types of modes are SWING/FIX selectable and settable by keeping Swing/Direction button pushed for 4 seconds or more on the remote controller. Q Standard (4…
-
Item Louver control (Continued): In case of 4-way Discharge Cassette type Outline of specifications • If there is the locked louver in the unit, [ ] goes on the remote controller screen. • While the following controls are performed, the louvers operate even if executing the louver lock. Control…
-
Outline of specifications
Remarks 16 Central control mode selection 1) Setting at the centerl controller side enables to select the contents which can be operated on the remote controller at indoor unit side. 2) Setup contents • 64 line central controller (TCB-SC642TLE2) [Individual]: Operated on the remote controller…
-
Item DC motor Remarks Outline of specifications 1) When the fan operation has started, positioning of the stator and the rotor are performed. (Moves slightly with tap sound) 2) The motor operates according to the command from the indoor controller. Notes) • When the fan rotates while the air…
-
Outline of specifications
22 8°C heating/ Frost protective operation 1) This functional is intended for the cold latitudes and performs objective heating operation (8°C heating operation). 2) This function is valid only for combination with the outdoor units (Super Digital Inverter (SDI) 4-series outdoor units). 3) Using the…
-
Connector No
Humidifier output (∗) CN66 ntilation output HA Option output – 74 – Outside error input AUTO up/down grille (∗) Specifications Pin No. CN60 CN80 CN20 DC12V 2 Output (Open collector) 1 DC12V 2 Output (Open collector) Setting at shipment: Interlock of ON by indoor unit operation, with OFF by stop…
-
Indoor/Outdoor inter-unit cable
-
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS
9-1. Outdoor Controls 9-1-1. Print Circuit Board <Viewed from parts of P.C board> RAV-SP1104AT-E, RAV-SP1404AT-E RAV-SP1104ATZ-E, RAV-SP1404ATZ-E RAV-SP1104ATZG-E, RAV-SP1404ATZG-E <MCC-1571> Fan motor output (Lower side) CN300 (White) Fan motor output (Upper side) CN400 (White) Compressor output…
-
C12, 13, 14
electrolytic capacitor DB02: High power factor diode Q404: High power factor circuit IGBT F03: 3.15A fuse DB01: Single-phase rectifier diode L-phase power supply lead (Black) N-phase power supply lead (White) Serial lead (Orange) Reactor lead connector (White) – 77 – CN701: 4-way valve connector…
-
9-2. Outline of Main Controls
<In case of RAV-SP110 and SP140 models> 1. PMV (Pulse Motor Valve) control 1) PMV is controlled between 30 and 500 pulsed during operation. 2) In cooling operation, PMV is usually controlled with the temperature difference between TS sensor and TC sensor aiming 1 to 4K as the target value. 3) In…
-
3. Outdoor fan control
-
4. Coil heating control
1) This control function heats the compressor by turning on the stopped compressor instead of a case heater. It purposes to prevent stagnation of the refrigerant inside of the compressor. 2) As usual, turn on power of the compressor for the specified time before a test run after installation…
-
7. Current release value shift control
Current release control value (11) [A] 1) This control purposes to prevent troubles of the electronic parts such as the compressor driving elements and the compressor during cooling operation. 2) The current release control value (11) is selected from the following table according to TO sensor…
-
10. Defrost control
1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to D zone. 2) During defrosting operation, it finishes if TE sensor continued 12°C or higher for 3 seconds or continued 7°C ≤ TE < 12°C for 1 minute. The defrost operation also finishes when it…
-
1. Pulse Motor Valve (PMV) control 1) For PMV with 50 to 500 pulses during operation, respectively. 2) In cooling operation, PMV is controlled with the temperature difference between TS sensor and TC sensor. 3) In heating operation, PMV is controlled with the temperature difference between TS sensor…
-
4. Outdoor fan control
-
2) Heating fan control
The outdoor fan is controlled by TE sensor, TO sensor and the operation frequency. (From Min. W1 to Max. are controlled according to the following table.) During 3 minutes after start-up, the fan is fixed with the maximum fan tap corresponding to zone in the following table. After then the fan…
-
6. Defrost control
In heating operation, defrost operation is performed when TE sensor temperature satisfies any condition in A zone to C zone. The defrost operation is immediately finished if TE sensor temperature has become 12°C or more, or it also is finished when condition of 5°C < TE < 12°C has continued for…
-
10. TROUBLESHOOTING
10-1. Summary of Troubleshooting <Wired remote controller type> 1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The…
-
<Wireless remote controller type>
1. Before troubleshooting 1) Required tools/instruments • + and – screwdrivers, spanners, radio cutting pliers, nippers, etc. • Tester, thermometer, pressure gauge, etc. 2) Confirmation points before check a) The following operations are normal. 1. Compressor does not operate. • Is not 3-minutes…
-
10-2. Troubleshooting
10-2-1. Outline of judgment The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method. Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of the receiving part) The…
-
Lamp indication
Operation Timer Ready Check code F01 F02 Alternate flash P10 Cause of trouble occurrence Heat exchanger sensor (TCJ) error Heat exchanger sensor (TC) error Heat exchanger sensor (TA) error Indoor unit sensor error F04 F06 Operation Timer Ready F07 F08 Alternate flash F12 F13 Discharge…
-
10-2-2. Others (Other than Check Code)
Lamp indication Operation Timer Check code Cause of trouble occurrence Ready — During test run — Disagreement of cool/heat (Automatic cool/heat setting to automatic cool/heat prohibited model, or setting of heating to cooling-only model) Simultaneous flash Operation Timer Ready Alternate flash – 91…
-
10-2-3. Check Code List (Indoor)
¡ : Go on, ¥ : Flash, l : Go off (Indoor unit detected) Check code indication TCC-LINK central & Wired remote controller E03 E04 E08 E10 E18 – 92 – F01 F02 F10 F29 L03 L07 L08 L09 L20 L30 P01 P10 P12 P19 P31 Sensor lamp indication Block indication Operation Timer Ready Flash l l l l l ¥ l ¥ ¥ ¥ ¥ ¥…
-
Check Code List (Outdoor)
ALT (Alternate): Alternate flashing when there are two flashing LED Remote controller indication F04 Sensor lamp part Block indication Operation Timer Ready Flash ALT ¥ ¥ ¡ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¡ L29 ¥ P03 E01 ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ ¥ E02 ¥ F06 F08 F07 F12 F13 F15 F31 H01 H02 H03 H04 L10 – 93 – P04…
-
ALT (Alternate): Alternate flashing when there are two flashing LED
Remote controller indication F01 F02 F10 F29 P01 P10 P12 P31 — Sensor lamp part Block indication Operation Timer Ready Flash ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ SIM ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ ALT ¥ ¥ l l l — l By unit with warning No. — L20 l l l l ALT — ¥ ¡ — Representative defective position Detection Indoor…
-
Error mode detected by indoor unit
Operation of diagnostic function Check code Cause of operation E03 No communication from remote controller (including wireless) and communication adapter E04 The serial signal is not output from outdoor unit to indoor unit. • Miswiring of inter-unit wire • Defective serial sending circuit on outdoor…
-
Error mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function Check code Cause of operation Status of air conditioner Judgment and measures Condition — Power supply error of remote controller, Indoor EEPROM error 1. Check remote controller inter-unit wiring. 2. Check remote controller. 3. Check indoor power wiring. 4. Check…
-
Error mode detected by outdoor unit
The check code has been ramified from 4 series and after. The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after. (Ex. Combination of RAV-SM1404UT-E with RAV-SP1404AT-E) When the indoor unit is 3 series and before, the conventional check code…
-
Operation of diagnostic function
Check code Indoor unit before 3 series after 4 series P03 P03 Cause of operation Condition Stop Displayed when error is detected Discharge temp. error P04 H04 ∗ Discharge temp. (TD) over specified value was detected. Case thermostat operation ∗ Abnormal overheat of compressor Judgment and measures…
-
10-2-4. Diagnostic Procedure for Each Check Code (Indoor Unit)
Check code [E01 error] Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller YES Correct connection of connector. Check circuit wiring. NO Check power connection of indoor unit. (Turn on power again.) NO Check indoor P.C. board (MCC-1570). Defect → Replace YES…
-
[E04 error]
NO Does outdoor operate? Is group address setup of remote controller correct? YES NO Check Item code [14]. YES Are wiring in indoor unit and 1, 2, 3 inter-unit cables correct? NO Correct wiring and inter-unit cables. NO Correct wiring of connector and terminal blocks. NO Check indoor P.C. board.…
-
[E18 error]
Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller. YES Correct connection of connector. Check circuit wiring. NO Check power connection status of indoor unit (Connect again). YES Is there no disconnection or contact error of connector on harness from terminal…
-
[L20 error]
Are wiring connections to communication lines U3 and U4 normal? NO Correct wiring connection. YES Is not the multiple same central control system addresses connected? YES Correct central control system address. NO Check central controller (including network adapter) and indoor P.C. board (MCC-1570).…
-
[P10 error]
Is connection of float switch connector (Indoor control board CN34) normal? NO Correct connection of connector. YES NO YES Does float switch work? Is circuit wiring normal? YES NO Check and correct wiring and wire circuit. NO Does drain pump work? YES Is power of drain pump turned on? ∗ NO YES Are…
-
[P12 error]
Turn off the power. Is there no connection error or disconnection on connectors CN333 and CN334 of indoor unit P.C. board (MCC-1570)? YES Correct connection of connector. CN333 NO Remove connectors CN333 and CN334 of indoor unit P.C. board (MCC-1570). CN334 Does the fan rotate without trouble when…
-
[F02 error]
Is connection of TC sensor connector (CN101 on Indoor P.C. board) correct? NO Correct connection of connector. YES Are characteristics of TC sensor resistance value normal? YES NO Replace TC sensor. ∗ Refer to Characteristics-2. Check indoor P.C. board (MCC-1570). Defect → Replace [F01 error] Is…
-
[C06 error] (TCC-LINK central controller)
NO Are U3 and U4 communication lines normal? Correct communication line. YES NO ∗1 Correct connection of connector. Is connection of connector normal? YES ∗1 TCC-LINK central: CN51 of TCC-LINK adapter P.C. board (MCC-1440) and CN050 of indoor P.C. board NO Are A and B communication lines normal?…
-
[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal from the remote controller (also central controller). Check A and B remote controllers and communication lines of the central control system U3 and U4. As communication is impossible, this check code [E03] is not displayed on the…
-
10-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)
1) This section describes the diagnostic method for each check code displayed on the remote controller. 2) In some cases, a check code indicates multiple symptoms. In this case, confirm LED display on the outdoor P.C. board to narrow the contents to be confirmed. 3) The check code on the remote…
-
code
Outdoor LED display [F04] <Display 1> <Display 2> ¡ ¡ l l ¡ ¡ l l ¥ l l [Discharge temp. sensor (TD) error] Is CN603 connection normal? Is resistance value of TD sensor normal? NO Correct connector. Sensor error → Replace YES ¡ [F06] Check outdoor P.C. board. Defect → Replace • There is a…
-
code
Outdoor LED display [F08] <Display 1> <Display 2> ¡ ¡ l l ¡ ¡ l l l ¥ l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Outside air temp. sensor (TO) error] Is CN602 connection normal? Is resistance value of TO sensor normal? NO Correct connector. Sensor…
-
code
Outdoor LED display [H01] <Display 1> <Display 2> l l ¡ l ¡ ¡ ¥ l l l l ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Compressor break down] Is power supply voltage normal? AC198 to 264V NO Correct power supply line. YES Is wire connection normal?…
-
code
Outdoor LED display [H04] <Display 1> <Display 2> l l ¡ l ¡ ¡ l l l ¥ l ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Case thermostat operation] Are CN609 connection and case thermostat normal? NO Correct connector. Case thermostat error → Replace NO…
-
code
Outdoor LED display Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) ∗ There is a possibility that it is one of the following errors. Confirm LED on outdoor P.C. board to judge which error it is. Communication error between MCU, Heat sing temp. sensor (TH)…
-
code
Outdoor LED display [P03] <Display 1> <Display 2> ¡ ¡ ¡ l ¡ ¡ ¥ ¥ l l l ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Discharge temp. error] Is there no gas leak? Is refrigerant charge amount adequate? NO Repair defective position. Recharge refrigerant.…
-
code
Outdoor LED display [P07] <Display 1> <Display 2> ¡ ¡ ¡ l ¡ ¡ ¥ ¥ ¥ l l ¡ Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Heat sink overheat error] Is there no loosening of screws of motor drive element of outdoor P.C. board Q200, Q300, Q400 and rectifier…
-
<Display 1> <Display 2>
¡ ¡ ¡ ¥ ¥ ¡ ¡ ¥ ¡ l l Is operation of 4-way valve normal? (Check pipe temp., etc. in cooling/heating operation.) Temperature sensor check TE sensor CN601 TS sensor CN600 Indoor TC sensor Defect → Correct and repair YES NO Is the coil resistance value of 4-way valve between 1.3 and 1.6kΩ? NO Replace…
-
code
Outdoor LED display [P20] <Display 1> <Display 2> l l ¡ ¡ ¡ ¥ ¡ ¡ ¥ ¡ l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [High pressure protective operation] NO Is valve fully opened? Open valve fully. YES Reset the power supply and then perform test run…
-
code
Outdoor LED display [P22] <Display 1> <Display 2> l ¡ ¡ ¡ ¥ ¥ ¡ ¡ ¥ ¡ l l Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Fan system error] Is there no problem on power supply voltage? (198 to 264V) NO Check wiring construction. Ask repair of power supply.…
-
Temperature sensor
Temperature – Resistance value characteristic table TD, TL sensors TA, TC, TCJ, TE, TS, TO sensors Representative value Representative value Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard value) (Maximum value) Ω) Resistance value (kΩ Temperature (°C) (Minimum value) (Standard…
-
10-2-6. Outline of judgment
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method. Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of the receiving part) The indoor unit monitors the…
-
Lamp indication
Operation Timer Ready F01 F02 Alternate flash Cause of trouble occurrence Check code P10 Heat exchanger sensor (TCJ) error Heat exchanger sensor (TC) error Heat exchanger sensor (TA) error F04 Operation Timer Ready F06 F08 Alternate flash Discharge temp. sensor (TD) error…
-
10-2-8. Check Code List (Indoor)
¡ : Go on, ¥ : Flash, l : Go off (Indoor unit detected) Check code indication TCC-LINK central & Wired remote controller E03 E04 E08 E10 E18 – 122 – F01 F02 F10 F29 L03 L07 L08 L09 L20 L30 P01 P10 P12 P19 P31 Sensor lamp indication Block indication Operation Timer Ready Flash l l l l l ¥ l ¥ ¥ ¥ ¥ ¥…
-
Check Code List (Outdoor)
¡ : Go on, ¥ : Flash, l : Go off Remote controller indication F04 F06 F08 F12 H01 H02 H03 P03 P05 P22 P26 P29 Sensor lamp part Block indication Operation Timer Ready Flash ALT ¥ ¥ ¡ ¥ ¥ ¥ l l l E01 ¥ ¥ ¥ ¥ ¥ ¥ E02 ¥ E03 – 123 – E04 E08 E09 E10 E18 L03 L07 L08 L09 L30 P19 F01 F02 F10 F29 P01 P10 P12…
-
Error mode detected by indoor unit
Operation of diagnostic function Check code Cause of operation E03 No communication from remote controller (including wireless) and communication adapter E04 The serial signal is not output from outdoor unit to indoor unit. • Miswiring of inter-unit wire • Defective serial sending circuit on outdoor…
-
Error mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function Check code Cause of operation Status of air conditioner Judgment and measures Condition — Power supply error of remote controller, Indoor EEPROM error 1. Check remote controller inter-unit wiring. 2. Check remote controller. 3. Check indoor power wiring. 4. Check…
-
Error mode detected by outdoor unit
Operation of diagnostic function Check code Cause of operation Judgment and measures Status of air conditioner Condition F04 Disconnection, short of discharge temp. sensor (TD) Stop Displayed when error is detected 1. Check discharge temp. sensor (TD). 2. Check outdoor P.C. board. F06 Disconnection…
-
10-2-9. Diagnostic Procedure for Each Check Code (Indoor Unit)
Check code [E01 error] Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller YES Correct connection of connector. Check circuit wiring. NO Check power connection of indoor unit. (Turn on power again.) NO Check indoor P.C. board (MCC-1570). Defect → Replace YES…
-
[E04 error]
NO Does outdoor operate? Is group address setup of remote controller correct? YES NO Check Item code [L07]. YES Are wiring in indoor unit and 1, 2, 3 inter-unit cables correct? NO Correct wiring and inter-unit cables. NO Correct wiring of terminal blocks. YES Are wirings of terminal blocks (1, 2, 3)…
-
[E18 error]
Is inter-unit cable of A and B normal? NO Correct inter-unit cable of remote controller. YES Correct connection of connector. Check circuit wiring. NO Check power connection status of indoor unit (Connect again). YES Is there no disconnection or contact error of connector on harness from terminal…
-
[L20 error]
Are wiring connections to communication lines U3 and U4 normal? NO Correct wiring connection. YES Is not the multiple same central control system addresses connected? YES Correct central control system address. NO Check central controller (including network adapter) and indoor P.C. board (MCC-1570).…
-
[P10 error]
Is connection of float switch connector (Indoor control board CN34) normal? NO Correct connection of connector. YES YES NO Does float switch work? Is circuit wiring normal? YES NO Check and correct wiring and wire circuit. NO Does drain pump work? YES Is power of drain pump turned on? ∗ NO YES Are…
-
[P12 error]
Turn off the power. Is there no connection error or disconnection on connectors CN333 and CN334 of indoor unit P.C. board (MCC-1570)? YES Correct connection of connector. CN333 NO Remove connectors CN333 and CN334 of indoor unit P.C. board (MCC-1570). CN334 NO Does the fan rotate without trouble…
-
[F02 error]
Is connection of TC sensor connector (CN101 on Indoor P.C. board) correct? NO Correct connection of connector. YES Are characteristics of TC sensor resistance value normal? YES NO Replace TC sensor. ∗ Refer to TC sensor (Temperature-Resistance value characteristic table) Check indoor P.C. board…
-
[C06 error] (TCC-LINK central controller)
NO Are U3 and U4 communication lines normal? Correct communication line. YES NO ∗1 Correct connection of connector. Is connection of connector normal? YES ∗1 TCC-LINK central: CN51 of TCC-LINK adapter P.C. board (MCC-1440) and CN050 of indoor P.C. board NO Are A and B communication lines normal?…
-
[E03 error] (Master indoor unit)
[E03 error] is detected when the indoor unit cannot receive a signal from the remote controller (also central controller). Check A and B remote controllers and communication lines of the central control system U3 and U4. As communication is impossible, this check code [E03] is not displayed on the…
-
10-2-10. Diagnostic Procedure for Each Check Code (Outdoor Unit)
• This section describes the diagnostic method for each check code displayed on the remote controller. In some cases, a check code indicates multiple symptoms. Check code [E04] Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Indoor/Outdoor communication…
-
[F12]
Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Suction temp. sensor (TS) error] NO Is CN603 connection normal? Is resistance value of TS sensor normal? Correct connector. Sensor error → Replace YES Check outdoor P.C. board. Defect → Replace [H01]…
-
[P03]
Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Discharge temp. error] Is there no gas leak? Is refrigerant charge amount adequate? NO Repair defective position. Recharge refrigerant. NO Repair defective position. Replace defective part. YES Is PMV normal?…
-
[P22]
Check and troubleshooting (Item without special mention Indicates part of outdoor unit.) [Fan system error] Is there no problem on power supply voltage? (198 to 264V) NO Check wiring construction. Ask repair of power supply. YES Check outdoor P.C. board. Defect → Replace YES Does the fan rotate…
-
Temperature sensor
-
11-1. Indoort Unit <Note: when replacing the P.C. board for indoor unit servicing> The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P.C. board before replacement includes the model specific type information and capacity codes as the factory-set value and the important…
-
[1] Setting data read out from EEPROM
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out. Step 1 Push SET , CL and TEST button on the remote controller simultaneously for more than 4 seconds. ∗ When the group operation control is performed, the unit No. displayed for the first…
-
Setting 4-way air discharge cassette Indoor Unit model only
1. Using the set temperature / 2. Using the timer time / buttons, set “+-” to the CODE No. (DN). buttons, set the data. (0001) • Push SET button. (The setting completes if the setting data are displayed.) <In case of 4-way Discharge Cassette type> If the plug for short-circuit is attached on the…
-
Step 4
Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above again. Step 5 Change the CODE No. (DN) to “” by pushing (this is the setting for the filter sign lighting time.) Step 6 Check the setting data displayed at this time with the setting data put…
-
Table 1. Setting data (CODE No. table (example))
DN Item Setting data Factory-set value 01 Filter sign lighting time Depending on Type 02 Filter pollution leve 0000: standard 03 Central control address 0099: Not determined 06 Heating suction temperature shift 0002: +2°C (flooring installation type: 0) OF Cooling only 0000: Heat pump 10 Type…
-
11-2. Outdoor Unit
1. Setting the jumper wires and DIP switches Function Part name Setting J800 to J803 Model switching Cut these jumper wires according to the following table. J804 to J810 Settings Set these jumper wires to the settings of the P.C. board before replacement. SW802 Settings Set SW802 to the setting of…
-
12. SETUP AT LOCAL SITE AND OTHERS
12-1. Indoor Unit 12-1-1. Test Run Setup on Remote Controller <Wired remote controller> TEST 1. When pushing button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display. ON / OFF Then push button. • “TEST” is displayed on LC display during operation of Test Run. • During…
-
(Except 4-way Air Discharge Cassette Type and Under Ceiling Type)
1 Remove a screw which fixes the name plate of the receiver part on the wireless remote controller. Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the bottom of the plate, and set the Dip switch to [TEST RUN ON]. 2 Execute a test operation with…
-
<In case of wireless remote controller>
Procedure Description Turn on power of the air conditioner. 1 2 The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and 1 minute when power has been turned on at the next time and after. After the specified time has passed, perform a test…
-
12-1-2. Forced Defrost Setup of Remote Controller (For wired remote controller only)
(Preparation in advance) 1 Push TEST SET CL + + buttons simultaneously for 4 seconds or more on the remote controller. (Push buttons while the air conditioner stops.) The first displayed unit No. is the master indoor unit address in the group control. 2 Every pushing UNIT button, the indoor unit No.…
-
12-1-4. Function Selection Setup
<Procedure> Perform setting while the air conditioner stops. 1 Push TEST SET CL + + buttons simultaneously for 4 seconds or more. The first displayed unit No. is the master indoor unit address in the group control. In this time, fan and louver of the selected indoor unit operate. 2 Every pushing ò…
-
Function selection item No. (DN) list
DN Item 01 Filter sign lighting time 0000: None 0002: 2500H 0004: 10000H 02 Filter stain level 0000: Standard 0001: Heavy stain (Half of standard time) 0000: Standard 03 Central control address 0001: No.1 unit 0099: Undecided 0099: Undecided 06 Heating suction temp. shift 0F Cooling-only 0000: Heat…
-
DN
Item Contents 0000: None 0000: 0.5 h to 0.012: 0 h Set when compressor-ON time is 10 to 60 minutes. 42 Self-clean operation time 45 Selection of louver horizontal discharge position 0000: Smudging-less setting 0002: Cold draft preventive setting C2 Current demand X% to outdoor unit 0050: 50% When…
-
12-1-5. Wiring and Setting of Remote Controller Control
2-remote controller control (Controlled by 2 remote controllers) This control is to operate 1 or multiple indoor units are operated by 2 remote controllers. (Max. 2 remote controllers are connectable.) • When connected 2 remote controllers operate an indoor unit Remote controller switch (Master)…
-
12-1-6. Monitor Function of Remote Controller Switch
n Calling of sensor temperature display <Contents> Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller. <Procedure> 1 Push CL TEST + buttons simultaneously for 4 seconds to call the service monitor mode.…
-
n Calling of error history
<Contents> The error contents in the past can be called. <Procedure> 1 Push SET TEST + buttons simultaneously for 4 seconds or more to call the service check mode. Service Check goes on, the item code 01 is displayed, and then the content of the latest alarm is displayed. The number and error…
-
n Indoor unit power-ON sequence
Power ON • The unit without power feed waits entirely → Waiting status is released by system start • Reboot when power is fed on the way <By feed unit> <Automatic address judgment> Not normal NO 3 minutes elapse Gr construction check YES Normal ∗ Gr normal 1) There is no duplicated indoor unit…
-
12-2. Setup at Local Site / Others
Model name: TCB-PCNT30TLE2 12-2-1. TCC-LINK Adapter (For TCC-LINK Central Control) 1. Function This model is an optional P.C. board to connect the indoor unit to TCC-LINK (Central controller). 2. Microprocessor block diagram Indoor unit Central controller TCC-LINK adapter P.C. board CN050 Indoor…
-
4. Wiring specifications
• Use 2-core with no polar wire. • Match the length of wire to wire length of the central Size No. of wires control system. Up to 1000m: twisted wire 1.25mm2 If mixed in the system, the wire length is lengthened 2 Up to 2000m: twisted wire 2.0mm2 with all indoor/outdoor inter-unit wire length at…
-
Terminator (SW01) 52 85 7. Address setup In addition to set up the central control address, it is necessary to change the indoor unit number. (Line/Indoor/Group address). For details, refer to TCC-LINK Adapter Installation Manual. 12-3. How to Set up Central Control Address Number When connecting…
-
2. How to confirm the central control address
(New function for AMT32 remote controller) <Procedure> It can be confirmed even during operation or stopping. 1 Push UNIT LOUVER button for 4 seconds or more. ò 2 In the frame at left side of the remote controller screen, the lighting set contents are displayed. During unset time, '' (At shipment…
-
<For only 4-way Discharge Cassette type> 1 Push SWING/FIX for 4 seconds or more during stop of the operation. • flashes. 2 Push UNIT LOUVER (At the left side of the button) and select the unit to be selected. • Every pushing the button, the unit No. changes. UNIT No. 1–1 UNIT No. 1–2 UNIT No. No…
-
4. How to set louver lock (Louver fix)
<For only 4-way Discharge Cassette type> 03 Refrigerant pipe 1 4Push (At the right side of the button) for seconds or more during stop of the operation. UNIT LOUVER • Electric parts box 04 flashes. 2 Push 02 Drain pipe UNIT LOUVER (At the left side of the button) and select the unit to be set. •…
-
7. When installing separately sold filters
REQUIREMENT • When you use this air conditioner for the first time, it takes approx. 5 minutes until the remote controller becomes available after power-on. This is normal. <When power is turned on for the first time after installation> It takes approx. 5 minutes until the remote controller becomes…
-
When wireless remote controller is used
Be sure to make ceiling setting when installing separately sold filters. ∗ Separately sold filters cannot be installed in an indoor unit on a high ceiling. Follow to the basic operation procedure (1 → 2 → 3 → 4 → 5 → 6 ). • For the CODE No. in Procedure 3, specify [5d]. • For the set data in…
-
Revised 2: Mar., 2008
<In case of SP110, SP140> 12-4. Outdoor Unit 12-4-1. Refrigerant Recovery Control The “ozone destruction coefficient” of HFC refrigerant is 0 and the discharge regulation is set as anathermal effect gas. To this model, a switch which can perform the refrigerant recovery (pump down) by the outdoor…
-
12-4-3. Service Support Function (LED Display, Switch Operation)
1. Outline A various setup and operation check can be performed by DIP switches at 3 positions (SW802, SW803, SW804) and the pushdown button switches (SW800, SW801) at 2 positions. Operation part Part No. Specifications SW800 Pushdown button switch SW803 DIP switch SW801 Pushdown button switch SW804…
-
12-4-4. Others
1. Selection of LED display (SW800, SW803 operation) 1) Display selection list The displayed contents of LED D800 to D804 on the outdoor control P.C. board can be exchanged by operation of SW803. Switch Function / Contents Error display (Error generating at present) Error generating at present is…
-
2) Error display
The error which is generating at present and the latest error (Latest error information including present) can be confirmed by lighting LED D800 toD804 on the outdoor control P.C. board. a) When all DIP switch SW803 are OFF, the status of error which is generating at present is displayed. b) <1>…
-
3) Sensor, current, compressor operation frequency, PMV opening display
-
4) Specific operation for maintenance check (SW801, SW804)
The following specific operations for the maintenance check are performed by operation of SW801 or SW804. a) Select DIP switch SW804. (See table below) b) Push the pushdown button switch SW801 for approx. 1 second. c) The following functions start. While each function starts, LED D805 (Green)…
-
SW804
1 ON SW804 Operation when pushdown button switch SW801 is pushed 4-way valve relay operation (For RY700, CN70 check) Turn on 4-way valve power relay (RY700). When pushing SW801 again or when 2 minutes elapsed, the operation returns to the normal control. 1 ON SW804 1 ON SW804 Self-hold valve…
-
13. ADDRESS SETUP
13-1. Address Setup Procedure When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit.…
-
13-2. Address Setup & Group Control
<Terminology> Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control) 1 = Master unit in group control 2 = Sub unit in group control Master unit (= 1) : The representative of multiple indoor units in group…
-
13-2-2. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit) 1) Single 1-1 Individual (Master/Sub) 2) Group operation (Twin, Triple operation) (Multiple outdoor units = Miltiple indoor units only with serial communication) 2-1 Sub/Header 1-1 Sub/Header 1-2 Sub/Follower 3-1 Master/Header 3-2 Sub/Follower 3-3 Sub/Follower Only…
-
13-2-3. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit) 1) Single 2) Twin 3) Triple (1-1) 1-2 Master/Header 1-1 Individual (1-1) (1-2) 1-2 Sub/Header 1-1 Sub/Follower (1-2) (1-3) 1-3 Master/Follower 1-1 Sub/Follower (Master/Header) Only turning on source power supply (Automatic completion) 2. Group operation (Multiple…
-
13-3. Remote Controller Wiring
<Single system> • Strip off approx. 9 mm the wire to be connected. • For single system, use non polarity, 2 core wire is used for wiring of the remote controller. (0.5 mm² to 2.0 mm² wires) • For the synchronous twin, triple system, use 2-conre shield wire (Vinyl cord for microphone 0.5 to 2.0 mm²)…
-
13-4. Address Setup (Manual setting from remote controller)
In case that addresses of the indoor units will be determined prior to piping work after cabling work • Set an indoor unit per a remote controller. • Turn on power supply. (Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe) Outdoor Outdoor Indoor Indoor Indoor Indoor A B…
-
13-5. Confirmation of Indoor Unit No. Position
1. To know the indoor unit addresses though position of the indoor unit body is recognized • In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure> 1 Push 2 Push ON / OFF button if the unit stops. UNIT LOUVER button.…
-
<Maintenance/Check list>
Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner. It is also recommended to maintain the units once a year regularly when operating…
-
14. DETACHMENTS
14-1. Indoor Unit 14-1-1. 4-Way Air Discharge Cassette Type RAV-SM564UT-E, RAV-SM804UT-E, RAV-SM1104UT-E, RAV-SM1404UT-E, RAV-SM1604UT-E No. Part name 1 Suction grille Procedure Remarks Suction grille XCAUTIONX Knobs of the suction grille hook Be sure to put on the gloves at disassembling work…
-
Electric parts cover (Continued) 3 Adjust corner cap Procedure Remarks 1. Detachment Adjust corner cap 1) Pull knob of the adjust corner cap to the arrow direction, remove strap of the adjust corner cap from pin of the panel and then remove all the 4 corners of the cap. Knob NOTE : The knob is…
-
Ceiling panel
Remarks Procedure 1. Detachment 1) Carry out works of item 1 of 2 and item 1 of 3 . 2) Remove the flap connector (CN510, White, 20P) connected to the control P.C. board and then remove the lead wire from the clamp. Clamp Louv Louver er motor wiring wiring CN510 NOTE : Unlock the lock of the housing…
-
Control P.C. board Procedure Remarks 1. Detachment 1) Carry out work of item 1 of 2 . 2) Remove connectors which are connected from the control P.C. board to the other parts and then remove wiring from the clamp. CN510 : Louver motor (20P, White) CN34 : Float switch (3P, Red) CN504 : Drain pump (2P…
-
Drain cap Remarks Procedure 1. Detachment Drain cap (outside) 1) Carry out work of item 1 of 1 . 2) Loosen screws (3 positions) fixing the drain cap (outside) and then turn the drain cap to the arrow mark direction to remove it. CLOSE NOTE : The drain cap is hung down because a strap is attached to…
-
Fan motor Remarks Procedure 1. Detachment 1) Carry out work of item 1 of 2 . 2) Remove connectors which are connected from the control P.C. board to the other parts and then remove each wiring from the clamp. CN510 : Louver motor (20P, White) CN34 : Float switch (3P, Red) CN504 : Drain pump (2P…
-
Fan motor (Continued) Remarks Procedure 2. Attachment 2) Fix the fan motor lead, TC sensor and TCJ sensor with the clamp of the bell mouth. 3) Mount the electric parts box with the fixing screws A and B. (Ø4 × 10, 3 pcs. Ø4 × 8, 1 pc.) 4) Connect the connector removed in item 1 as before and then…
-
Drain pump Procedure Remarks 1. Detachment 1) Carry out works of item 1 of 2 and item 1 of 6 . 2) Remove the drain pump connector (CN504, White, 2P) connected to the control P.C. board and then remove the lead wire from the clamp. 3) Remove the fixing screws and then remove the drain pump. (Ø4 × 10…
-
Float switch assembly Remarks Procedure 1. Detachment 1) Carry out works of item 1 of 7 and works from 1) to 5). 2) Remove the fixing screw and then remove the float switch assembly. (Ø4 × 25, 1 pc.) Float switch switch assembly assemb 2. Attachment 1) Mount the float switch assembly as before with…
-
Heat exchanger Procedure Remarks 1. Detachment 1) Recover the refrigerant gas. 2) Carry out work of item 1 of 10 . 3) Remove refrigerant pipe at indoor unit side. 4) Remove the fixing screws and then remove the piping cover. (Ø4 ×10, 3 pcs.) 5) Remove the drain hose from the drain pump and remove…
-
14-1-2. Slim Duct Type
RAV-SM404SDT-E, RAV-SM454SDT-E, RAV-SM564SDT-E No. Part name Procedure Remarks XREQUIREMENTX Be sure to put on gloves at working; otherwise an injury may be caused by parts, etc. • Before replacement of the parts, be sure to stop operation of the air conditioner and turn off switch of the breaker. 1…
-
E-cover Procedure Remarks 1. Detachment 1) Perform work 1. of 2 . 2) Take off screws fixing E-cover, and then remove hooks of the hooking part by lifting up. (Ø4 × 10, 2 pcs) 2. Attachment E-cover 1) Hang on E-cover to hooks of the hooking part so that it does not fall down. NOTE) Be sure not to…
-
Part name P.C. board assembly Remarks Procedure 1. Detachment 1) Perform works 1. of 2 , 1. of 3 , and 1. of 4 . 2) Disconnect connectors which are connected from P.C. board assembly to other parts. P.C. board assembly NOTE) Unlock the lock of the housing to disconnect the connectors. CN41 : Remote…
-
Procedure
No. Part name 7 Fan motor Remarks 1. Detachment 1) Perform works 1. of 2 , 1. of 3 , and 1. of 6 . 2) Remove lead wires which are connected to the following connectors of P.C. board assembly. NOTE) Unlock locks of the housing, and then remove the connectors. CN333 : Fan motor power supply (5P…
-
Drain pump, 1. Detachment Float switch, 1) Perform works in procedures 1. of 2 , 1. of Drain hose 3 , 1. of 8 . 2) Disconnect lead wires which are connected to the following connectors of P.C. board assembly. Procedure Drain hose Hose band Drain pump NOTE) Unlock locks of the housing to remove the…
-
14-2. Outdoor Unit
RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E No. Part name Procedure 1 Common procedure XCAUTIONX Remarks Front panel Never forget to put on the gloves at working time; otherwise an injury will be caused by the parts, etc. 1. Detachment 1) Stop…
-
Discharge port cabinet 3 Side cabinet Procedure Remarks 1. Detachment 1) Carry out work of 1 of 1 . 2) Remove screws for the discharge port cabinet and the partition board. (ST1T Ø4 × 8, 4 pcs.) 3) Remove screws for the discharge port cabinet and the bottom plate. (Hexagonal screw Ø4 × 10, 2 pcs.)…
-
Procedure
Replacement of 1. Control P.C. board electric parts 1) Carry out work of 1 of 1 . Control P.C. board Upper fan motor Compressor case thermo. X Reactor lead WARNINGX Never disassemble the inverter for 1 minute after power supply has been turned off because an electric shock may be caused. 2) Remove…
-
Procedure
Replacement of 2. Reactor electric parts 1) Carry out work of 1 of 1 . (Continued) 2) Remove the reactor lead connected to the control P.C. board. CN05 White, CN06 White 3) Cut the bundling band which bundled the compressor lead and fan motor lead. 4) Remove the reactor. (Trust B tight screw, Ø4 ×…
-
Procedure
5 Fan motor 1) Carry out works of item 1 of 1 and work of 2 . 2) Remove the flange nut fixing the fan motor and the propeller fan. • The flange nut is loosened by turning it clockwise. (When tightening it, turn it counterclockwise.) 3) Remove the propeller fan. 4) Remove the connector for the fan…
-
Compressor Compressor lead Procedure Remarks 1. Removal of defective compressor 1) Recover the refrigerant gas. 2) Carry out work of item 1 of 1 and work of 3. 3) Remove the piping panel (Front). Remove the piping panel (Front) and screws of the bottom plate. (Hexagonal screw Ø4 × 10, 2 pcs.) Remove…
-
Compressor Compressor lead (Continued) Procedure Remarks 2. Mounting of compressor 1) Mount the compressor in the reverse procedure for removal. Wrap the ferrite core with the compressor lead wire for 4 times. Compressor lead NOTE : 0t 0 o5 • After replacement of the compressor, be sure to replace…
-
PMV coil Procedure Remarks 1. Detachment Concave part PMV main unit Positioning projection PMV coil Fan guard Discharge port cabinet 1) Carry out work of item 1 of 1 . 2) Turn the coil while pulling upward and then remove the coil from the PMV main unit. 2. Attachment 1) Surely match the positioning…
-
No. Part name Procedure 1 Common procedure XCAUTIONX Remarks Never forget to put on the gloves at working time, otherwise an injury will be caused by the parts, etc. Valve cover 1. Detachment 1) Stop operation of the air conditioner, and turn off the main switch of the breaker for air conditioner.…
-
Front cabinet Remarks Procedure 1. Detachment 1) Perform work of item 1 of 1 . 2) Remove screws (ST1T Ø4 × 10L, 2 pcs.) of the front cabinet and the inverter cover. 3) Take off screws of the front cabinet and the bottom plate. (ST1T Ø4 × 10L 3 pcs.) 4) Take off screws of the front cabinet and the…
-
Inverter assembly Remarks Procedure 1. Detachment 1) Perform work of item 1 of 1 . 2) Take off screws of the upper part of the front cabinet. • If removing the inverter cover under this condition, P.C. board can be checked. • If there is no space in the upper part of the upper cabinet, perform work…
-
Procedure
Control P.C. 1) Disconnect lead wires and connectors board assembly connected from the control P.C. board assembly to other parts. 1. Lead wires • Connection with the power terminal block: 3 wires (Black, White, Orange) • Earth wire: 1 wire (Black) 2. Connectors • Connection with compressor: Remove…
-
Procedure
5 Rear cabinet 1) Perform works of items 1 of 1 and 2 , 3 . 2) Take off fixed screws for the bottom plate. (ST1T Ø4 × 10L, 3 pcs.) 3) Take off fixed screws for the heat exchanger. (ST1T Ø4 × 10L, 2 pcs.) 4) Take off fixed screw for the valve mounting plate. (ST1T Ø4 × 10L, 1 pc.) 6 Fan motor Remarks…
-
Procedure
7 Compressor 1) Perform works of items 1 of 1 and 2 , 3 , 4 , 5 . 2) Discharge refrigerant gas. 3) Remove the partition plate. (ST1T Ø4 × 10L, 2 pcs.) 4) Remove the noise-insulator. 5) Remove the terminal covers of the compressor, and disconnect lead wires of the compressor and the compressor thermo…
-
Remarks Procedure Part name Pulse Motor Valve 1. Detachment (PMV) coil 1) Perform works of items 1 and 2 . 2) Release the coil from the concavity by turning it, and remove coil from the PMV. PMV body Positioning extrusion PMV coil Concavity 2. Attachment 1) Put the coil deep into the bottom…
-
15. EXPLODED VIEWS AND PARTS LIST
-
Model Name RAV-SM
Location No. Part No. 201 43120248 Fan Ass’y, Turbo, ABS 202 43120247 Fan Ass’y, Turbo, ABS 203 43166011 Remote Controller, SX-A4EE 1 204 4314J399 Refrigeration Cycle Ass’y 1 205 4314J400 Refrigeration Cycle Ass’y Description 564UT-E 804UT-E 1104UT-E 1404UT-E 1604UT-E 4314J401 Refrigeration Cycle…
-
308, 306, 307, 323, 310, Location No. Part No. 301 43409207 302 43480017 303 Description Model Name RBC- U31PG (W)-E U31PG (WS)-E U31PGS (W)-E U31PGS (WS)-E Grille, Air Inlet Air Filter, ABS + PPNET 4302D003 Motor, Louver, MP24Z3N 43407145 Outlet, Air Form, PS-F 43407146 Outlet, Air Form, PS-F…
-
356, 357 Model Name RBC- Location No. Part No. AX31U (W)-E AX31U (WS)-E 353 43459011 P.C. Board Ass’y, Remote Receiver 43462010 Cover, WRS, ABS Description 355 43461006 Sheet, PC 1 356 43108018 Cover, Panel, WRS 1 357 43108019 Cover, Panel, WRS 358 43460126 Lead 1 1 – 215 – 1
-
220 206, 213, 218, 224 225, 226, TEST C SETTING – 216 – 236 ADR 234 237
-
Part No
201 4312C040 203 43120227 205 43170244 206 4314J402 207 43122084 Model Name RAV-SM Description 404SDT-E 454SDT-E 564SDT-E Motor, Fan Fan, Multi blade Hose, Drain Refrigeration Cycle Ass’y Case, Fan, Lower 43122085 Case, Fan, Upper 43100319 Plate, Inlet-B 43172183 Pan Ass’y, Drain 43149351 Socket…
-
15-2. Outdoor Unit
-
Model Name RAV-SP
Part No. Description 1104AT-E 1404AT-E 1104ATZ-E 1404ATZ-E 1104ATZG-E 1404ATZG-E 1 43019904 Holder, Sensor, SUS 43032441 Nipple, Drain 43041794 Compressor, DA422A3F-25M 43047246 Bonnet, 3/8 IN 43047669 Nut, Flange 43197164 Nut, Flange, SUS304-WSB 43049739 Cushion, Rubber 43050407 Thermostat, Bimetal…
-
Model Name RAV-SP
Part No. Description 404AT-E 404ATZ-E 404ATZG-E 454AT-E 454ATZ-E 454ATZG-E 1 43105042 Cabinet, Front, RoHs 43105041 Cabinet, Upper 43005698 Cabinet, Side, Right, RoHs 43005672 Cabinet, Side, Left 4301V035 Guard, Fan 4301V053 Guard, Fin 43100346 Base Ass’y, RoHs 43119471 Caver, Valve, Packed 43162055…
-
WARNINGS ON REFRIGERANT LEAKAGE
Important Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity…
-
TOSHIBA CARRIER CORPORATION
23-17, TAKANAWA 3 CHOME, MINATOKU, TOKYO, 108-8580, JAPAN Copyright © 1999 to 2007 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.