Air Conditioning
SysTemp NEW Close Control Engineering Data Manual Series Series Series Series
-
2 | Key points
Key points SySmart Control Advanced electronic control system is conceived and designed to provide an energy savings and the optimized management of the entire unit. Thanks to the control via Modbus® Master protocol, all key components of the unit are continuously supervised, with over 50 different…
-
Unit identification and specifications |
Unit identifcation and specifications Unit identification ST O P A 07 General The air conditioners have been specifically designed and manufactured for close control air conditioning where the handling almost exclusively sensible heat loads is a fundaAccessories mental requirement. TS Two Sources…
-
4 | Specifications
The structure is riveted monobloc made by hot-galvanized sheet steel of 1mm-thickness painted in anthracite colour RAL 7024. Thermal acoustic insulation system consisting of 23mm thickness for the sides panel and 12 or 20 mm for the back panel according to the unit model. The insulation is high…
-
Specifications |
ST UGU 70-150-230-300. For the units with monobloc structure the drain tray is made by galvanized steel of 1mm-thickness painted in anthracite colour RAL 7024. Valid for models: ST OPA/UPA 071-141-211-251-301-302 ST OPU/UPU 10-20-30-50 ST HRA 121-231-361 ST HRU 20-40. Electrical panel The machines…
-
6 | Specifications
Total run hours Menu displays accumulative components operating hours for major components including compressors, fan motor, humidifier and reheat. Auto restart system The units will automatically restart after a power loss, providing a power supply failure alarm as signaling. Temperature and…
-
Specifications |
Available close control accessories Inverter on the compressor Water leak detector DC brushless technology, driven by frequency driver (inverter), mounted on vibration isolators. The system includes a manual high-pressure reset switch; auto reset low-pressure managed by software. Valid for units…
-
8 | Specifications
Floor stand Adjustable Under base (height up to 600mm) made of hotgalvanised tubular metal structure with relevant feet. The under-base comes demounted in a package with the installation manual. Protected line and air condenser regulator Consisting in an electrical line protected from overload and…
-
10 | SysTemp P
SysTemp P The P Series close control air conditioners have constructional and operating characteristics suitable for environments where thermal loads of a sensitive nature prevail. Although optimised for data centers, the technical characteristics of the P series make these units suitable for…
-
Air Conditioners with downflow air supply Standard version with top air intake and downflow air supply, with stand for raised floors. Version with top air intake and front air supply through air distribution plenum with adjustable grilles. Version with top air intake and front air supply through…
-
12 | SysTemp P
Air Conditioners with upflow air supply Standard version with front air intake and upflow air supply. Version with front air intake and supply, through air distribution plenum with adjustable grilles. Version with air intake from the bottom, stand for raised floor, blind front panel and upflow air…
-
Direct expansion
Brushless DC compressors with inverter regulation and integrated oil separator Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LT Kit for operation with low temperature…
-
14 | SysTemp G
SysTemp G G series close control air conditioners have constructional and operating characteristics suitable for meeting the design criteria of the latest generation data centers. When designing air conditioning systems for large data centers, the need for electrical cable housing and the enormous…
-
SysTemp G |
Air Conditioners with downflow air supply Standard version for data center perimetral installation: the height of the raised floor must be at least 550 mm. Standard version for data center perimetral installation with raised floor height less than 550 mm. In this case the stand, having a fixed…
-
16 | SysTemp G
Available accessories Direct expansion: Brushless DC compressors with inverter regulation and integrated oil separator Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LT kit…
-
18 | SysTemp R
SysTemp R R series close control air conditioners are built and sized in such a way that they can be installed alongside data center racks In air conditioning systems for large data centers, the adoption of the following design concepts has in fact become an established custom: The racks containing…
-
Air Conditioners with horizontal air supply Version for "in row" Iinstallation with front and side air supply ST HRA: Direct expansion air conditioners with horizontal ST HRU: Chilled water air conditioners with horizontal supply ST HRA ST HRU supply Performance 20 40 31,6 Performance Total cooling…
-
20 | SysTemp R
Available accessories Direct expansion: Power supply line for remote condenser Power supply line with speed regulator for remote condenser Condensing regulation with 0-10V signal for remote condenser with EC fans LT Kit for operation with low temperature outside air with remote condenser…
-
TMC
Remote condensers and dry coolers for Close Control units. Technical features Versions for horizontal and vertical installation and with V-shaped structure. Turbocoil heat exchangers made of hot dipped galvanized metal sheet with copper tubes expanded into aluminum fins Casing made of galvanised…
-
22 | Technical data
Main technical data Operating range Air Conditioners Type Direct Expansion Chilled Water Maximum Temperature (Air infeed) °C 40 40 Minimum Temperature (Air infeed) °C 20 18 Minimum Humidity (Air infeed) % 60 60 Maximum Humidity (Air infeed) % 25 25 Storage Conditions °C Temperature from -20°C to +…
-
Water circuit connections
3-way valve A B A B C D E F G H C 2-way valve H F G Water connections E Armaflex insulation Mechanical filter Thermometer Shut-off valves Pressure gauge Balance valve Drain Supports D Water supply line Cooled water coil connection Dimensions Ø (Inches) Standard models 10 ST OPU ST UPU ST UGU Inlet…
-
24 | Technical data
Water condenser connection ( accessory) Dimensions Ø (Inches) Standard models ST OPA ST UPA Standard With pressure adjustment valve 71 – 141 – 211 3/4” Male 1” Female 251 3/4” Male 1 1/4” Female 301 – 361 – 461 1 1/4” Male 1 1/4” Female 302 – 422 2 x 3/4” Male 2 x 1” Female 512 2 x 3/4” Male 2 x 1…
-
Water condenser connection of the submerged electrode humidifier
-
26 | Technical data
Chilled water hydraulic circuit The following image represents the hydraulic circuit of chilled water units with two/three-way valves. E D A B C D E F G H I C C B F G H Water inlet Inlet water temperature (accessory) Manual vent valves Chilled water coil Fan Outlet water temperature (accessory)…
-
Direct expansion cooling circuit
The following image represents the cooling circuit in units with external air condenser. K A B C D E F G J L I H I M N H 1 O G P Q F 2 E D R S C T B A U V J K L M N O P Q R S T U V Liquid line Liquid line cock Liquid line check valve Liquid receiver Pressure intake 5/16” SAE Liquid temperature probe…
-
28 | Technical data
The following image represents the cooling circuit in units with water condenser. K J L I M N H O G P F Q E A B C D E F G H I J K L M N O P Q R S T U D R S C B B T A U Water inlet Manual vent valves Water-cooled condenser Liquid receiver Pressure intake 5/16” SAE Liquid temperature probe Dehydrator…
-
CW/DX two sources cooling circuit unit
The following image illustrates the cooling circuit of the Two Sources units, with a chilled water (CW) and direct expansion (DX) circuit. K d J c c I L e b N M H a O 1 P G Cooling circuit: Q R F 2 E D C f S T U B V A W A B C D E F G H I J K L M N O P Q R S T U V W Liquid line Liquid line cock…
-
30 | Technical data
-
Free Cooling circuit
The following image represents the cooling circuit of the Free Cooling units. J I d c c H K M b e L N G a O F P E Q D R C S B A c c f Cooling circuit: A B C D E F G H I J Water-cooled condenser Valvetocheckcondensationpressure Liquid receiver Pressure intake 5/16” SAE Liquid temperature probe…
-
32 | Weights, dimensions and clearances
Weights Standard Model Weight (kg) Standard Model Weight (kg) Standard Model Weight (kg) 10 115 P Series G Series 1250 300 R Series Dimensions and clearances Plan dimensions Dimensions (mm) Standard Model Scheduled maintenance (mm) Clearances (mm) Length Depth Height Front and side intake Front…
-
Plan dimensions
-
34 | Dimensions and clearances
Plenum and base frame (accessory) Various types of air distribution plenum and base frame are available as accessories for both the Under (U) and Over (O) versions of the unit. When installing plenums and base frame, it is advisable to place a gasket (rubber or similar material) of an adequate…
-
Dimensions and clearances plenum and plinth
Plan dimensions - standard model dimensions (mm) P series - Plenum and soundproofed duct section Length Depth Height 071 – 141 – 10 – 450/550 (lower plenum) – 251 – 30 – – 302 1410 361 – 461 – 422 – 512 – 80 – 110 1750 662 – 852 2300 932 – 160 2640 220 3495 P series - Free-cooling plenum * Length…
-
36 | Dimensions and clearances
Sizing the hole for the installation of the base frame in the finished floor surface P series Plinth plan dimensions - Dimensions (mm) 071- 141 – 10 – 20 Length Depth Tolerance A B C – 251 – 30 – – 302 1410 361 – 461 – 422 – 512 – 80 – 110 1750 662 – 852 2300 932 – 160 2640 3495 G series ventilated…
-
TMC Dimensions
Vertical Installation ( V ) Horizontal Installation ( H ) Standard models TMC 11 TMC 19 TMC 31 TMC 35 Length (A) mm 880 Depth (B) mm Height (C) mm V H V H TMC 55 TMC 2220 1100 TMC 63 TMC 1220 TMC 40 TMC 49 Weight Kg 3220 170 TMC Clearances Vertical Installation ( V ) Horizontal Installation ( H ) 37
-
As part of our ongoing product improvement programme, our products are subject to change without prior notice. Non contractual photos.