OPERATION AND INSTALLATION
Central ventilation appliance with heat recovery » LWZ 180 » LWZ 280 » LWZ 180 Enthalpie » LWZ 280 Enthalpie
-
CONTENTS | Special information
SPECIAL INFORMATION 12.3 Code��������������������������������������������������������������� 44 OPERATION 13. Appliance shutdown��������������������������������������� 44 1. 1.1 1.2 1.3 1.4 1.5 General information��������������������������������������� 29 Safety…
-
General information
ff This symbol indicates that you have to do something. The action you need to take is described step by step. 1.3 1. General information The chapters "Special information" and "Operation" are intended for both users and qualified contractors. The chapter "Installation" is intended for qualified…
-
Appliance description
The appliance can also be used in non-domestic environments, e.g. in small businesses, as long as it is used in the same way. Any other use beyond that described shall be deemed inappropriate. Observation of these instructions and of the instructions for any accessories used is also part of the…
-
Switching the appliance on Press the "HOME" and "OK" buttons simultaneously to activate the function block. The "padlock" symbol appears. Then you can wipe the programming unit clean without inadvertently changing any settings. Press the "HOME" and "OK" buttons simultaneously for two seconds to…
-
At times where there is no time program defined, the appliance
runs in set fan stage 2. P3: Bypass mode 4.5 0 Menu Display P1 - Pxx I1 - Ixx Pro Cod Description Parameter Actual values Programs Entry of the code for unlocking protected parameters and actual values ff To access the parameters, press the "MENU" button. The "HOME" button takes you…
-
P28
: Enable fan 4.5.3 Programs You can switch off the fans at any time via the programming unit menu, e.g. to deactivate ventilation if there is a fire. Pro P80: Day Monday Tuesday Wednesday Thursday Friday Saturday Sunday P83: M ode of backlighting Effect On Backlighting switched on OFF…
-
Maintenance, cleaning and care
Note At times where there is no time program defined, the appliance runs in set fan stage 2. Saturday, Sunday x 1 2 3 4 Maintenance, cleaning and care Maintenance by the user is limited to filter inspection and replacement required at certain intervals. 5.1 Example Monday - Friday 5. Time…
-
Troubleshooting
! 6. Troubleshooting Faults detected by the appliance are stored in actual values I70 to I79. The latest fault is also shown in the lower section of the standard display. If you cannot remedy the fault, contact your qualified contractor. To facilitate and speed up your request, provide the number…
-
Safety
INSTALLATION 7. Safety Only a qualified contractor should carry out installation, commissioning, maintenance and repair of the appliance. 7.1 General safety instructions We guarantee trouble-free function and operational reliability only if original accessories and spare parts intended for the…
-
Appliance description
9.2 Installation site When commissioning the ventilation unit, it is important to check and document in the commissioning log that combustion exhaust gases are not penetrating the dwelling in a quantity that is harmful to health. ! Material losses Never install the appliance outdoors. Commissioning…
-
10. Installation
10.1 Removing the front panel Remove the front panel before removing the appliance from the pallet, to avoid damaging the appliance. 2 ff Carefully raise the front panel by a small amount on the right-hand side. ff On the appliance, pull out the plug connecting the programming unit with the…
-
Material losses
When warm air meets cold surfaces, condensation can result. ff For outdoor air and exhaust air ducts, use vapour proof thermally insulated pipes. ff If the supply and extract air ducts are routed through unheated rooms, insulate these ducts as well. 10.4.2 Connecting air ducts to the appliance…
-
ff
Push the air duct over the air connector. 10.4.7 Supply and extract air vents Supply and extract air vents for the living space are available for wall or ceiling mounting. 1 When venting the kitchen, ensure that the extract air vent is fitted as far as possible from the cooker. D0000062520 3x 1…
-
Commissioning
D0000065180 ! ! Material losses Never operate the appliance without filters. ! Material losses Never operate the ventilation system if there are high levels of dust inside the building or outside in the immediate vicinity, as this could block the filter. Dust is created by cutting tiles or working…
-
12. Settings
When you enter a four-digit code, additional actual values become visible, which were hidden beforehand. 12.1 Parameter Note P6, P7, P8, P9: This parameter is displayed only if P5 = 0. P10, P11, P12, P13: T his parameter is displayed only if P5 = 1. P28: Delivered conditionOFF Description Code Unit…
-
P5
Fan operating mode P23 :Frost protection mode Use this parameter to switch between flow rate control and constant pressure control. Effect The appliance maintains a constant flow rate for both fans. The appliance operates with set flow rates P6 to P9. The appliance maintains a constant pressure…
-
Appliance shutdown
13. Appliance shutdown 12.2 Actual values Display I1 I2 I3 I4 I5 I6 I7 I8 I9 I10 I11 I12 I13 I14 I15 I16 I17 I18 I19 I20 I21 I22 I23 I24 I70-79 Description Bypass damper status Extract air temperature Relative humidity of extract air Filter service life Appliance software version Unit software patch…
-
Maintenance
D0000082556 1 ENGLISH 1 2 300° D0000063652 1 Wing screw ff To remove the heat exchanger from the appliance, undo the wing screw, which pushes the support bar against the heat exchanger from below. D0000040365 1 Eccentric bolt tightened (slot horizontal) 2 Eccentric bolt released ff Use a medium…
-
Troubleshooting
Checking the condensate drain Note The appliance will only function correctly if the condensate drain is working and is filled. ff Check the condensate drain at regular intervals – at least once every six months. Cleaning the air ducts Air ducts must be checked at regular intervals and cleaned if…
-
Disposal
www.stiebel-eltron.com Sensor resistance values Note When measuring with a multimeter, the resistance values serve only to identify faulty or incorrect sensors. Measuring with a multimeter is too imprecise to test for accuracy. Supply air Exhaust air Temperature [°C] –30 –20 –10 Sensor type PT 1000…
-
17. Specification
17.1 Dimensions and connections i13 105 g05 g04 g06 g03 D0000040353 23 d45 b01 105 b01 d45 g03 g04 g05 g06 i13 Entry electrical cables Condensate drain Outdoor air Exhaust air Extract air Supply air Wall mounting bracket 265 Diameter Diameter Diameter Diameter Diameter mm mm mm mm mm LWZ 180 LWZ 280…
-
Heizregister
-
17.3 Fan diagram
The graph shows the pressure drop for examples of air distribution systems. LWZ 180/LWZ 180 Enthalpie 0,57 125 0,45 0,40 100 0,34 0,36 75 0,29 0,25 0,23 50 0,17 0,06 0,03 0,09 0,06 0,03 100 0,05 0,07 125 150 0,09 175 0,20 0,16 0,12 D0000063739 25 X Y z 0,18 0,13 0,11 Air flow rate [m³/h] Average…