Инструкция на Рекуператоры воздуха Stiebel Eltron серии LWZ 5- 8 CS Premium
Центральные вентиляционные установки с рекуперацией тепла Stiebel Eltron серии LWZ 5 CS Premium, LWZ 8 CS Premium. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
Central ventilation unit with heat recovery
» LWZ 5 CS Premium » LWZ 8 CS Premium uuu
-
CONTENTS
SPECIAL INFORMATION 9.5 Cleaning the filter ballvalve [и 9.6 Replacing the anode 31 INSTALLATION 9.7 Checking the diaphragm expansion vessels 32 1, General information 3 10. Specification 3 1.1 Relevant documents 3 101 Dimensions and connections. 8 1.2 Information on the appliance 3 10.2 Connection…
-
SPECIAL INFORMATION | INSTALLATION
General information SPECIAL INFORMATION - Observe all applicable national and regional regulations and instructions during installation. - The appliance is not approved for outdoor installation. - Observe the requirements concerning the installation room (see chapter ,,Specification / Data table").…
-
Safety
Depending on the chosen test method and the extent to which this method differs from the test conditions defined in the first paragraph of this section, any deviations can be considerable. Additional factors that have an influence on the test values are the measuring equipment, the system…
-
Appliance description
As the appliance can produce negative pressure in the installation room, we recommend using a tightly sealing door between the installation room and the living space containing combustion equipment. lf, due to its use, the installation room is connected to the extract air system, you must also make…
-
Appliance description
The cross-countercurrent heat exchanger ensures that up to 90 % of the heat in the extract air is returned with the supply air into the living space. in addition, heat is extracted from the outdoor air by means of an aif source heat pump. The energy extracted from the outdoor air in the evaporator…
-
3.4.3 Frost protection for the cross-countercurrent heat
exchanger A heat exchanger in the path of the outdoor air flow preheats the outdoor air, and thus prevents the cross-countercurrent heat exchanger from freezing up. 3.4.4 Buffer mode for air heating На heating system with а low draw-off rate and little thermal capacity is used, e.g. air heating coil…
-
Outdoor/exhaust air connection with air hose
4) (ZLZLZZLZILATL LLL LLL \ Aad т g | РУХНЕТ А | 2255 N \ Х zi АХ 2650 PRK Connecting outdoor air to geothermal heat exchanger Decco seta 1 Filter box осоки 766 Outdoor air mechanical ventilation connection option 4 $on0ea1 936 1 “Filter box 4.2 Air routing Prevent air stream ,short circuits". The…
-
The floor between the installation room and living areas must
have carefully applied anti-vibration separation. Ensure that no pipes are routed on or in the wall and that the air ducts have anti-vibration separation. if the unit installation room is included in the building ventilation system, the design must include an extract air vent and supply air vent for…
-
4.4 Electrical installation
Permission must be obtained from your local power supply utility. WARNING Electrocution Carry out all electrical connection and installation work in accordance with national and regional regulations. WARNING Electrocution The appliance contains inverters (e.g. variable speed compressors, high…
-
5. Installation
5.1 Siting the function module Material losses Never tilt the appliance excessively. Contacts between the casing and the floor can damage the paintwork. | Desooowsas | 1 Support screws of the fascia framework 2 Fascia fixing screws The fascia and fascia frame that are fitted to the front of the ар…
-
Outdoor air mechanical ventilation connection option
an Note Observe the minimum clearance at the back of the appliance. See chapter “Preparations / Installation site / Minimum Clearances”, 24.6%, 01 ща 1 Upper front panel 2 Cross-courtercurrent heat exchanger 3 Outdoor air filter cassette > Remove the upper front panel. > Undo the screws on the cover…
-
5.2 Installing the cylinder module
> Undo the screws underneath the pallet with which the cylinder module is secured to the pallet. Material losses Never tilt the cylinder module excessively. Contacts bet~ ween the casing and the floor can damage the paintwork. 76 04.95 1598 1 Captive nut on the bottom of the cylinder module 2…
-
Pushing the cylinder module towards the function module
> Push the cylinder module carefully towards the function module, so that the rear r.h. adjustable foot of the cylinder module is near the recess in the joining bracket. 5.3 Connecting modules Cylinder temperature sensor and anode cable > Remove the cable tie that tie together the electrical cables…
-
Fitting the horizontal locking bracket to the front
> Connect the function module and cylinder module at the front by securing one horizontal locking bracket each at the top and bottom using screws. Material losses Before filling, tighten the screws only lightly so that the paint finish is not damaged when the cylinder module moves down during…
-
Making the push-fit connection
The connector must be in its relaxed position before the pipe is inserted. In this position, there is a small gap between the screw cap and connector body. 2 1 ый 7 =) 3 a 1 Retainer 2 Screw cap 3 Gap between screw cap and connector воду 4 Connector body $ =) —a | = 8 Pipe dizmeter mm 2 A__…
-
»Heating return” connection Note
3 ae = ay Suitable appliances for water softening, as well as for filling and flushing heating systems, can be obtained via 4 6 trade suppliers. 3 Я 2 2 Minimum flow rate 1 5 The appliance is designed in such а way that no buffer cylinder Л »Heating return” connection Plug-in connector Flanged pipe…
-
Safety valve
The appliance is a sealed unvented OHW cylinder, Provide the appliance with a pressure relief valve. > install a type-tested safety valve in the cold water supply line. The response pressure of the safety valve must be below ог equal to the permissible operating pressure of the DHW cylinder. The…
-
WARNING Electrocution
Only components that operate with safety extra low voltage (SELV) and that ensure secure separation from the mains voltage supply may be connected to the low voltage terminals of the appliance. Connecting other components can make parts of the ap- pliance and connected components live. > Only use…
-
‘Оооо
Ем Contact for Power-OFF command by the power supply wtitity {optioe) Steuerung Control MiAUF Mixer open mi zu Mixer close WK? Healing circuit 2 pump This commection can only be used if the “UMV" connection is not used. ком Cooling (options: Gutput {230 V) to activate the cooling бух OK…
-
AOL Oe
1 Sensor well for the cylinder temperature sensor (economy mode/buffer mode) 2 Sensor well for the cylinder temperature sensor (Comfort) 26,06 OL 9954 1 Aperture in the thermal insulation for the sensor lead 2 Clamp (prevents the cylinder temperature sensor from slipping out) 3 Cylinder temperature…
-
5.9.9 CAN BUS
Connecting the external programming unit Note i Check whether the room in which the external programming unit is installed receives a lot of warmth, for example sunlight. if it is warmed from outside, the device might regulate the flow temperature downwards. As a result, the temperature in other…
-
> Refit the protective caps on the fill valves
Determine the fill pressure Volume of the diaphragm expansioe vessels integrated into the | 15 appliance Expansion vessel pre-charge pressure (Pa) _bar___ 0.75 ifthe height difference Ah between the highest point of the heating system and the diaphragm expansion vessel is no more than 6 m, the…
-
> Determine the .PRESSURE HTG CIRC” value for one of the
three favourites, For this, navigate from the default display to the FAVOURITES” parameter. Note i Proceed carefully when filling as the “PRESSURE HTG CIRC” value is only updated every 10 seconds. If you have determined the value not in association with one of your favourites but instead by calling…
-
> Connect the bus cable to the programming unit, The BUS
cable must run upwards with the jumper in the Ih. side. > Insert the fascia from the top into the fascia frame. The fascia has one screw each on the |.В. and rh. side. > Tighten these screws to secure the fascia to the fascia frame. 5.12 Outdoor air and exhaust air hose installation Note rf A If…
-
Commissioning
> Pull the external hose and the thermal insulation below it over the connector. > Tuck the thermal insulation into the outer hose in such a way that the thermal insulation is no longer visible. | Doeuces esse > Seal the transition from the external hose to the connector with the self-adhesive…
-
Commissioning
- Has the condensate hose been routed correctly? - Was a vessel placed beneath the safety valve discharge hose? 6.1.2 Ventilation system ~ Have the air ducts been installed correctly and sealed if required? ~ Have all air connections been designed correctly? 6.1.3 Heat pump ~ Have the insulated air…
-
Appliance shutdown
7. Appliance shutdown WARNING Injury There will be no ventilation if the appliance is taken out of use. This may result to the development of mould fun- gus and damage to the building. > Prevent the appliance being out of use for prolonged periods. Note Prevent the appliance being shut down if it is…
-
8.3 Circulation pump
Hf the LED on the heating circuit pump flashes red even though there is an active heat demand, disconnect the power supply for 30 seconds. If the circulation pump does not run after switching the power supply back on, replace the circulation pump. 8.4 Fault messages in the programming unit Note a В…
-
9.2 Cleaning the outdoor air filter
The outdoor air filter is fitted downstream of the cross-countercurrent heat exchanger, #4541) ХХ. 1 Upper front panel 2 Cross-countercurrent heat exchanger 3 Outdoor air filter cassette > Pull out the cross-countercurrent heat exchanger. > Grasp the outdoor air filter cassette by the grip holes and…
-
> Spray water across the evaporator fins
> Remove the water from the appliance using a wet suction device. > Remove contaminants and blockages. Note Check the condensate drain regularly, at least once a year. 9.4 Cleaning the condensate drain Check the condensate drain regularly. > Remove the evaporator cover {see chapter ,,Cleaning the…
-
97 Checking the diaphragm expansion vessels
2% 0% 91 own? 1 Fill valve of the expansion vessel > Remove the protective caps from the fill valves on the expansion vessels. own Lact 1 Cap valve > Close the cap valve and depressurise the expansion vessel by draining the cap valve. > Check the pre-charge pressure of the exparision vessel using а…
-
10. Specification
10.1 Dimensions and connections 812 +430 < ob) fee гы - bl a й 2 = | и, Е ae LWZ 5 CS Premium LWZ 8 CS Premium bol Entry electrical cables < Cold water inlet Diameter та 2 22 <06 DHW outlet Diameter mm _ Entry DHW circelation 12 _Salety маме drain Diameter fren Solar Во Diameter men Solar return…
-
10.2 Connection examples
Example 1: Without power-OFF periods MFG МР Steuverung 002 хр муз 1..2 8-8: 3 7 $4 MOD Het” ВБР | Н T | i i ' i : Н i i i i i : ' 1 ro ь т # j \ Н 55) } > i } i } i : i ААА |i ad а |! H 1 i ! i Е : H LILZL3 N PE Е NPE М NPE $ WWE - ФОНЕ «И DUPE - ЗОНЕ ЗУМ UNPE - $04; 230% ё we Heat pemp / Fan MEG…
-
INSTA
Speci LLATION fication 10.5 Wiring diagram Wiring diagram key AAO? Integral control unit RFo6 Ferrite core ring AAOG Inverter $01 Reset button AA06 Programming unit XDO1 Compressor/HP fan power supply BFoi Heating circuit flow rate sensor XD02 Instantaneous water heater (MFG) power supply 8101…
-
xn
— Pe wi www.stiebel-eltron.com 36 | LWZ 5/8 CS Premium
-
БЕЯ Е
-
10.6 Output graph
-
10.7 Available external head of the circulation pump
& 8 co oA 1.2 1,4 16 18 X Flow rate [т] 2 Pump rate 85 % У Pressure [hPa] 3 Pump rate 65 % 1 Pump rate 100 % & Pump rate 45 % 10.8 Fan curve + 20 220 оо сок 2009 80 100 1% — Application range 0.30 Specific power consumption 0.30 Wh/m? X — Аи flow rate [m/h] 0.35 Specific power consumption 0.35 Whim?…
-
10.9 Data table
The output data refers to new appliances with clean heat exchangers, The power consumption of the integral auxiliary drives represents the maximum value and may vary subject to operating point. The power consumption of the integral auxiliary drives is included in the output details of the appliance…
-
Reon Вод
Refrigerant charge № 295 235 CO, equivalent {CO,e) t 6.16 6.26 Global warming patertial of the refrigerant (GWP100) 2088 2088 й _ в ХВ Filter class, extract ам 150 Coarse > 60% (G4) — 150 Coarse > 50% (G4) Filter class, supply air ePM10 > 50 % (M5) еРМ10 > 50% (MS) Filter class, ogtdoor ait 150…