Инструкция на Тепловые насосы воздух/вода Stiebel Eltron серии WPL 33 HT
Тепловые насосы воздух/вода Stiebel Eltron серии WPL 33 HT. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
OPERATION AND INSTALLATION
Air | water heat pump »» WPL 33 HT 290987-40278-9266_WPL_33_HT_en.indd 1 10.10.2017 14:38:57
-
CONTENTS
SPECIAL INFORMATION OPERATION 1. 1.1 1.2 1.3 1.4 1.5 General information�����������������������������������������3 Relevant documents�������������������������������������������� 3 Safety instructions����������������������������������������������� 3 Other symbols in this…
-
Special information
General information SPECIAL INFORMATION OPERATION The appliance may be used by children aged 8 and older and persons with reduced physical, sensory or mental capabilities or a lack of experience and know-how, provided that they are supervised or they have been instructed on how to use the appliance…
-
Operation
Safety 1.3 Other symbols in this documentation mestic environments, e.g. in small businesses, as long as it is used in the same way. Note General information is identified by the adjacent symbol. ff Read these texts carefully. Any other use beyond that described shall be deemed inappropriate.…
-
Operation
Settings Comprises all components and safety equipment required for operation. Filled with non-combustible safety refrigerant. ff Once a month, check that the condensate drain is working correctly (visual inspection). When doing so, check for water collecting below or next to the appliance. See…
-
Safety
Note Even when the condensate is draining away correctly, it is not unusual for water to drip from the appliance onto the floor. If you cannot remedy the fault, notify your qualified contractor. To facilitate and speed up your request, provide the number from the type plate. The type plate is…
-
Sound emissions The appliance is louder on the air intake and air discharge sides than on the two enclosed sides. Take the following information into account when selecting the installation location. Note For details regarding the sound power level, see chapter "Specification / Data table". 9.1.1…
-
Example: Foundations with recess
9.2.2 Indoor installation D0000023464 800 d02 d01 ≥300 2 1 Air discharge 2 Air intake 3 Main wind direction 4 Entry supply lines d01 Heat pump flow d02 Heat pump return ff Ensure that the foundations offer an adequate recess. ≥500 ≥500 ≥500 1390 D0000019242 ≥1000 Example: Installation on foundations…
-
ff
Protect the flow and return lines against frost with sufficient thermal insulation. The thermal insulation must be at least twice as thick as the diameter of the pipe. Provide thermal insulation in accordance with applicable regulations. ff Isolate the installation surface around the heat pump by…
-
Buffer cylinder 10.2 Outdoor installation A buffer cylinder is recommended to ensure trouble-free appliance operation. ff Pay attention to the air discharge direction. ff Position the standard appliance on the prepared substrate. The buffer cylinder provides hydraulic separation of the volume flows…
-
10.3 Indoor installation
1 2 ff Position the standard appliance on the prepared substrate. ff Remove the knock-out at the top in the appliance cover panel. 26_03_01_1687_ Material losses Observe the torque of the flow meter (see chapter “Specification/Data table”) when carrying out the following procedure. 1 Heating return…
-
10.6 Filling the heating system
10.7 Minimum flow rate Heating water quality The minimum flow rate and the defrost energy must always be assured (see chapter “Specification / Data table”). Carry out a fill water analysis before filling the system. This analysis may, for example, be requested by the relevant water supply utility.…
-
ff
Install the open heating circuit(s) in the lead room (room where the external programming unit of the heat pump control unit is installed, such as in the living room). The individual room can then be controlled either with the external programming unit or indirectly by adjusting the heating curve or…
-
Electrical connection
11. Electrical connection 11.4 Making the electrical connections ff Observe chapter "Preparing the electrical installation". 11.1 General WARNING Electrocution ff Before working on the appliance, isolate it from the power supply at the control panel. 1 The connection must only be carried out by a…
-
Fitting casing parts
12. Fitting casing parts 12.2 Fitting casing parts for indoor installation Before fitting the casing parts, seal the appliance by affixing plastic sheets. The plastic sheets are supplied with the casing parts. 12.1 Fitting the casing sections for outdoor installation Side panel 2 Cover 3 Front panel…
-
Routing the air hoses
ff Manipulate the ends of the air hoses to fit the oval shape of the connectors on the cover and the hose connection panels or wall outlets. ff Secure the plastic sheets by pressing them onto the appliance. Seal the apertures around the hooks using adhesive strips with slits. The adhesive strips…
-
Routing the air hoses
D0000070816 D0000070819 13.1 Fitting the air hoses ff With the sound-optimised hoses (LSWP 560-4 S), pull the sheet over the connector. ff With the sound-optimised hoses (LSWP 560-4 S), seal the sheet to the connector using the fabric tape provided. D0000070818 D0000070821 ff Push the inner hose…
-
Commissioning
ff Pull the outer hose over the connector. 1 ff Secure the hose using the oval hose clip provided and seal it. 13.2 Insulating the wall outlets Prevent cold bridges forming between the wall outlets to be installed on site and the brickwork. To prevent condensation forming in the brickwork, insert…
-
Appliance shutdown
Increase the “HEATING CURVE” parameter, if the room temperature is not high enough when outside temperatures are low. If the "HEATING CURVE" parameter has been raised, in the case of high outside temperatures, adjust the zone valve or thermostatic valve in the lead room to the required temperature.…
-
Troubleshooting
16.1 Elements on the IWS HT WP - Typ The IWS HT (integral heat pump controller) helps you to troubleshoot if the fault cannot be identified using the WPM. D0000057055 ON 4 ff Check whether the DIP switch is set correctly. 1 DIP switch (BA) ff Check whether the DIP switch (BA) is set correctly. BA…
-
Maintenance
17. Maintenance 1 We recommend a regular inspection (to establish the current condition of the system), and maintenance if required (to return the system to its original condition). 2 1 High limit safety cut-out reset button 2 Electric emergency/booster heater ff Reset the high limit safety cut-out…
-
D0000035034
Installation Maintenance D0000035005 D0000035007 ff Cut a recess into the thermal insulation around the perforation. D0000035006 ff Then remove the side cover panel. ff Clean out the front section of the condensate pan. ff Clear all blockages from openings in the separating plate of the condensate…
-
18. Specification
18.1 Dimensions and connections 18.1.1 Outdoor installation i21 i21 D0000016772 g02 g01 WPL 33 HT g01 g02 i21 Air intake Air discharge Entry supply line www.stiebel-eltron.com 290987-40278-9266_WPL_33_HT_en.indd 23 WPL 33 HT | 23 10.10.2017 14:39:33
-
1162 18.1.2 Indoor installation 800 d44 1390 g01 g02 D0000016774 b01 e02 203 289 e01 WPL 33 HT b01 d44 e01 e02 g01 g02 Entry electrical cables Condensate drain outlet Heating flow Heating return Air intake Air discharge Male thread Male thread Nominal diameter Nominal diameter G 1 1/4 G 1 1/4 DN 560…
-
www.stiebel-eltron.com
-
18.2 Wiring diagram
-
Bus
-
18.3 Output diagrams
Heating output -20 -15 -10 -5 D0000034154 4 X Outside temperature [°C] Y Heating output [kW] 1 min. W35 2 max. W35 3 min. W55 4 max. W55 28 | WPL 33 HTwww.stiebel-eltron.com 290987-40278-9266_WPL_33_HT_en.indd 28 10.10.2017 14:39:35
-
18.4 Data table
-
WPL 33 HT
Electrical data Compressor fuse/MCB Control unit fuse/MCB MCB/fuse protection, emergency/booster heater Frequency Compressor phases Control unit phases Emergency/booster heater phases Rated voltage, compressor Rated voltage, control unit Rated voltage, emergency/booster heater Starting current…
-
GUARANTEE | ENVIRONMENT AND RECYCLING
Guarantee The guarantee conditions of our German companies do not apply to appliances acquired outside of Germany. In countries where our subsidiaries sell our products a guarantee can only be issued by those subsidiaries. Such guarantee is only granted if the subsidiary has issued its own terms of…
-