Инструкция на Инверторные тепловые насосы Sinclair серии S-THERM 4
Инверторные тепловые насосы Sinclair серии S-THERM 4-го поколения: GSH-60IRB + GSH-60ERB, GSH-80IRB + GSH-80ERB, GSH-100IRB + GSH-100ERB. Руководство пользователя.
Смотрите также: Коды ошибок: 20 кодов →
Загружаем документ…
Текст инструкции
-
SPLIT INVERTER
AIR TO WATER HEAT PUMPS GSH-80IRB + GSH-80ERB GSH-100IRB G+ GSH-100ERB G
-
“Original instructions”
-
To Users
Thank you for selecting Sinclair’s product. Please read this instruction manual carefully before installing and usingthe product, so as to master and correctly use the product. In order to guide you to correctly install and use ourproduct and achieve expected operating effect, we hereby instruct as…
-
UNIT CONTROL
-
1 Integral Control Concept
1.1 Control Principle Diagram Control Diagram 2
-
1. The outdoor temperature is detected by the sensor installed at fins of the finned heat exchanger,
which is mainly used to control the initialization steps of the fan and the electrostatic expansion valve and also limit the maximum running frequency of the compressor. When this sensor fails, the main board will detect it and deliver this error message to the controller and then the unit will fail…
-
When this sensor fails, this error will be displayed at the controller and the unit will continue to operate. 10. The optional water temperature is detected by the sensor installed at the outlet pipe of the optional E-heater, which is mainly used to control the supply water temperature. When this…
-
Items 15~ 20 are control parameters input by the filed installed equipment
1.2 Control Flowchart 2 Main Control Logics 2.1 Cooling 2.1.1 Control to the Compressor When the unit is controlled by the leaving water temperature, the operating frequency of the compressor will be adjusted by the temperature difference in the way that it increases as the temperature difference…
-
freeze protection temperature, the compressor will drop its operating frequency until it reaches the
minimum operating frequency. Then if it is still detected that the leaving water temperature is lower than the freeze protection temperature, the main unit will stop as per the shutdown frequency but the water pump keeps normal operation. When it is detected that the leaving water temperature of the…
-
range of the main unit but the actual water tank temperature is lower than the maximum value of the
water heating range of the main unit, the auxiliary electric heater of the main unit will run depending on the temperature difference. If the actual water tank temperature is higher than the maximum value of the water heating range of the main unit, the water tank heater will start. At any time…
-
2.6 Control to the Fan
Under the cooling mode, the operating frequency of the fan is adjusted according to pressure at the high pressure side. Under the heating or water heating mode, the operating frequency of the fan is adjusted according to the pressure at the low pressure side. During defrosting, the fan stops and…
-
(5) Communication Error
When the indoor unit main board or drive board does not receive correctly any data from the unit main board, all loads will stop. 3 Controller 3.1 General (This picture is just for reference) This display panel uses the capacitor touch screen for input operation. The valid touching area indicates…
-
3.1.1 Homepage
[Notes] ●The “ON/OFF” icon will turn to green when the control is turn ed on. ●When the control mode is “Room temperature”, the temperature displayed at the upper right corner indicates the remote room temperature; when the control mode is “leaving water temperature”, it indicates the leaving water…
-
3.1.2 Menu Page
Above the menu, the corresponding icon will be displayed based on the mode and status of the controller. Menu Page No Item Description 1 Current mode Current mode 2 Data Current data 3 Time Current time 4 Function setting Go to the user setting page. 5 Parameter setting Go to the parameter setting…
-
●The “Cooling” mode is unavailable to the heating only unit
●The “Hot water” mode is unavailable to the heating only unit. ●The “Heating + Hot water” (“Hot water” takes the priority) is unavailable to the mini chiller. ●The “Hot water + Heating” (“Heating” takes the priority) is unavailable to the mini chiller. ●The “Cooling + Hot water” (“Hot water” takes…
-
●As shown in the figure below, the error icon will appear at the upper left corner when any error exists. Error Icon [Notes] ●At any other page, where there is no operation in 10 minutes, the display panel will back to the menu page. 3.1.3 Backlight Among the general setting page, when “Back light”…
-
3.2.2 Function Setting
[Operation Instructions] ★1. At the menu page, by touching “FUNCTION”, it will go to the function setting page as shown in the figure below. FUNCTION Setting Page ★2. At the function setting page, by touching the page turning key, it will access to the last or next page. When setting is finished, by…
-
8 9 Item Weather depend Weekly timer Holiday release Range Default On/Off Off On/Off Off On/Off Off Remarks When the water tank is unavailable, it will be reserved 1. The disinfection date ranges from Monday to 10 Disinfection On/Off Off Sunday. Saturday is defaulted. 23:00. 2. The disinfection time…
-
●For the heat pump, the “ Cool” mode is allowed; for the heating only unit, “ Cool+ Hot water” and
“Cool” are unallowable. ●This setting can be memorized upon power failure. 3.2.2.2 Fast Hot Water [Operation Instructions] ★At the function setting page with the unit turned off, by touching “ Fast hot water”, the display panel will go to the corresponding setting page, where desired option can be…
-
Timer for Quite Mode
★ 3. This setting will be saved by touching the corner at the upper right corner. [Notes] ●It can be set under both ON and OFF statuses, but will work only when the main unit is turned on. ●When it is set to “On”, it will automatically back to “Off” when the main unit is turned off; while it is set…
-
3.2.2.7 Weekly Timer
[Operation Instructions] ★1. At the function setting page, by touching “Weekly timer”, it will go to the setting page as shown below. ★2. At the “Weekly timer” setting page, as shown in the figure below, the weekly timer can be set to “On” or “Off”. ★3. At the “Weekly timer” setting page, by…
-
3.2.2.9 Disinfection
[Operation Instructions] ★At the function setting page, access to “ Disinfection” setting page. ★At the “Disinfection” setting page, it can select the disinfection clock, disinfection temperature and disinfection week and the corresponding setting page will pop up at the right side. ★Then, this…
-
the corresponding water temperature; “Period” is used to for time setting. After that, by touching the “Save” icon, all settings will be saved. [Notes] ● When “Clock timer” has been set and “Hot water” mode is involved, in this case, if “Water tank” is changed to “Without”, “Hot water” will be…
-
●When “Weekly timer”, “Preset mode”,“Clock timer” “Temp. timer” have been set at the same time,
then the latter takes the priority. ●This setting is valid only when the unit is turned on. ●Under the “Cool” or “Cool+Hot water” mode, the setting targets at “WT-Cool”; while under the “Heat” or “Heat+Hot water” mode, the setting targets at “WT-Heat”. ●When start time of period 2 is the same as…
-
a window will pop up, saying “ Please turn off the system first!”
● “Floor debug”, “Disinfection”, and“Holiday mode” cannot be activated at the same with this function. When doing so, a window will pop up, saying “ Please disable the emergen. mode!”. ● Upon power failure, “Emergen. mode” will back to “Off”. 3.2.2.13 Holiday Mode [Operation Instructions] ★At the…
-
3.2.2.14 Preset Mode
[Operation Instructions] ★ At the function setting page, select “Preset mode” and go to the corresponding setting page. ★ At the time period setting page, each time period can be set to “Valid” or “Invalid”. ★ The option “Mode” is used to preset the mode; “WOT-Heat” is used to set the leaving…
-
● It can be performed only when the unit is turned off
3.2.2.16 WiFi Reset [Operation Instructions] ★At the function setting page, by touching “WiFi”, a choice box will pop up, where by touching “OK” , the WiFi setting will be reset, and by touching “Cancel” the choice box will quit and WiFi will not be reset. 3.2.2.17 Reset [Operation Instructions] ★At…
-
default value also will change as the corresponding condition changes
● All parameters will be memorized upon power failure. Parameter Setting No Full Name Range Range (℃ ) (°F) WOT-Cool 7~25℃ 45~77℉ 18℃/64℉ WOT-Heat 20~60℃ 68~140℉ 45℃/113℉ RT-Cool 18~30℃ 64~86℉ 24℃/75℉ RT-Heat 18~30℃ 64~86℉ 20℃/68℉ T-water tank 40~80℃ 104~176℉ 50℃/122℉ ΔT-Cool 2~10℃ 36~50℉ 5℃/41℉…
-
will automatically save this change and this change will remain upon power failure
Do not modify any commissioning parameter except the approved qualified servicemen, as it would give birth to adverse effects to the unit. Commissioning Function Setting No Item Range Default 1 Ctrl. state T-water out/T-room T-water out Description When “Remote sensor” is set to “ With”, it can be…
-
Item
Range Default Description available and the unit is OFF. 16 Gate-Ctrl. On/Off Off Current limit: it ranges from 0 to 50A and the 17 C/P limit Off/Current limit/Power limit default is 16A. Off Power limit: it ranges from 0.0 to10.0kW and the default is 3.0kW. Address Refri. recovery Gate-Ctrl memory…
-
3.2.4.2 2-Way valve
[Operation Instructions] ★ At the commissioning parameter setting page, by touching “Cool 2-Way valve” or “Heat 2-Way valve”, the control panel will access to the corresponding setting page. [Notes] ●Under “Cool”, or “Cool + Hot water” mode, “Cool 2-Way valve” will decide the status of the 2-way…
-
●When “Water tank” is set to “Without”, the “Air + hot water” mode is unavailable
●When “Floor debug” and “Emergen.mode” have activated, function of the thermostat will be invalid. ●When “Thermostat” is set to “Air” or “ Air + hot water”, timer function will be disabled and the unit will run based on the mode set by the thermostat. Meanwhile, mode setting and On/Off operation…
-
Under the “Heat + Hot water” mode, the other thermal only works for space heating, and the electric
heater of the water tank works for water heating. In this case, the 2-way valve is controlled base d on the setting of the control panel, and the 3-way valve will always turn to space heating system. During heating operation, the water pump of the heat pump unit will be stopped; however, during…
-
compressor has run for four minutes and TOptional Water Temp is equal to or lower than WOT-heat–Δt2
3.2.4.8 Remote Sensor [Operation Instructions] ★At the commissioning parameter setting page, by touching “Remote sensor”, the control panel will access to the corresponding setting page, where it can be set to “With” or “Without”. [Notes] ●This setting will be memorized upon power failure. ●Only…
-
segment” can be set
Displayed Name Range Default Accuracy Floor debug switch Floor debug On/Off Off / Quantity of segments Segments 1~10 1 1 25~35℃/ 25℃/ 77~95℉ 77℉ 12~72 hours 0 2~10℃/ 5℃ / 36~50℉ 41℉ No. Full Name Temperature of the first segment Duration of each segment Temperature difference of each segment Period…
-
response to any touching operation except the ON/OFF operation, with a window popping up, saying
“The force-mode is running!”. In this case, by touching ON/OFF, “Force mode” will quit. [Notes] ●This function is allowed only when the unit has just repowered and not turned on. For the unit which once has been put into operation, this function is unavailable, alerting “Wrong operation!”. ● It will…
-
★At the commissioning parameter setting page, by touching “Current limit”, it can be set the address. [Notes]: ● It is used to set the address of the control panel for being integrated to the centralized control system. ● This setting will be memorized upon power failure. ● The setting range is…
-
★At the commissioning parameter setting page, by touching “PARAM.”, it will access to the pages as
shown below. Page of Commissioning Parameters ★At this page, select the desired option and then go to the corresponding page. ★After that, by pressing “OK”, this setting will be saved and then the unit will run based on this setting; or by pressing “Cancel”, this setting will not be saved and quit.…
-
the figure below
VIEW Page 3.2.5.1 Status Viewing [Operation Instructions] ★1. At the “VIEW” page, by touching “Status”, it is able to view status of the unit, as shown in the figure below. Status View Page 36
-
Viewable Status
No Full Name Displayed Name Status Compressor On/Off 1 Status of the compressor 2 Status of the fan Fan On/Off 3 Status of the unit Unit status Cool/Heat/Hot water/Off 4 Status of the water pump HP-pump On/Off 5 Status of the water tank heater Tank heater On/Off 6 Status of the 3-way valve 1 3-way…
-
Defrosting temperature T-defrost 5 Entering water temperature of the plate type heat exchanger T-water in PE 6 Leaving water temperature of the plate type heat exchanger T-water out PE 7 Leaving water temperature of the auxiliary heater 8 Water tank temperature T-tank ctrl. 9 Floor debug target…
-
Full Name
Displayed Name Code 7 Fan error Outdoor fan EF 8 High pressure protection High pressure E1 9 Low pressure protection Low pressure E3 10 High discharge protection Hi-discharge E4 11 Capacity DIP switch error Capacity DIP c5 ODU-IDU Com. E6 Drive-main com. P6 IDU Com. E6 HI-pre. sens. Fc Temp-HELW F9…
-
Full Name
Displayed Name Code 32 Communication error with the drive board Driver Com. P6 33 Driver resetting Driver reset P0 34 Compressor overcurrent Com. over-cur. P5 35 Overspeed Overspeed LF Current sen. Pc 36 Current sensing circuit error or current sensor error 37 Desynchronization Desynchronize H7 38…
-
● The error log can accommodate up to 20 pieces of error. Name and occurrence time are available for
each error. ● When error log exceeds 20, the latest will supersede the earliest. 3.2.5.5 Version Viewing [Operation Instructions] ★ At the “VIEW” page, by touching “Version”, the control panel will go to the version view page, where it is able to view both the program version and protocol version.…
-
General Settings
No Item Range Default Remarks 1 Temp. unit ℃/°F ℃ / 2 On/Off memory On/Off On / 3 Beeper Enter On / 4 Back light Lighted/Energy save Energy save “Lighted”: the control panel will always light on. “Energy save”: When there is no touching operation in 5 minutes, the control panel will be lighted off…
-
3.3 Intelligent Control
[Notes]: ● Make sure the smart phone or tablet computer adopts standard Android or Ios operation system. For detailed version, please refer to the APP. ● The Wi-Fi function doesn’t support Chinese Wi-Fi network name. ● The devices can be connected and controlled only in Wi-Fi and 4G hotspot modes. ●…
-
★ 2. Open Ewpe Smart APP and click “Sign up” for registration
-
★ 3. Except sign in in the prompt interface, you can also enter the homepage and click the profile
picture at the left upper corner to sign in. 45
-
4. Click "+" at the right upper corner of homepage to add device. 46
-
After selecting “ATW Heat Pump”, the APP interface will provide relevant operation instructions
-
Reset the air conditioner (refer to the operation instructions in APP interface) and click “Next” to add home appliance automatically (Wi-Fi password shall be input). Or after setting and energizing the air conditioner, click “Add appliance manually” at the right upper corner to select the wireless…
-
3.3.2 Setting of Main Functions
★ 1. Set mode and temperature. 49
-
★2. Click Func at the left lower corner in device operation interface to enter advanced settings 50
-
3.3.3 Setting of Other Functions
Click the profile picture at the left upper corner of homepage and set each function in the following menu. 3.3.3.1 Home management Click “Home management” to create or manage family. You can also add family members according to the registered account. 51
-
3.3.3.2 Help
Click “Help” and view the operation instructions of the APP. 53
-
3.3.3.3 Feedback
Click “Feedback” to submit feedback. 54
-
NOTE CONCERNING PROTECTION OF
ENVIRONMENT This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal…