USER´S MANUAL
MONOBLOCK INVERTER AIR TO WATER HEAT PUMP SMH-60IRB SMH-100IRB SMH-100IRB-3 SMH-160IRB
-
To Users
Thank you for selecting Sinclair product. Please read this instruction manual carefully before installing and using the product, so as to master and correctly use the product. In order to guide you to correctly install and use our product and achieve expected operating effect, we hereby instruct as…
-
Safety Notices (Please be sure to abide )
Do not install the control where it is damp or exposed to direct sunlight. Once the air conditioning unit is installed where possibly subject to electromagnetic interference, shielded twisted pairs should be used as signal lines and other communication lines. Be sure communication lines are wired to…
-
1. General
(This picture is just for reference) This display panel uses the capacitor touch screen for input operation. The valid touching area indicates the black rectangle when the display panel lights off. This control panel is of high sensitivity and will response to unexpected click by the foreign matters…
-
Icon
Description Icon Description Heating Floor commissioning Cooling Floor commissioning error Hot water Card out Heating + Hot water Defrosting Hot water + Heating Holiday Cooling + Hot water WiFi Hot water + Cooling Back Quiet Menu page Sanitation Save Emergency Error [Notes] ●The “Cooling” mode is…
-
2. Operation Instructions
2.1 ON/OFF [Operation Instructions] At the menu page, by touching ON/OFF, the unit will be turned on/off. [Notes] ●It is defaulted to be OFF upon first power-on. ●ON/OFF operation will be memorized by setting “On/Off Memory” to be “On” at the “GENERAL.” setting page. That is, in case of power…
-
Function Setting
No Item Range Default Remarks Heat 1. When the water tank is unavailable, then only “Cool” and “Heat” are available. 2. For the heating only unit, only "Heat" mode, “Hot water”, and “Heat + hot water” are available. 3. It is defaulted to be “Heat” for the heat pumps and heating only units and “Cool”…
-
●The default mode is “Heat” upon first power-on
●Mode setting is allowed only when the unit is turned off, otherwise a dialog box will pop up, saying “Please turn off the system first!” ●When the water tank is unavailable, only ‘Heat” and “Cool” mode are allowed. ●When the water tank is available, “Cool”, “Heat”, “Hot water”, “Cool+ Hot water”…
-
to “Hot water”
●It will be memorized upon power failure. ●This function is unavailable to the heating only unit and the mini chiller. 2.2.5 Quiet Mode [Operation Instructions] At the function setting page with the unit turned off, by touching “Quiet mode”, there will be a choice box, where “Quiet mode” can be set…
-
●It works under the “Cool” or “Heat” mode. Under the “Cool +Hot water” or “Heat +Hot water” modes, it works only when the current mode is “Cool” or “Heat”. Under the “Hot water” mode, it doesn’t work. ●Temperature setting relative to the cooling mode is unallowed to the heating only unit. ●It will…
-
2.2.9 Disinfection
[Operation Instructions] 1.At the function setting page, access to “Disinfection” setting page. 2.At the “Disinfection” setting page, it can select the disinfection clock, disinfection temperature and disinfection week and the corresponding setting page will pop up at the right side. 3.Then, this…
-
● When “Clock timer” has been set and “Hot water” mode is involved, in this case, if “Water tank” is changed to “Without”, “Hot water” will be automatically switched to “Heat”, and “Cool/Heat + Hot water” will be switched to “Cool/Heat”. ● When “Weekly timer” and “Clock timer” have been set at the…
-
●When “Weekly timer”, “Preset mode”,“Clock timer” “Temp. timer” have been set at the same time, then the latter takes the priority. ●This setting is valid only when the unit is turned on. ●Under the “Cool” or “Cool+Hot water” mode, the setting targets at “WT-Cool”; while under the “Heat” or…
-
2.2.13 Holiday Mode
[Operation Instructions] At the function setting page, select “Holiday mode” and set it to “On” or “Off”. [Notes] ● This function can be activated only when the unit has been turned off, otherwise a prompt dialog box will pop up, saying “Please turn off the system frist!”. ●When “Holiday mode” has…
-
water tank is unavailable, the preset mode can only be “Heat” or “Cool”
● “Start timer” should be earlier than “End timer”, otherwise a dialog will pop up, saying “time setting wrong”. ● The setting for “Preset mode” will works until it has been canceled manually. ● When “Start timer” is reached, the unit will perform the preset mode. In this case, mode and temperature…
-
Parameter Setting Page
2. At the menu setting page, by touching the page turning keys, it is able to switch to the page where the desired parameter is. 3. After that, this setting will be saved by touching “OK” and then the unit will run based on this setting. While this setting will give up by touching “Cancel”. [Notes]…
-
2.4 Commissioning Parameter Setting
[Operation Instructions] 1. At the menu page, by touching “Commission”, it will access to the commissioning parameter page, where the left side is for the function setting and the right side is for the parameter setting, as shown in the figure below. [Notes] At the commissioning parameter setting…
-
Air removal On/Off Off / 12 Floor debug On/Off Off / 13 Manual defrost On/Off Off / 14 Force mode Off/Force-cool/Force-heat Off "Force-cool" is unavailable to heating only units. 15 Tank heater Logic 1/Logic 2 Logic 1 1. This setting is allowed when the water tank is available and the unit is OFF.…
-
2.4.2 2-Way valve
[Operation Instructions] At the commissioning parameter setting page, by touching “Cool 2-Way valve” or “Heat 2-Way valve”, the control panel will access to the corresponding setting page. [Notes] ●This setting is unavailable to heating only units. ●Under “Cool”, or “Cool + Hot water” mode, “Cool…
-
will run based on the mode set by the control panel. For mini chillers, it can be set to "On" or "Off". 3.For mini chillers, it can be set to "On" or "Off". [Notes] ●When “Water tank” is set to “Without”, the “Air + hot water” mode is unavailable. ●When “Floor debug” and “Emergen.mode” have…
-
Logic 1
1. The set point of other thermal should be equal to that of “WOT-Heat” in “Heat” mode and “Heat + hot water”mode; The set point should be the smaller one between “T-Water tank ” +5°C and 60°C in “Hot water” mode. 2. The water pump for other thermal must be always active under the “Heat” mode. 3.…
-
●This setting will be memorized upon power failure
●Either “Other thermal” or “Optional E-Heater” can be activated at the same time. ●There are two working logics for “Optional E-heater”. Logic 1: either the heat pump or the optional electric heater can be started at the same time. Logic 2: both the heat pump and the optional electric heater can be…
-
No
Full Name Displayed Name Range Default Accuracy 1 Floor debug switch Floor debug On/Off Off / 2 Quantity of segments Segments 1~10 Temperature of the first segment Period 1 temp 25~35℃ / 77~95°F 25℃ / 77°F 1℃ 4 Duration of each segment Segment time 12~72 hours 0 12 hours 5 Temperature difference of…
-
been put into operation, this function is unavailable, alerting “Wrong operation!”
● It will not be memorized upon power failure. 2.4.13 Gate-Ctrl. [Operation Instructions] At the commissioning parameter setting page, by touching “Gate-Ctrl.”, the control panel will access to the corresponding setting page. [Notes] ●When “Gate-Ctrl.” has been activated; the display panel will…
-
been put into operation, this function is unavailable, alerting “Wrong operation”
● This function will not be memorized upon power failure. 2.4.17 Control Logic of the Water Tank Heater [Operation Instructions] At the commissioning parameter setting page, by touching “Tank heater”, it will access to the setting page of control logic for the water tank heater. [Notes] ● “Reserved”…
-
● All parameters at this page will be memorized upon power failure
2.5 Viewing [Operation Instructions] 1. At the menu page, by touching “VIEW”, the control panel will go to the sub-menu page as shown in the figure below. VIEW Page 2.5.1 Status Viewing [Operation Instructions] 1. At the “VIEW” page, by touching “Status”, it is able to view status of the unit, as…
-
Status of the thermostat Thermostat Off/Cool/Heat “Cool” is unavailable to the heating only unit. 16 Status of other thermal source Other thermal On/Off / 17 Status of the 2-way valve 2-way valve On/Off / 18 Status of antifreeze HP-Antifree On/Off / 19 Status of the door guard Gate-Ctrl. Card…
-
2.5.3 Error Viewing
[Operation Instructions] At the “VIEW” page, by touching “Error”, it is able to view errors of the unit, as shown in the figure below. Error View Page [Notes] ●The control panel can display real-time errors. And at these pages, all errors will be listed here. ● Each page displays at most 5 pieces of…
-
Welding protection to the water tank electric heater Auxi. -WTH EH 25 DC bus under-voltage or voltage drop error DC under-vol. PL 26 DC bus over-voltage DC over-vol. PH 27 AC current protection (input side) AC curr. pro. PA 28 IPM defective IPM defective H5 29 PFC defective PFC defective Hc 30 Start…
-
● When error log exceeds 20, the latest will supersede the earliest
2.5.4 Version Viewing [Operation Instructions] At the “VIEW” page, by touching “Version”, the control panel will go to the version view page, where it is able to view both the program version and protocol version. 2.6 General Setting [Operation Instructions] 1. At the menu page, by touching…
-
2.6.1 Clock Setting
[Operation Instructions] 1. At the “GENERAL” setting page, by touching “Time&Data”, it will go to the setting page as shown in the figure below. Time&Data Page 2. The mouse roller can change the date and time value. After it, by touching the “Save” icon, this setting will be saved and directly…
-
● Software operation interface is universal and its control functions may not be completely corresponding to the unit. Software operation interface may vary along with APP upgrading or different operation system. Please refer to the actual program. 3.1 Install EWPE Smart APP [Operation Instructions]…
-
2.Except sign in in the prompt interface, you can also enter the homepage and click the profile picture at the left upper corner to sign in. 4. Click "+" at the right upper corner of homepage to add device. 31
-
After selecting “VERSATI”, the APP interface will provide relevant operation instructions
-
Reset the air conditioner (refer to the operation instructions in APP interface) and click “Next” to add home appliance automatically (Wi-Fi password shall be input). Or after setting and energizing the air conditioner, click “Add appliance manually” at the right upper corner to select the wireless…
-
3.2 Setting of Main Functions
1. Set mode and temperature. 34
-
2. Click Func at the left lower corner in device operation interface to enter advanced settings
3.3 Setting of Other Functions Click the profile picture at the left upper corner of homepage and set each function in the following menu. 35
-
3.3.1 Home management
Click “Home management” to create or manage family. You can also add family members according to the registered account. 36
-
3.3.2 Help
Click “Help” and view the operation instructions of the APP. 3.3.3 Feedback Click “Feedback” to submit feedback. 37
-
NOTE CONCERNING PROTECTION OF
ENVIRONMENT This product must not be disposed of via normal household waste after its service life, but must be taken to a collection station for the recycling of electrical and electronic devices. The symbol on the product, the operating instructions or the packaging indicate such disposal…