PowerTag System Design and Commissioning Guide PowerLogic offers power quality, uptime and efficiency. DOCA0194EN-00 11/2020 HeatTag Sensor PowerTag Energy 630 A Sensor PowerTag F160 Sensor PowerTag Control Module www.se.com PowerTag R2000 Sensor PowerTag Link Display PowerTag Energy 63 A Sensor…
-
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its subsidiaries referred to in this guide are the property of Schneider Electric SE or its subsidiaries. All other brands may be trademarks of their respective owners. This guide and its content are protected under…
-
Important Information
PowerTag System Important Information NOTICE Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn…
-
About the Book
About the Book Document Scope PowerTag System is a Schneider Electric wired/wireless solution designed to connect and digitize the electrical distribution installation and to perform energy management and monitoring, from the switchboard incomer down to the load level. This guide is intended for…
-
About the Book
PowerTag System Title of Documentation Reference Number Smartlink Modbus Gateway – Instruction Sheet S1B33423 PowerTag C IO 230 V Control and Monitoring Wireless Communication Module – Instruction Sheet MFR25181 PowerTag C 2DI 230 V Monitoring Wireless Communication Module – Instruction Sheet…
-
PowerTag System Presentation
PowerTag System Presentation Introduction PowerLogic Master Range PowerLogic smooths the power supply, protects the network, the installation and the operator by improving the power factor and hence the quality of the power. It also allows for remote control of equipment and the monitoring of its…
-
PowerTag System Enclosure
PowerTag System PowerTag System Enclosure The PowerTag system is designed for mounting inside low voltage (LV) enclosures. It can be mounted from simple plastic panel (for example, Kaedra panel) up to multi-column (non-partitioned) metallic switchboard (for example, Okken switchboard, BlokSeT…
-
PowerTag System Architecture Ranking
PowerTag System Architecture Ranking The PowerTag system architecture is ranked as: • Sparse wireless architecture: When only one gateway communicates in a radius of 20 meters. • Concentrated wireless architecture: When two gateways communicate in a radius of 20 meters. In Concentrated wireless…
-
PowerTag System Engineering Workflow
PowerTag System PowerTag System Engineering Workflow The PowerTag System engineering workflow consists of the following design phases: • • PowerTag system enclosure design ◦ For generic design rules, refer to Generic Design Rules, page 12. ◦ For enclosure implementation rules, refer to Enclosure…
-
Generic Design Rules
Rule GEN1: Mount the devices of the system in the same enclosure. The gateway and the associated wireless devices shall be mounted in the same enclosure (plastic or metallic) to have: • A wireless perimeter protected against the wireless external disturbances (especially for the metallic enclosure)…
-
Rule GEN3: Mount the PowerTag energy sensor upstream a contactor, a variable speed
drive, or a motor starter. It is not possible to mount the PowerTag energy sensor downstream a contactor, a variable speed drive, or a motor starter. Rule GEN4: 3 meters maximum between the gateway and the wireless devices. To avoid wireless communication disturbances, the gateway and the wireless…
-
Rule GEN5: No metallic partition between the gateway and the wireless devices
To avoid wireless communication disturbances, the gateway and the wireless devices must be mounted without metallic partition between them. Metal partition between wireless gateway and wireless device 2,5 meters 2,5 meters Rule GEN6: Follow the maximum capacity of the system. For more information on…
-
In example 2 and 3, the PowerTag energy sensors or PowerTag control modules
are not balanced between the two gateways. DOCA0194EN-00 15
-
Enclosure Implementation Rules
Rule SW1: Mount the gateway in the center of the switchboard. Reduce the distance between the gateway and the wireless devices to avoid wireless communication disturbances. Distance between farthest PowerTag and PowerTag Link is maximum PowerTag Link in central position in the panel minimize…
-
Rule SW3: Use one gateway per cubicle in partitioned switchboard
Use one gateway per cubicle in partitioned switchboard to avoid wireless communication disturbances. Rule SW4: Use one gateway for a maximum of three non-partitioned cubicles. Use one gateway for a maximum of three non-partitioned cubicles with a maximum cubicle width of 0.7 meters, to avoid…
-
Wireless Channel Assignment Plan Definition
Each gateway is set to one wireless channel. A wireless channel has a limited bandwidth and it depends upon: • the number of associated gateways and their paired wireless devices • the wireless communication periods set in each gateway NOTE: If the bandwidth in a channel exceeds the limit, it can…
-
Wireless Channel Assignment Procedure
Step Action 1 Add all the panel in the layout of the zone (strictly follow the scale of the layout) and tag each panel with a label. 2 Indicate a legend to identify the type of panel and to associate easily with the PowerTag system. 3 Define the overlapped wireless channel using the wireless…
-
Wireless Channel
During commissioning, the user defines the wireless channel used by PowerTag system for wireless bidirectional communication between the gateway and the paired wireless devices. The value can be set from channel 11 to 26 in gateway webpage. Each channel is 2 MHz wide with an unused spacing of 5 MHz.…
-
Wireless Communication Periods
The user defines the wireless communication periods for cyclic data exchanged between the gateway and the various types of wireless devices. These periods have an impact on the periodic wireless traffic generated. Their values must be increased to decrease the wireless traffic, in case of…
-
Wireless Channel Assignment Plan Rules
Rule WCAP1: Assign non-contiguous channels in a panel. Follow the rules to assign non-contiguous channels in a panel: • Do not use the same channel for several gateways inside an enclosure. • Do not use contiguous channel for adjacent gateway inside an enclosure. • Prefer to use non-contiguous…
-
Rule WCAP3: Reserve channels for future evolution
-
Wireless traffic not balanced on
-
PowerTag System Commissioning
PowerTag System PowerTag System Commissioning Commissioning Rules The commissioning rules are applicable to the gateway webpages. Rule COM1: Use the Manual Channel Selection mode in concentrated wireless architecture. In concentrated wireless architecture, the PowerTag systems interfere between…
-
Schneider Electric
35 rue Joseph Monier 92500 Rueil Malmaison France + 33 (0) www.se.com As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication. © 2020 – Schneider Electric. All rights reserved. DOCA0194EN-00
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.