TECHNICAL & SERVICE MANUAL
-
When Transporting
Important! Please Read Before Starting Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers. This air conditioning…
-
1. OPERATING RANGE
-
2. SPECIFICATIONS
2-1. Unit Specifications Indoor Unit Outdoor Unit SAP – K71GH SAP – C71GH Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Capacity kW BTU/h Air circulation (High) Moisture removal (High) m3/h Liters/h 2.05 7,000 / / / / 2.05 7,000 2.50 8,500 / / 2.50 8,500 /…
-
SAP – K91GH
SAP – C91GH Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Capacity kW BTU/h Air circulation (High) Moisture removal (High) m3/h Liters/h 2.55 8,700 / / 2.55 8,700 Heating / / 0.85 Electrical Rating 2.55 8,700 3.20 / 3.25 / 3.30 10,900 / 11,100 / 11,300 430…
-
2-2. Major Component Specifications
2-2-1. Indoor Unit Indoor Unit SAP – K71GH Controller PCB Part No. Controls Control circuit fuse POW-K71GH Microprocessor 250 V 3.15 A Remote Control Unit RCS-7HS1E Fan & Fan Motor Type Q'ty Dia. and length Fan motor model Q'ty No. of poles rpm (230 V, High) Nominal output Coil resistance (Ambient…
-
SAP – K91GH
Controller PCB Part No. Controls Control circuit fuse POW-K91GH Microprocessor 250 V 3.15 A Remote Control Unit RCS-7HS1E Fan & Fan Motor Type Q'ty Dia. and length Fan motor model Q'ty No. of poles rpm (230 V, High) Nominal output Coil resistance (Ambient temp. 20°C) Safety devices Type Operating…
-
2-2-2. Outdoor Unit
Outdoor Unit SAP – C71GH Controller PCB POW-C96GH-S Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices Rotary (Hermetic) C-1R71H5V 80688845-S 700 SUNISO 4GSD-T 320 C–R : 4.57 C–S : 6.90 External(OLR A) External(OLR T)…
-
SAP – C91GH
Controller PCB POW-C96GH-S Compressor Type Compressor model Nominal output Compressor oil Amount Coil resistance (Ambient temp. 25°C) Safety devices Rotary (Hermetic) C-R92H5W 80692945-S 900 SUNISO 4GSD-T 550 C–R : 3.07 C–S : 7.97 External(OLR A) External(OLR T) MRA99057-9201 CS-7C115 145±5 115±3…
-
2-3. Other Component Specifications
-
3. DIMENSIONAL DATA
Indoor Unit SAP – K71GH SAP – K91GH (3) 41.0 41.0 161 Remote control unit 57 132 18.5 58.5 Center of tubing hole (2 places) Drain hose ø18 Narrow tube ø6.35 (1/4") Wide tube ø9.52 (3/8") Unit : mm 9
-
SAP – C71GH
SAP – C91GH 2 – ø12 holes (C91 only) Air intake Wide tube service valve ø9.52 (3/8") Air discharge Narrow tube service valve ø6.35 (1/4") Unit : mm 10
-
4. REFRIGERANT FLOW DIAGRAM
SAP – K71GH SAP – K91GH Outdoor Unit Outdoor unit Wide tube Muffler 4-way valve Heat exchanger O.D. ø9.52 mm (3/8 ") Accumulator Wide tube service valve Narrow tube O.D. ø6.35 mm (1/4") Narrow tube service valve Compressor Indoor unit SAP – C71GH SAP – C91GH Capillary tubes Capillary tube (both for…
-
5. PERFORMANCE DATA
-
SAP – K91GH
-
5-2. Air Throw Distance Chart
Indoor Unit SAP – K71GH Cooling Room air temp. : Fan speed : 27°C High Horizontal distance (m) Axis air verocity (m/s) Vertical distance (m) : Flap angle 0° , : Flap angle 30°, : Axis air velocity 0° : Axis air velocity 30° Heating Room air temp. : Fan speed : 27°C High Horizontal distance (m) Axis…
-
SAP – K91GH
Cooling Room air temp. : Fan speed : 27°C High Horizontal distance (m) Axis air verocity (m/s) Vertical distance (m) : Flap angle 0° , : Flap angle 30°, : Axis air velocity 0° : Axis air velocity 30° Heating Room air temp. : Fan speed : 27°C High Horizontal distance (m) Axis air verocity (m/s)…
-
5-3. Cooling Capacity
Indoor Unit Outdoor Unit SAP – K71GH SAP – C71GH 240V Single Phase 50Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23…
-
SAP – K91GH
SAP – C91GH 240V Single Phase 50Hz RATING CAPACITY AIR FLOW RATE EVAPORATOR ENT. TEMP. °C W.B. D.B. TC CM 21 SHC 15 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 17 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 21 SHC 19 23 SHC 25 SHC 27 SHC 29 SHC 31 SHC TC CM 23 SHC 21 25 SHC 27 SHC 29 SHC 31 SHC TC…
-
Heating capacity ratio (%)
5-4. Heating Capacity –8 –5 Outdoor temperature (°C D.B.) NOTE 1) … Point of Rating condition Black dot in the chart indicate the following rating condition. Indoor : 20°C D.B. Outdoor : 7°C D.B. / 6°C W.B. 2) Above characteristics indicate instantaneous operation, which does not take into account…
-
6. ELECTRICAL DATA
6-1. Electrical Characteristics Indoor Unit Outdoor Unit SAP – K71GH SAP – C71GH COOLING Indoor Unit Outdoor Unit Fan Motor Fan Motor Performance at Rating Conditions Complete Unit Compressor 220 – 240V Single phase 50Hz Running Amps. Power Input Full Load Conditions Running Amps. Power Input A 0.16…
-
SAP – K91GH
SAP – C91GH SAP C91GH COOLING Indoor Unit Outdoor Unit Fan Motor Fan Motor Performance at Rating Conditions Complete Unit Compressor 220 – 240V Single phase 50Hz Running Amps. Power Input Full Load Conditions Running Amps. Power Input / 0.18 0.24 / 0.25 3.89 / 3.87 4.3 / kW 0.034 / 0.040 A 0.052 /…
-
6-2. Electric Wiring Diagrams
Indoor Unit SAP – K71GH SAP – K91GH WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 851-2-5253-401-xx-0 21
-
SAP – C71GH
SAP – C91GH WARNING To avoid electrical shock hazard, be sure to disconnect power before checking, servicing and/or cleaning any electrical parts. 851-2-5253-430-xx-1 22
-
7. INSTALLATION INSTRUCTIONS 7-1. Installation Site Selection Indoor Unit WARNING To prevent abnormal heat generation and the possibility of fire, don’t place obstacles, enclosures and grills in front of or surrounding the air conditioner in a way that may block air flow. AVOID: ● direct sunlight. 5…
-
AVOID
● heat sources, exhaust fans, etc. (Fig. 3) NO ● damp, humid or uneven locations. Exhaust fan Hot air Heat source DO: ● choose a place as cool as possible. Outdoor unit ● choose a place that is well ventilated. ● allow enough room around the unit for air intake/exhaust and possible maintenance.…
-
7-2. Remote Control Unit Installation
Position Removable mounting Wall The remote control unit can be operated from either a non-fixed position or a wall-mounted position. To ensure that the air conditioner operates correctly, do not install the remote control unit in the following places: Special mounting screw ● In direct sunlight ●…
-
7-3. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation. NOTE Refer to the WIRING SYSTEM DIAGRAM for the meaning of "A" and "B" in Table 6.…
-
8. FUNCTION
8-1. Room Temperature Control ■ Cooling ● Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit. ● The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the…
-
■ Heating
● Room temperature control is obtained by cycling the compressor ON and OFF under control of the room temperature sensor in the remote control unit. ● The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the controller in the indoor unit. Signal…
-
8-2. Dry Operation (Dehumidification)
● Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON and OFF automatically as shown in the chart below according to the room…
-
8-4. Freeze Prevention (Cooling)
● This function prevents freezing of the indoor heat exchange coil. ● When the compressor has been running for 10 minutes or more and the temperature of the indoor heat exchange coil falls below –1°C, the control circuit stops the compressor for at least 6 minutes. The compressor does not start…
-
8-5. Overload Prevention (Heating)
● This function prevents overheating of the indoor heat exchange coil. ● When the temperature of the indoor heat exchange coil rises above 54°C, and if the indoor fan is L (low speed), then the fan speed changes from L (low speed) to M (medium speed). ● When the temperature of the indoor heat…
-
8-6. Cold Draft Prevention (Heating)
● This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coil have sufficiently warmed up. ● STANDBY lamp on front of the indoor unit lights up when this function is working. ● when 10 minutes has elapsed,the fan speed is automatically…
-
8-7. Defrosting Operation (Heating)
■ Defrosting Flowchart Compressor ON Release of overload prevention (Outdoor fan operates.) Overload prevention works. Does outdoor fan stop? YES NO A B Outdoor fan is either operated or stopped for more than 10 minutes. NO C Indoor heat exchanger coil temperature drops 0.8°C per 6 minutes and it…
-
■ Defrosting Mode Timing Chart
Release of defrosting Start of defrosting 32 seconds Compressor ON Outdoor fan ON OFF 11 minutes ON 32 seconds ON OFF OFF ON 2 seconds Solenoid coil (4 – way valve) Indoor fan Standby lamp 2 seconds OFF ON ON Set speed OFF ON Set speed ON ON OFF Indoor heat exch. coil ✻1 temp. 34 °C ✻1 Release of…
-
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting WARNING Hazardous voltage can cause ELECTRIC SHOCK or DEATH. Disconnect power or turn off circuit breaker before you start checking or servicing. 9-1-1. Check power supply wiring. ● Check that power supply wires are correctly connected to terminals No.8…
-
9-2. Air conditioner does not operate
9-2-1. Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.) ● There is a possibility of ground fault. ● Check insulation resistance. If resistance value is 2MΩ or less, insulation is defective (“NO”). 2 Indoor unit 1…
-
B. Circuit breaker trips in several minutes after turning the air conditioner on
● There is a possibility of short circuit. • Check capacity of circuit breaker. Replace with suitable one (larger capacity). NO Capacity of circuit breaker is suitable. In case of Heating operation : • Measure resistance of 4-way valve's winding. • Measure resistance of outdoor fan motor winding. •…
-
C. Check remote control unit
• Try to run with another remote control unit. OK First remote control unit is defective. • Check for residue buildup on transmitter of remote control unit. Clean transmitter. • Check for residue buildup on remote control receiver on front of indoor unit. Clean receiver. D. Check fuse on the indoor…
-
9-2-3. Only outdoor unit does not run
A. Check setting temperature. Is room temperature too low ? Is room temperature too high ? NO NO Try to lower setting temperature by temperature setting button ( button). Try to raise setting temperature by temperature setting button ( button). Outdoor unit still does not run. Outdoor unit still…
-
9-3. Some part of air conditioner does not operate
9-3-1. Only indoor fan does not run. • Check fan rotation. Turn fan gently once or twice by hand. Fan cannot be turned. • Check fan casing foreign matter on inside. Remove foreign matter or repair. Fan motor burnout or foreign matter in bearings. Repair or replace. • Check fan casing foreign matter…
-
9-3-4. Only compressor does not run
Overload relay is working. (Either OLR T or OLR A) • Check compressor motor capacitor. (C1) YES • Measure resistance of compressor motor winding. Temperature of compressor is abnormally high. YES YES Refrigerant gas shortage. NO • Measure Power supply voltage. The voltage is too low. No Rotor may be…
-
9-4. Air conditioner operates, but abnormalities are observed
9-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT). • Remote control unit may be defective. Receiver in switch Ass'y may be defective. • Measure resistance of 4–way valve's winding. COOL ➞ HEAT • Check voltage between terminals No. 4(+) and No. 6 at terminal plate. (DC 24V) OK…
-
9-4-2. Poor cooling or heating
• Check position of remote control unit. • Cool air from air conditioner reaches position directly. YES Change position of remote control unit. • Wide and narrow tubes between indoor unit and outdoor unit are insulated. NO Insulate both wide and narrow tubes separately and then tape together. YES •…
-
9-5-1. Indoor coil temp. thermistor (TH1) is defective. • Operation lamp on front side of indoor unit is flashing on and off. (*) YES • Thermistor (TH1 ) is defective. (That is, sensor is SHORT.) YES • Replace thermistor. NOTE Alarm Signal (*) Operation lamp on the front side of the indoor unit will…
-
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance Ground wire Clip ● The insulation is in good condition if the resistance exceeds 2MΩ. Probe 10-1-1. Power Supply Wires Insulation tester Clamp the ground wire of the power supply wires with the lead clip of the insulation resistance tester and measure the…
-
10-2. Checking Continuity of Fuse
on PCB Ass'y Fuse ● Remove the PCB Ass’y from the electrical component box. Then pull out the fuse from the PCB Ass’y. (Fig. 5) PCB Ass’y ● Check for continuity using a multimeter as shown in Fig. 6. Fig. 5 10-3. Checking Motor Capacitor Remove the lead wires from the capacitor terminals, and then…
-
APPENDIX INSTRUCTION MANUAL
-
Features
This air conditioner is equipped with cooling, heating, and drying functions. Details on these functions are provided below; refer to these descriptions when using the air conditioner. • Compact Size This model is smaller than its predecessors and yet offers the same capabilities. • Microprocessor…
-
Installation Location
We recommend that this air conditioner be installed properly by qualified installation technicians in accordance with the Installation Instructions provided with the unit. Before installation, check that the voltage of the electric supply in your home or office is the same as the voltage shown on…
-
Names of Parts
Air intakes INDOOR UNIT Air outlet Remote control unit Drain hose Refrigerant tubes OUTDOOR UNIT Air outlet NOTE This illustration is based on the external appearance of a standard model. Consequently, the shape may differ from that of the air conditioner you have selected. This air conditioner…
-
Unit Display and Operation Selector
Operation selector INDOOR UNIT IMPORTANT Avoid using radio equipment such as mobile phone near (within 1 m of) the indoor unit. Some radio equipment may cause the unit to malfunction. If the trouble occurs, disconnect power and restart the air conditioner after a few minutes. Remote control receiver…
-
Remote Control Unit (Display)
Displayed when setting temperature SET TEMP. Displayed when transmitting data C Displayed when temperature is shown Displayed when the temperature setting is at the upper or lower allowable limit Displayed when setting timer 1HR. Symbols (1) Operation mode AUTO (3) Set temperature 16–30°C When set…
-
Remote Control Unit
AIR CONDITIONER Transmitter AIR CONDITIONER SET TEMP. C Display 1HR. (Cover closed) 1 HR. TIMER TEMP. 1 HR. TIMER button TEMP. setting buttons ON I /OFF ON/OFF operation button MODE ON FLAP OFF FAN SPEED SET SELECT TIMER NIGHT SETBACK NIGHT SETBACK button MODE selector button TIMER ON button FLAP…
-
Remote Control Unit (continued)
TIMER ON button : The air conditioner starts at the set time. TIMER OFF button : The air conditioner stops at the set time. TIMER SET button This button is used to set the time at which you wish the air conditioner to go on or off. MODE selector button (AUTO) Use this button to select AUTO, HEAT…
-
Using the Remote Control Unit
How to Install Batteries ACL button 1. Slide the cover in the direction indicated by the arrow and remove it. 2. Install two AAA alkaline batteries. Make sure the batteries point in the direction marked in the battery compartment. 3. Use a thin object such as the tip of a pen to press the ACL…
-
Using the Remote Control Unit (continued)
Mounting the Remote Control Unit Removable mounting Non-removable mounting Wall Wall (Packed in the indoor unit) (Packed in the indoor unit) Mounting on a wall A. Removable mounting 1) Momentarily hold the remote control unit at the desired mounting position. 2) Confirm that the air conditioner…
-
Operation with the Remote
Control Unit 1. Automatic Operation AIR CONDITIONER SET TEMP. C 1 HR. TIMER TEMP. ON I /OFF STEP 2 MODE ON FLAP OFF FAN SPEED SET NIGHT SETBACK STEP 1 SELECT ACL TIMER BATTERIES NOTE Check that the circuit breaker on the power panel is turned on and that the operation selector of the indoor unit is…
-
2. Manual Operation
AIR CONDITIONER SET TEMP. C 1 HR. TIMER TEMP. STEP 3 ON I /OFF MODE ON FLAP OFF FAN SPEED SET NIGHT SETBACK STEP 2 STEP 1 STEP 5 STEP 4 SELECT ACL TIMER BATTERIES NOTE Check that the circuit breaker on the power panel is turned on and that the operation selector of the indoor unit is in the ON…
-
NOTE
• This appliance has a built-in 3-minute time delay circuit to ensure reliable operation. When the operation button is pressed, the compressor will start running within three minutes. In the event of power failure, the unit will stop. When the power is restored, the unit will restart automatically…
-
4. Night Setback Mode
SET TEMP. C 1 HR. TIMER TEMP. ON I /OFF MODE ON FLAP OFF FAN SPEED SET NIGHT SETBACK ACL Night Setback Mode is used for saving energy. Press the NIGHT SETBACK button while operation. mark appears in the display. The To release the night setback function, press the NIGHT SETBACK button again. A. In…
-
( ) When the night setback mode is selected, the air conditioner automatically lowers the temperature setting 2°C when 30 minutes have passed after the selection was made, and then another 2°C after another 30 minutes have passed, regardless of the indoor temperature when night setback was selected.…
-
Special Remarks
‘‘DRY’’ ( ) Operation How it works? • • • Once the room temperature reaches the level that was set, the unit repeats the cycle of turning on and off automatically. During DRY operation, the fan speed is automatically set to LOW or VERY LOW; the fan speed then switches back and forth between LOW (for…
-
Using the 12-Hour ON and OFF
Timer 1. TIMER ON mode (Example) After the length of time set for TIMER ON elapses, the unit begins operating. The display depicted at left indicates that the air conditioner will begin operating in three hours. H Setting procedure: ON STEP 1 MODE ON FLAP OFF FAN SPEED SET SELECT NIGHT SETBACK STEP…
-
Using the 12-Hour ON and OFF Timer (continued)
3. ON/OFF Program Timer A combination of the TIMER ON and TIMER OFF modes, this function allows you to specify the time that the unit turns on and the time when it turns off. (Example) The unit will turn on three hours from now, and turn off five hours from now. Timer setting H ON Stop Operate 3…
-
Using the 1-Hour OFF Timer
1. 1-Hour OFF Timer C 1HR. 1HR. ON 1 HR. TIMER This function causes the unit to operate for one hour and then stop, regardless of whether the unit is on or off when this button is pressed. indicator in the display indicates that this function is operating. The Setting procedure: Regardless of…
-
Adjusting the Airflow Direction
MODE ON FLAP OFF FAN SPEED SET SELECT TIMER 1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right. CAUTION When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If…
-
Operation without the Remote
Control Unit INDOOR UNIT If you have lost the remote control unit or it is not working properly, follow the steps below. 1. When the air conditioner is not running If you want to turn on the air conditioner, switch the operation selector to the OFF position, and then to the ON position. NOTE…
-
Care and Cleaning (continued)
Anti-Mold Filter How to remove the anti-mold filter The anti-mold filter behind the air intake grille should be checked and cleaned at least once every two weeks. 1. Grasp both ends of the air intake grille and pull it out and up. Air intake grille 2. Push the anti-mold filter up slightly, and then…
-
Care and Cleaning (continued)
Air Cleaning Filter (not provided) NOTE The air cleaning filter removes dust and dirt from the air, and reduces odors and smoke from tobacco. The air cleaning filter is not provided with the air conditioner and must be purchased separately. The first time that you buy the air clean filter, it is…
-
Troubleshooting
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work properly, contact your dealer or service center. Trouble Air conditioner does not run at all. Possible Cause 1. Power failure. 2. Leakage breaker tripped. 3. Line…
-