1509876HC1501 LOSSNAY HEAT RECOVERY VENTILATOR (RESIDENTIAL USE) MODEL: VL-220CZGV-E Installation Manual
-
1. Safety Precautions (continued)
CAUTION Incorrect handling of the product may result in injury or damage to property or household effects. The product is exclusively for horizontal installation. Do not install the product on walls. Injury could result if parts fall. Do not install the product at regions or locations that exceed…
-
2. Outside Dimensions
English Lossnay unit Top view EA (exhaust air) Duct connecting flange (EA) 234 80 Auxiliary fixture Duct connecting flange (RA1) RA1 (return air) 850 SA (supply air) 885 229 Duct connecting flange (SA) 848 (Ceiling suspension fixture) 116 Ceiling suspension fixture 86 Drain outlet 31 Power supply…
-
3. Standard Installation Examples
Piping example - When connecting the RA (return air) to a bathroom, be sure to branch into two lines and return air from two locations, the bathroom and living room. Outdoor side Indoor side Name of Connection Point RA RA2* For optional motorized damper (P-133DUE-E) (return air) Exclusive for intake…
-
4. Installation Procedure
3. Installing the Lossnay unit Install the four duct connecting flanges (supplied) to the Lossnay unit using the duct connecting flange mounting screws (4-25 mm) (supplied). (4 pcs x 4 locations) When installing the duct connecting flange (RA1, EA), fill in any gaps between the duct connecting…
-
4. Installation Procedure (continued)
Duct piping Note: - Make sure that there are no metal chips or other foreign matter (e.g. paper or vinyl) inside the ducts or the Lossnay unit before connecting the ducts. 1. Duct piping (1) Choose the connection duct Use the ducts shown in the table below. Piping duct locations OA EA SA RA1…
-
4. Installation Procedure (continued)
English Connecting drain pipe Connecting the drain hose (1) Firmly insert the drain hose (supplied) down to the base of the drain outlet. Securely tighten the hose band (supplied) using a flathead screwdriver to secure in place. (Poor tightening may result in water leakage.) (2) Connect the other…
-
5. Electrical Work
WARNING Electrical work must be carried out safely and reliably by a professional electrical contractor (properly qualified electrician) in accordance with internal wiring provisions and electricalequipment technical standards. Poor connection and faulty electrical work could result in electric…
-
5. Electrical Work (continued)
English Wire connection diagram * TM1, TM4 shown in dotted lines are field work. * CN7 (DAMPER) is optional. * Be sure to connect the ground wire. * A power supply isolator must be installed. * Always use an isolator for the main switch power connection. * Select proper circuit breaker according to…
-
5. Electrical Work (continued)
Connecting the wires (1) Remove the terminal block cover. (3 screws) Remote controller (PZ-61DR-E or PZ43SMF-E) Lossnay Terminal block cover * The figure shows the PZ-61DR-E Power supply Transmission cables 2 1 Remote controller input terminal (2) Connecting the power supply cable and transmission…
-
6. Initial Settings
English Settings when the motorized damper (option) is installed When the optional motorized damper (P-133DUE-E) is installed, change the SW6-1 setting to OFF. SW6-1 SW6-2 SW6-3 SW6-4 Remarks Without the damper Motorized damper selection ON ON ON ON Factory default With the damper OFF ON ON ON (SW6)…
-
Language selection
Function description The desired language can be set. The language options are English, French, German, Spanish, Italian, Portuguese, Swedish, and Russian. Button operation 1 Main display: Cursor F1 2 2/2 Main Main menu Initial setting Service F2 Page F3 Cursor F1 3 F4 Initial setting menu 2/2 Auto…
-
Entering the maintenance information
Button operation 1 Accessing the Main menu Main F1 MENU 2 F2 Press the MENU button. The Main menu will appear. Page F3 F4 Item selection Main Cursor 3 1/2 Main menu Timer Weekly timer Restriction Filter information Error information Main display: Cursor F1 F2 SELECT F1 F2 F3 2/2 Press F1 , F2 , F3…
-
1/2 Service menu Test run Input maintenance info. Lossnay Check Self check Main menu: Select Input maintenance info. on the Service Menu screen, and press the SELECT button. Cursor F1 6 F2 F3 F4 Maintenance information Model name input Serial No. input Dealer information input Initialize maintenance…
-
Change the function settings from the remote controller PZ-61DR-E
Function description Make the Lossnay units' function settings from the remote controller as necessary. • Please refer to the Instruction book of PZ-61DR-E for how to set the function settings. • When changing the Lossnay units' function settings, record all the changes made to keep track of the…
-
2/2 Service menu Maintenance password Remote controller check Function setting Initializing Select Function Setting on the Service Menu screen, and press the SELECT button. Main menu: Cursor F1 6 F2 F3 F4 Function setting M-NET address 0 Function No. 1 Data 2 Set / Conf Function Select: Cursor F1 F2…
-
0 1 Indicator available Fan power up N/A 1 Filter maintenance and fan power up setting against filter choking Dip-SW priority 5 Automatic recovery setting after power interruption Dip-SW priority 6 Indoor negative pressure setting Dip-SW priority 7 Indoor positive pressure setting Exhaust fan…
-
maintenance and fan power up
No. 1 Filter setting against filter choking No.7 Indoor positive pressure setting Set the schedule for filter cleaning based on the estimated concentration of dust in the air. Supply fan speed becomes bigger than exhaust fan speed. When fan power up is available, exhaust and supply fans power up at…
-
Set one of conditions for By-pass mode in auto ventilation operation,
outdoor air temperature upper limit. This function is N/A from Lossnay unit DIP-SW. This function is available when setting Data 3 is selected at function No. 51. Example* By-pass/Heat recovery ventilation map in automatic ventilation mode 40 PZ-61DR-E Setting Setting Indoor temperature check…
-
No.61 Fan speed for air volume “High” input
Set the fan speed setting when receiving “High” signal from remote controllers(e.g. PZ-43SMF-E) which have High/Low air volume. When PZ-61DR-E is used, this setting does not need to be changed. DIP-SW SW No. Setting - Setting Operating fan speed check - OFF SW2-9 (Factory setting) DIP-SW priority…
-
7. Post-installation Checks
Check Item Remedy for Malfunction Check Are the Lossnay unit and the duct piping installed on the indoor side of the insu- Install them on the indoor side of the insulation layer/airtight layer. lation layer/airtight layer? Installation of Lossnay unit Duct connections Drain piping Wiring Is the…
-
8. Trial operation
After the system has been installed, make sure that wires are properly connected, then test the system’s operation, referring to the operation manual for the remote controller. ■ Perform trial operation with the user in attendance. - Noise sometimes increases for several minutes after the power to…
-
8. Trial operation (continued)
Press each of the buttons by following the procedure below to check that operation is normal. "3. Selecting the ventilation mode" is displayed on the remote controller only when the optional motorized damper is installed to indicate that the mode can be switched. Relevant button Relevant display…
-
Explaining to the User
● Explain to the user where the circuit breaker and remote controller are located and how to clean the filters. ● Tell the user the results of checks performed using the check list. ● Hand over the CD-ROM containing this Installation Manual to the user. ● Explain correct use by following the…
-