Настенные сплит-системы Midea серии MSMBA-07HRN1(W)/ MOAB01-07HN1,MSMBA-09HRN1(W)/ MOAB01-09HN1, MSMBB-12HRN1(W)/ MOBA02-12HN1, MSMBC-19HRN1(W)/ MOBA02-18HN1, MSMBD-24HRN1(W)/ MOCA01-24HN1,MSMBAU-09HRFN1(BW)/ MOBA02-09HFN1, MSMBBU-12HRFN1(BW)/ MOB03-12HFN1, MSMBCU-18HRFN1(BW)/ MOB02-18HFN1, MSMBDU-24HRFN1(BW)/ MOCA01-24HFN1. Руководство пользователя.
Смотрите также: Инструкция по техническому обслуживанию →
Загружаем документ…
Текст инструкции
-
Библиотека СОК
DM16-01.01.22en Mission Inverter Series Service Manual 2016 MSMBAU-09HRFN1(BW) / MOBA02-09HFN1 MSMBBU-12HRFN1(BW) / MOB03-12HFN1 MSMBCU-18HRFN1(BW) / MOB02-18HFN1 MSMBDU-24HRFN1(BW) / MOCA01-24HFN1 1
-
1. Precaution
1.1 Safety Precaution To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. Before service the unit, be sure to read this service manual at first. 1.2 Warning …
-
Do not plug or unplug the power supply plug during operation. There is risk of fire or electric shock. Do not touch (operation) the product with wet hands. Do not place a heater or other appliance near the power cable. There is risk of fire and electric shock. Do not allow water to run into…
-
Use two or more people to lift and transport the product. Do not install the product where it will be exposed to sea wind (salt spray) directly. It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient…
-
2. Function
Model Names of Indoor/Outdoor Units Inverter 6 Capacity Indoor units Outdoor units 9k MSMBAU-09HRFN1(BW) MOBA02-09HFN1 12k MSMBBU-12HRFN1(BW) MOB03-12HFN1 18k MSMBCU-18HRFN1(BW) MOB02-18HFN1 24k MSMBDU-24HRFN1(BW) MOCA01-24HFN1 Service manual
-
3. Specification
Indoor MSMBAU‐09HRFN1(BW) MSMBBU‐12HRFN1(BW) Outdoor MOBA02‐09HFN1 MOB03‐12HFN1 Ph‐V‐Hz 220‐240V~ 50Hz, 1Ph 220‐240V~ 50Hz, 1Ph Btu/h 9000(4000‐11300) 12000(4600‐15400) kW 2.64 (1.17~3.31) 3.52 (1.35~4.51) Cooling Power input W 816(100‐1270) 1088(110‐1740) Cooling A 3.5(0.4‐5.5) 4.7(0.5‐7.6) Btu/h…
-
Indoor
MSMBCU‐18HRFN1(BW) MSMBDU‐24HRFN1(BW) Outdoor MOB02‐18HFN1 MOCA01‐24HFN1 Ph‐V‐Hz 220‐240V~ 50Hz, 1Ph 220‐240V~ 50Hz, 1Ph Btu/h 18000(6500‐21100) 24000(8800‐27600) kW 5.28 (1.91~6.18) 7.03 (2.58~8.09) Cooling Power input W 1633(150‐2380) 2336(230‐3110) Cooling A 7.1(0.7‐10.3) 10.2(1.0‐13.5) Btu/h…
-
d.Fin type (code)
-
4. Dimension
4.1 Indoor Unit Model W D H MSMBAU-09HRFN1(BW) MSMBBU-12HRFN1(BW) MSMBCU-18HRFN1(BW) MSMBDU-24HRFN1(BW) 1090 235 338 Service manual 11
-
For MSMBAU-09HRFN1(BW),
For MSMBBU-12HRFN1(BW), 12 Service manual
-
For MSMBCU-18HRFN1(BW),
For MSMBDU-24HRFN1(BW), Service manual 13
-
4.2 Outdoor Unit
-
For MOBA02-09HFN1,
-
For MOB03-12HFN1, MOB02-18HFN1,
-
For MOCA01-24HFN1,
Service manual 17
-
5. Capacity tables
-
MSMBBU-12HRFN1(BW) / MOB03-12HFN1
-
MSMBCU-18HRFN1(BW) / MOB02-18HFN1
-
MSMBDU-24HRFN1(BW) / MOCA01-24HFN1
-
6. Refrigerant Cycle Diagram
INDOOR OUTDOOR CHECK VALVE (Heating Model only) LIQUID SIDE 2-WAY VALVE CAPILIARY TUBE HEAT EXCHANGE (EVAPORATOR) HEAT EXCHANGE (CONDENSER) T1 Room temp. sensor T2 Evaporator temp. sensor GAS SIDE 4-WAY VALVE 3-WAY VALVE ACCUMULATOR COOLING COMPRESSOR 22 HEATING Service manual
-
7. Wiring diagram
MSMBAU-09HRFN1(BW), MSMBBU-12HRFN1(BW), MSMBCU-18HRFN1(BW) MSMBDU-24HRFN1(BW) Service manual 23
-
MOBA02-09HFN1, MOB03-12HFN1,
24 Service manual
-
MOB02-18HFN1, MOCA01-24HFN1
Service manual 25
-
8. Installation Details
8.1 Wrench torque sheet for installation Outside diameter Torque Additional tightening torque mm inch N.cm N.cm Ф6.35 1/4 1500(153kgf.cm) 1600(163kgf.cm) Ф9.52 3/8 2500(255kgf.cm) 2600(265kgf.cm) Ф12.7 1/2 3500(357kgf.cm) 3600(367kgf.cm) Ф15.9 5/8 4500(459kgf.cm) 4700(479kgf.cm) Ф19 3/4…
-
8.3 Pipe length and the elevation
The pipe length and refrigerant amount: Pipe size Model MSMBAU-09HRFN1(BW) + MOBA02-09HFN1 MSMBBU-12HRFN1(BW) + MOB03-12HFN1 MSMBCU-18HRFN1(BW) + MOB02-18HFN1 MSMBDU-24HRFN1(BW) + MOCA01-24HFN1 Gas Liquid 3/8’’ 1/4’’ (Ф9.52) (Ф6.35) 3/8’’ 1/4’’ (Ф9.52) (Ф6.35) 1/2’’ 1/4’’ (Ф12.7) (Ф6.35) 5/8’’ 3/8’’…
-
8.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below: Pressure in the system rises. Operating current rises. Cooling or heating efficiency drops. Moisture in the refrigerant circuit may freeze and block capillary tubing. Water may lead to corrosion of parts in the refrigerant…
-
Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump
Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump). 7) Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure…
-
3. Adding the refrigerant if the pipe length >5m
Procedure: 1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure the liquid…
-
8.5 Adding the refrigerant after running the system for many years
Procedure: 1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3-way valve. Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge. 2). Purge the air from the charge hose.…
-
8.6 Re-installation while the indoor unit need to be repaired
1. Collecting the refrigerant into the outdoor unit Procedure 1). Confirm that both the 2-way and 3-way valves are set to the opened position Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems. 2).…
-
2. Air purging by the refrigerant
Procedure: 1). Confirm that both the 2-way and 3-way valves are set to the closed position. 2). Connect the charge set and a charging cylinder to the service port of the 3-way valve Leave the valve on the charging cylinder closed. 3). Air purging. Open the valves on the charging cylinder and the…
-
8.7 Re-installation while the outdoor unit need to be repaired
1. Evacuation for the whole system Procedure: 1). Confirm that both the 2-way and 3-way valves are set to the opened position. 2). Connect the vacuum pump to 3-way valve’s service port. 3). Evacuation for approximately one hour. Confirm that the compound meter indicates -0.1Mpa. 4). Close the valve…
-
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge. 2). Purge the air from the charge hose Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant). 3) Put the charging…
-
9. Operation Characteristics
Mode Cooling operation Heating operation Drying operation Room temperature 17℃~32℃ 0℃~30℃ 10℃~32℃ Outdoor temperature 0℃~50℃ -15℃~30℃ 0℃~50℃ Temperature -15℃~50℃ (For the models with low temperature cooling system) CAUTION: 1. If the air conditioner is used beyond the above conditions, certain…
-
10. Electronic function
10.1 Abbreviation T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 10.2 Display function 7.2.1 Icon explanation on indoor display board. Digital display: Displays the temperature…
-
Dispalys ‘
’ during self clean operation (if aplicable). Dispalys ‘ ’ under 8℃ heating operation. When ECO function(optional) is actived,the “ ” illuminates gradually one by one as In one second interval. WIFI control display (WiFi kit is in standard) Displays when the WIFI control feature is activated NOTE: A…
-
10.3 Main Protection
10.3.1 Three minutes delay at restart for compressor 1 minute delay for the 1st time stand-up and 3 minutes delay for others. 10.3.2 Temperature protection of compressor top The unit will stop working when the compressor top temp. protector cut off, and will restart after the compressor top temp.…
-
10.4 Operation Modes and Functions
10.4.1 Fan mode (1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: T1 a b c d e 10.4.2 Cooling Mode 10.4.2.1…
-
The indoor fan is controlled as below
-
When the AC run in mute mode, the compressor will run with low frequency
When the current is more than setting value, the current protection function will be activated and the compressor will stop. 10.4.3.2 Outdoor fan running rules The outdoor unit will be run at different fan speed according to T4. For different outdoor units, the fan speeds are different. T4 A+ A B C…
-
normal heating mode
----T3 rises to be higher than TCDE1℃. ----T3 keeps to be higher than TCDE2℃ for 80 seconds. ----The machine has run for 15 minutes in defrosting mode. 10.4.3.5 Evaporator coil temperature protection T2 Off TEstop Decrease TEdown Hold TEH2 Resume Off: Compressor stops. Decrease: Decrease the running…
-
The action of forced auto mode is the same as normal auto mode with 24℃ setting temperature
When AC receives signals, such as switch on, switch off, timer on, timer off, mode setting, fan speed setting, sleeping mode setting, follow me setting, it will quit the forced operation. 10.4.7 Timer function 10.4.7.1 Timing range is 24 hours. 10.4.7.2 Timer on. The machine will turn on…
-
memorize the maximum angle of the louver. During operation, if the power fails or the end user shuts
down the unit in the turbo mode, the louver will restore to the default angle. 10.4.12 8℃ Heating In heating operation, the preset temperature of the air conditioner can be as lower as 8℃, which keeps the room temperature steady at 8℃ and prevents household things freezing when the house is…
-
When the AC enter into the information enquiry status, it will display the code value in the next 25s, the details are as follows. Enquiry Display value Meaning Remark T1,T2,T3,T4, -1F,-1E,-1d,-1c,-1b,-1A -25,-24,-23,-22,-21,-20 1. All the displaying temperature is actual T2B,TP,TH, -19—99 -19—99…
-
11. Troubleshooting
Safety Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capacitor. Electrolytic Capacitors (HIGH VOLTAGE! CAUTION!) For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug)…
-
11.1 Indoor Unit Error Display
Operation lamp Timer lamp Display ☆ 1 time X E0 Indoor unit EEPROM parameter error ☆ 2 times X E1 Indoor / outdoor units communication error ☆ 4 times X E3 Indoor fan speed has been out of control ☆ 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit ☆ 6 times X E5…
-
11.2 Trouble shooting
11.2.1 EEPROM parameter error diagnosis and solution(E0/F4) Error Code E0/F4 Malfunction decision Indoor or outdoor PCB main chip does not receive feedback conditions from EEPROM chip. Supposed causes ● Installation mistake ● PCB faulty Trouble shooting: EEPROM: a read-only memory whose contents can…
-
11.2.2 Indoor / outdoor unit’s communication diagnosis and solution(E1)
Error Code E1 Malfunction decision Indoor unit does not receive the feedback from outdoor unit during conditions 110 seconds and this condition happens four times continuously. Supposed causes ● Wiring mistake ● Indoor or outdoor PCB faulty Trouble shooting: 50 Service manual
-
Remark
Use a multi meter to test the resistance of the reactor which does not connect with capacitor. The normal value should be around zero ohm. Otherwise, the reactor must have malfunction and need to be replaced. Service manual 51
-
11.2.3 Fan speed has been out of control diagnosis and solution(E3)
Error Code E3 Malfunction decision When indoor fan speed keeps too low (300RPM) for certain time, conditions the unit will stop and the LED will display the failure. Supposed causes ● Wiring mistake ● Fan ass’y faulty ● Fan motor faulty ● PCB faulty Trouble shooting: 52 Service manual
-
Index1
1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced. DC…
-
11.2.4 Refrigerant Leakage Detection diagnosis and solution(EC)
Error Code EC Malfunction decision Define the evaporator coil temp.T2 of the compressor just starts conditions running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 <Tcool-2℃ does not keep continuous 4 seconds and this situation happens 3 times, the display area will…
-
11.2.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5)
Error Code E4/E5/F1/F2/F3 Malfunction decision If the sampling voltage is lower than 0.06V or higher than 4.94V, conditions the LED will display the failure. Supposed causes ● Wiring mistake ● Sensor faulty Trouble shooting: Check the connection between temperature sensor and PCB. No Correct the…
-
11.2.6 Overload current protection diagnosis and solution(F0)
Error Code F0 Malfunction decision An abnormal current rise is detected by checking the specified conditions current detection circuit. Supposed causes ● Power supply problems. ● System blockage ● PCB faulty ● Wiring mistake ● Compressor malfunction Trouble shooting: 56 Service manual
-
11.2.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0)
Error Code P0 Malfunction decision When the voltage signal that IPM send to compressor drive chip conditions is abnormal, the display LED will show “P0” and AC will turn off. Supposed causes ● Wiring mistake ● IPM malfunction ● Outdoor fan ass’y faulty ● Compressor malfunction ● Outdoor PCB faulty…
-
11.2.8 Over voltage or too low voltage protection diagnosis and solution(P1)
Error Code P1 Malfunction decision An abnormal voltage rise or drop is detected by checking the conditions specified voltage detection circuit. Supposed causes ● Power supply problems. ● System leakage or block ● PCB faulty Trouble shooting: 58 Service manual
-
11.2.9 High temperature protection of compressor top diagnosis and solution(P2)
Error Code P2 Malfunction decision If the sampling voltage is not 5V, the LED will display the failure. conditions Supposed causes ● Power supply problems. ● System leakage or block ● PCB faulty Trouble shooting: Check the air flow system of indoor and outdoor units Yes Clear up the air inlet and…
-
11.2.10 Inverter compressor drive error diagnosis and solution(P4)
Error Code P4 Malfunction decision An abnormal inverter compressor drive is detected by a special conditions detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on. Supposed causes ● Wiring mistake ● IPM malfunction ●…
-
Main parts check
1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature Sensors. Room temp.(T1) sensor, Indoor coil temp.(T2) sensor, Outdoor coil temp.(T3) sensor, Outdoor ambient temp.(T4) sensor, Compressor discharge temp.(T5) sensor.…
-
Appendix 2 Temperature Sensor Resistance Value Table for T5 (°C --K)
-
2. Compressor checking
Measure the resistance value of each winding by using the tester. Position Blue - Red Blue - Black Red - Blue 64 Resistance Value ASN98D22UFZ ASM135D23UFZ ATF235D22UMT 1.57Ω 1.75Ω 0.75Ω (20℃/68℉) (20℃/68℉) (20℃/68℉) Service manual