Инструкция на Чиллеры с водяным конденсатором серии WHS
Чиллеры с водяным конденсатором серии WHS 095.1-539.4. Справочное руководство (English).
Смотрите также: Справочное руководство →
Загружаем документ…
Текст инструкции
-
Product Manual
804 B – 04/11 I Data: November 2004 Supersedes: 804B- 03/05 H :DWHUFRROHGVFUHZFKLOOHUV :+6· &RROLQJFDSDFLW\IURPWRN: +]±5HIULJHUDQW+)&D McQuay is participating in the Eurovent Certification Programme. Product are as listed in the Eurovent Directory of Certified Products and on the web site…
-
New water cooled screw chillers McQuay WHS
McQuay International introduces their newest water cooled screw chillers equipped with new single screw compressors. McQuay water cooled WHS chillers equipped with 1, 2, 3 and 4 McQuay screw compressors are a new range of the unit using the StarGateTM Frame 4 single screw compressors. They are…
-
same time, thus cancelling the radial loads. Also, both ends of the screw rotor are subjected to suction pressure only, which cancels the axial loads and eliminates the huge thrust loads inherent in twin-screw compressors. Oil injection is used for these compressors in order to get high COP at high…
-
Water content in cooling circuits
The cooled water distribution circuits should have a minimum water content to avoid excessive compressors start and stop. In fact, each time the compressor starts up, an excessive quantity of oil goes from the compressor’s sump and simultaneously there is a rise in the temperature of the compressor…
-
Oil differential pressure switch
Compressor thermal High Discharge Temperature on the compressor Phase Monitor Star / Delta Transition Failed Low Delta Pressure between Suction and Discharge System security A serious alarm input (stops the unit) A flow controller input (stops the unit) A pump thermal input (stops the unit) Remote…
-
MicroPlant allows
• Visualization and modification of all the parameters for each controller • Protection of the main parameters against incidental modifications (different levels of passwords) • Memorization of the detected values and visualization of their graphics • Display, print-out and chronological…
-
Flow switch - Supplied separately to be wired and installed on the evaporator water piping (by the customer). Suction line shut off valve – Suction shut-off valve installed on the suction port of the compressor to facilitate maintenance operation. Cu-Ni 90-10 condenser – To work with sea water the…
-
Table 2 – Evaporator fouling factors
Fouling factors m2°C / kW Cooling capacity correction factor Power input corretion factor COP correction factor 0,0176 0,0440 0,0880 0,1320 1,000 0,978 0,957 0,938 1,000 0,986 0,974 0,962 1,000 0,992 0,983 0,975 Table 3 – Condenser fouling factors Fouling factors m2°C / kW Cooling capacity…
-
Physical data WHS HFC 134a
“WHS” Unit size 095.1 114.1 132.1 146.1 Cooling capacity (1) kW Power input (1) kW McQuay StargateTM Screw compressor No. Refrigerant circuits No. Refrigerant charge HFC 134a kg Oil charge l Min % of capacity reduction % Evaporator Evaporators / water volume No./l 1/140 1/135 1/128 1/152 Max…
-
Physical data WHS HFC 134a
“WHS” Unit size 379.3 397.3 434.4 Cooling capacity (1) kW 1331 1394 1525 Power input (1) kW McQuay StargateTM Screw compressor No. Refrigerant circuits No. Refrigerant charge HFC 134a kg Oil charge l Min % of capacity reduction % 8,3 8,3 6,25 Evaporator Evaporators / water volume No./l 1/415 1/415…
-
Sound pressure level WHS
WHS Unit size 63 Hz 095.1 114.1 132.1 146.1 191.2 210.2 226.2 248.2 266.2 306.3 325.3 343.3 361.3 379.3 397.3 434.4 464.4 502.4 539.4 53,6 54,6 56,6 56,6 56,2 56,6 57,1 58,2 59,1 57,5 57,8 58,2 58,9 59,6 60,2 58,6 59,1 60,2 61,1 -5 Sound pressure level at 1 m from the in free field ( rif. 2 x 10 )…
-
Sound pressure level correction factor for different distances
WHS Unit size Distance (m) 095.1 114.1 132.1 146.1 191.2 210.2 226.2 248.2 266.2 306.3 325.3 343.3 361.3 379.3 397.3 434.4 464.4 502.4 539.4 8,7 8,7 8,7 8,7 8,4 8,3 8,3 8,3 8,3 7,9 7,9 7,9 7,9 7,9 7,9 7,8 7,8 7,8 7,8 13,7 13,7 13,7 13,7 13,4 13,3 13,3 13,3 13,3 12,7 12,7 12,7 12,7 12,7 12,7 12,5…
-
size
WHS 095.1 WHS 114.1 WHS 132.1 WHS 146.1 WHS 191.2 WHS 210.2 WHS 226.2 Evaporator leaving water temp. (°C) Standard ratings WHS 095.1 ÷ 226.2 ENTERING CONDENSER WATER TEMPERATURE °C Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power cap. input cap. input…
-
size
WHS 248.2 WHS 266.2 WHS 306.3 WHS 325.3 WHS 343.3 WHS 361.3 Evaporator leaving water temp. (°C) Standard ratings WHS 248.2 ÷ 361.3 ENTERING CONDENSER WATER TEMPERATURE °C Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power cap. input cap. input cap. input…
-
size
WHS 379.3 WHS 397.3 WHS 434.4 WHS 464.4 WHS 502.4 WHS 539.4 Evaporator leaving water temp. (°C) Standard ratings WHS 379.3 ÷ 539.4 ENTERING CONDENSER WATER TEMPERATURE °C Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power Cool. Power cap. input cap. input cap. input…
-
Evaporator pressure drop
(WHS 095.1 – 539.4) 325.3 - 343.3 - 361.3 - 379.3 - 397.3 266.2 306.3 248.2 210.2 226.2 191.2 132.1 539.4 146.1 502.4 114.1 464.4 095.1 434.4 Water pressure drop (kPa) Water flow rate (l/s) 804 B – 04/11 I – pag. 17/28
-
Condenser (1 pass) – heat recov. cond. (1 pass) pressure drop
804 B – 04/11 I – pag. 18/28
-
Condenser (2 passes – ∆T 4÷8 °C) pressure drop
Condenser (2 passes – ∆T 8÷15 °C) pressure drop Partial heat recovery ratings WHS 095.1 ÷ 539.4 804 B – 04/11 I – pag. 19/28
-
WHS 114.1 WHS 132.1 WHS 146.1 WHS 191.2 WHS 210.2 WHS 226.2 WHS 248.2 WHS 266.2 WHS 306.3 WHS 325.3 WHS 343.3 WHS 361.3 WHS 379.3 WHS 397.3 WHS 434.4 WHS 464.4 WHS 502.4 WHS 539.4 Leaving desuperheaters water temperature °C WHS Unit Heating capacity (kW) Heating capacity (kW) Heating capacity (kW)…
-
size
Leaving chilled water temp. °C Total heat recovery ratings WHS 095.1 ÷ 306.3 WHS 095.1 WHS 114.1 WHS 132.1 WHS 146.1 WHS 191.2 WHS 210.2 WHS 226.2 WHS 248.2 WHS 266.2 WHS 306.3 LEAVING HEAT RECOVERY CONDENSER WATER TEMPERATURE - °C Cool. cap. (kW) Pow. input (kW) Heat. cap. (kW) Cool. cap. (kW) Pow.…
-
size
WHS 325.3 WHS 343.3 WHS 361.3 WHS 379.3 WHS 397.3 WHS 434.4 WHS 464.4 WHS 502.4 WHS 539.4 Leaving chilled water temp. °C Total heat recovery ratings WHS 325.3 ÷ 539.4 LEAVING HEAT RECOVERY CONDENSER WATER TEMPERATURE - °C 40 Cool. cap. (kW) 994 1026 1059 1092 1127 1161 1051 1085 1120 1155 1191 1227…
-
Dimensions WHS 095.1 ÷ 146.1
804 B – 04/11 I – pag. 23/28
-
Dimensions WHS 191.2 ÷ 266.2
804 B – 04/11 I – pag. 24/28
-
Dimensions WHS 306.3 ÷ 397.3
804 B – 04/11 I – pag. 25/28
-
Dimensions WHS 434.4 ÷ 539.4
804 B – 04/11 I – pag. 26/28
-
WHS Frame 4 - Technical specifications
To supply and install, where specified in the project n unit(s) water cooled chiller with cooling capacity of kW, to cool l/sec. of water from °C to , condenser entering water temperature ….°C, condenser leaving water temperature ….°C. The unit should work with electricity at V, 3ph, 50Hz. The…
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay partecipa al programma di Certificazione Eurovent. I prodotti interessati figurano nella Guida Eurovent dei Prodotti Certificati. McQuay is participating in the…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.