Инструкция на Чиллеры с водяным охлаждением конденсатора и винтовым компрессором серии PFS 'B'
Чиллеры с водяным охлаждением конденсатора и винтовым компрессором серии PFS 'B' 103.1-296.2. Инструкция по монтажу и эксплуатации.
Загружаем документ…
Текст инструкции
-
Product Manual 803 B – 04/11 D Data: November 2004 Supersedes: 803 B-02/09 C :DWHUFRROHGVFUHZFKLOOHUV 3)6³%´· &RROLQJFDSDFLW\IURPWRN: +]±5HIULJHUDQW+)&D McQuay is participating in the Eurovent Certification Programme. Product are as listed in the Eurovent Directory of Certified Products and on the…
-
New water cooled screw chillers McQuay PFS “B”
McQuay International introduces their newest water cooled screw chillers equipped with new single screw compressors. McQuay water cooled PFS chillers equipped with 1 or 2 McQuay screw compressors are a new range of the unit using the StarGateTM single screw compressors. They are manufactured by…
-
General characteristics
Ecological HCF 134a refrigerant McQuay has designed and optimized StargateTM compressors to operate with HFC 134a, ecological refrigerant with zero ODP (Ozone Depletion Potential) and very low GWP (Global Warming Potential) that means low value of the “direct effect” in the formula of TEWI (Total…
-
Servo Controlled modulating liquid level regulators
PFS are equipped with a modulating servo-controlled main expansion valve type controlled by a pilot float valve type to perfectly modulate refrigerant flow to the evaporator, proportionally to the required capacity. This ensures a stable regulation and economic operation, because pressure and…
-
Microtech II Plus controller
Microtech II Plus device is installed as standard on all the units; it can be used to alter unit set points and control commands. A display illustrates the machine's operating status and programable parameters (setpoints) e.g. temperatures and pressures of fluids (water, refrigerant). Device…
-
Microtech II Plus terminal
The Microtech II Plus terminal has following features: • 4-lines by 20-character liquid crystal display • Removable and remote key-pad • Key-pad consisting of 15 keys “ clear language display ” • Memory to protect the data • General faults alarm led • 4-level password access to modify the setting •…
-
Standard Accessories (furnished on basic unit)
Modulating condenser water flow valve – Factory mounted on condenser outlet water connection, in order to allow fast and safe unit starting. It is not supplied for condensers with water side pressures higher than 10 bar. Discharge line check valve – Ensures compressors maintainence operations…
-
Installation notes
Warning Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and who are experienced with this type of equipment. Must be avoided the unit installation in places that could be considered dangerous for all the maintenance…
-
Table 1 – Operating limits
PFS 103.1÷296.2 Max evaporator leaving water temperature Min evaporator leaving water temperature (without glycol) Min evaporator leaving water temperature (with glycol) Max condenser leaving water temperature HFC 134a °C °C °C °C 15 3 -8 50 Table 2 – Evaporator fouling factors Fouling factors m2°C…
-
Nomenclature
-
Physical data PFS “B”
PFS Unit size Cooling capacity (1) Power input (1) COP (1) McQuay Screw compressors Refrigerant circuits Min % of capacity reduction Refrigerant charge HFC 134a Oil charge Evaporator Evaporators / water volume Max water operating pressure Condenser Condensers / water volume Max water operating…
-
Sound pressure level PFS “B”
PFS Unit size 63 Hz 103.1 124.1 147.1 208.2 229.2 249.2 272.2 296.2 63,5 64,5 65,5 66,5 67,0 67,5 68,0 68,5 Sound pressure level at 1 m from the unit in free field ( rif. 2 x 10-5 ) 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz 70,5 71,5 72,5 73,5 74,0 74,5 75,0 75,5 80,0 81,0 82,0 83,0 83,5…
-
PFS
Unit size 103.1 124.1 147.1 208.2 229.2 249.2 272.2 296.2 Leaving chilled water temperature °C Standard ratings PFS “B” 103.1 ÷ 296.2 ENTERING CONDENSER WATER TEMPERATURE - °C Cool. Pow. cap. input (kW) (kW) COP Cool. Pow. cap. input (kW) (kW) COP Cool. Pow. cap. input (kW) (kW) COP Cool. Pow. cap.…
-
PFS “B” - 2 passes evaporator water pressure drop
Pressure drop (kPa) Water flow rate (l/s) 803 B – 04/11 D – pag. 14/24
-
PFS “B” - 3 passes evaporator water pressure drop
Pressure drop (kPa) Water flow rate (l/s) 803 B – 04/11 D – pag. 15/24
-
PFS “B” - 2 passes condenser water pressure drop
Pressure drop (kPa) Water flow rate (l/s) 803 B – 04/11 D – pag. 16/24
-
PFS “B” - 3 passes condenser water pressure drop
Pressure drop (kPa) Water flow rate (l/s) 803 B – 04/11 D – pag. 17/24
-
PFS “B” - 4 passes condenser water pressure drop
Pressure drop (kPa) Water flow rate (l/s) 803 B – 04/11 D – pag. 18/24
-
Dimensions PFS “B” 103.1
-
Dimensions PFS “B” 208.2-229.2
-
Dimensions PFS “B” 272.2-296.2
803 B – 04/11 D – pag. 21/24
-
PFS “B” Frame 4 - Technical specifications
To supply and install, where specified in the project n unit(s) water cooled chiller with cooling capacity of kW, to cool l/sec. of water from °C to , condenser entering water temperature ….°C, condenser leaving water temperature ….°C. The unit should work with electricity at V, 3ph, 50Hz. The…
-
We reserve the right to make changes in design and construction at any time without notice, thus the cover picture is not binding. McQuay partecipa al programma di Certificazione Eurovent. I prodotti interessati figurano nella Guida Eurovent dei Prodotti Certificati. McQuay is participating in the…
Схемы, таблицы и рисунки — в просмотре документа выше. Клик по номеру страницы открывает её в просмотре.