Design & Installation Guide For McQuay MDS Multi System
-
c 2004 McQuay International. All Rights Reserved
is a registered trademark of McQuay in the United States and other countries, licensed and recognized all over the world. Without prior written consent of McQuay, use of the above-named trademark for business purposes may constitute a violation of the federal and state laws in the Unites states and…
-
Overview 1.1 General Information The MDS(Multi Digital Scroll) air conditioning system is operated by a digital compressor and is accommodated by multiple evaporators (indoor units). It is touted as the next-generation modular system in the world of high-efficiency air conditioning. lt has…
-
Discharge pressure
Solenoid valve Modulation chamber Discharge pressure Solenoid valve Modulation chamber Bleed hole Loading Suction pressure Bleed hole Unloading PWM valve power off PWM valve power on Valve close Valve open Suction pressure Fixed scroll move downwards Fixed scroll moves upwards Two scrolls gather…
-
1.2.3 Diagram of the Unit System
MDS030A MDS040A MDS050A MDS060A Filter Indoor unit 1 Outdoor heat exchanger HPS Outdoor Filter LPS Electronic expansion valve Digital compressor PWM Liquid receiver Filter Indoor unit n Accumulator indoor Filter Dry filter Electronic expansion valve Note: The MDS030A unit excludes the reservoir.…
-
MDS080BR
MDS100BR MDS120BR Ball valve Four-way valve Filter Pressure tapping point Oil separator Low pressure sensor High pressure switch Pressure tapping point Heat exchanger Check valve Accumulator Check valve Standard compressor Digital compressor Ball valve Filter Electronic expansion valve Electronic…
-
MDS180BR
Check valve Filter Filter High pressure sensor High pressure switch Ball valve Pressure tapping point Low pressure sensor Heat exchanger Pressure tapping point Oil separator Four-way valve Heat exchanger Four-way valve Ball valve Check valve Electronic expansion valve Accumulator Check valve…
-
MDS260BR
Master unit Filter Ball valve Four-way valve Pressure tapping point Check valve Low pressure sensor Oil separator High pressure sensor High pressure switch Heat exchanger Pressure tapping point Check valve Accumulator Ball valve Standard compressor Digital compressor Filter Electronic expansion…
-
1.3 Main Features
1.3.1 Wide Range and Stepless Capacity Modulation Wide capacity modulation range 10%-100%) According to changing the ratio of loading time and unloading time, MDS can modulate Running ratio of compressors(%) the capacity steplessly Lower the energy consumption and running cost. 100% MDS system…
-
1.3.4 Energy Saving
The inverter system capacity modulation range is from 30% to 100%, while MDS system capacity modulation range is from 10% to 100%; Quick response to the capacity modulation; Min. power consumption is only 10% of the full load power consumption; Compared to the inverter system, there is no power…
-
1.3.7 Space Saving
Compared to traditional central air conditioning, MDS system is higher centralized, no need for special equipment room to save more space, and bring more benefits. Traditional central air conditioning MDS system 1.3.8 Easy to Install and Simple to Maintain Easy installation MDS system is simple, and…
-
Indoor unit: ceiling concealed unit
M CC 050 T -R (B)/(D)- A M A McQuay Ceiling concealed indoor unit Cooling capacity No. Design serial No. Design alternation No. Type of connecting pipe: R-right connecting pipe L-left connecting pipe Matching outdoor units: Air return mode: B-rear air return plenum D-lower air return plenum…
-
Indoor unit: Wall Mounted Indoor Units
M WM 015 T - A M A Design alternation No. Matching outdoor units: MDS series Power supply features: A:220V /50Hz Design serial No. Cooling capacity No. Indoor unit: Wall Mounted Indoor Units McQuay Outdoor unit: MDS unit MDS 060 A R - F AA Description of the unit Power supply: A:220V /50Hz B:380V/3N…
-
1.5.2 Indoor Products
Model 0.8HP 1.0HP 1.5HP 1.8HP Capacity range 2.0HP 2.5HP 3.0HP 4.0HP 5.0HP 6.0HP MCC MCK MCM MDB MWM 1.6 Performance Parameter 1.6.1 Ceiling Concealed Model Indoor unit MCC 008T MCC 010T MCC 015T MCC 018T MCC 020T MCC 025T MCC 030T MCC 040T MCC 050T MCC 060T Cooling capacity W 2000 2500 3650 4500…
-
1.6.3 Ceiling Cassette
MCK018T MCK020T MCK025T MCK030T Nominal cooling capacity Model Indoor unit MCK010T MCK015T W 2800 3600 4500 5400 6500 7500 10000 12500 Nominal heating capacity W 3200 3900 5000 5900 7200 8000 11000 13500 Nominal input W Power supply Air flow 220V /50Hz High m3/h 1200 1300 1360 1650 Medium m3/h 1100…
-
1.6.6 MDS-A Specification(Outdoor Unit)
Model Unit Nominal cooling capacity kW MDS030A MDS030AR MDS040A 8.5 8.5 10 MDS040AR MDS050A 10 12.5 12.5 14.5 14.5 Nominal heating capacity kW - 9.0 - 11.5 - 13.5 - 16.5 Dimension (L x W x H) mm 840x408x900 Weight kg 82 Cooling rated power input kW 3.0 3.0 Cooling rated current A 13.6 13.6 Heating…
-
1.6.7 MDS-B Specification (Outdoor Unit)
MDS Model MDS MDS MDS MDS MDS MDS MDS MDS MDS MDS Nominal cooling capacity kW 24.5 24.5 28.0 28.0 32.5 32.5 40.0 40.0 47.5 47.5 50.0 50.0 Nominal heating capacity kW - 26.0 - 30.0 - 34.0 - 43.0 - 50.0 - 53.0 380V/3N /50Hz Power supply Sound level dB(A) Dimension (Lx W x H) mm 1290x840x1840…
-
1.7 Operating Range
-
Type: MDS-Y5
-
1.9.2 MDB050T
-
1.9.4 MCC008
-
1.9.6 Auxiliary Heating Coil
-
1.10 Outline of Outdoor Units
-
MDS120B(R)
-
2 Unit Control
2.1 Introduction to the Controller MDS system is controlled by the micro-computer. Several types of controller are available, including wireless controller, wire controller, wire controller + remote controller and central controller. One wireless controller can control one unit, one wire controller…
-
2.3 Operation of the Controller
2.3.1 Main Features Both wired controller (using the key on board) and remote controller (equipped with infrared receiver to receive the order from the remote controller ) to control the unit, and to perform such functions as parameter setting, working mode setting, status display and malfunction…
-
Temp unit setting
There is a switch on the PCB board. When switch OP1 is ON, the unit is ; when it is OFF, the unit is oF.Alternate method is as follows: Press fan key and last for 5 seconds in the normal condition, the temp unit setting will be successful and there will be a buzzer to indicate. Real time setting…
-
Timer setting
Press Timer to enter timer setting (When the unit is ON, it can only be set to OFF; When the unit isOFF , it can only be set to ON) and last timer will be shown on the LCD. If there is no press on any key within 5 seconds, it will exit and cancel the timer setting at to increase the hour while the…
-
2.3.3 Wire Control Panel
Fan ON/OFF Fan ON/OFF Fan ON/OFF Fan ON/OFF Fan ON/OFF Temp. Temp. Temp. Temp. Temp. Fan speed Sleep Timer Sleep Mode Timer For three-speed unit with wind wing Mode Timer Sleep Heat Sleep Heat Sleep Mode Timer Mode Timer Mode For the cooling and heat pump unit with For the cooling and heat pump unit…
-
2.4 Software Management System
2.4.1 Real-time Monitor Software System monitoring software: The real-time MDS unit monitoring software features powerful functions, including indoor monitoring, system monitoring, loop monitoring and service monitoring. With it, the user or service debugging personnel can view detailed unit…
-
Loop monitoring*
Select and view the outdoor unit s system Service monitoring* Display the current operation parameters figure, operation parameters and the operation parameters of all indoor units. and history record curve of indoor/outdoor unit in the system. Note: Only the authorized maintenance personnel can…
-
2.5 Network Central Control
One outdoor unit can be connected with maximum 48 indoor units.Control over up to 32 outdoor units can be realized by a centralized controller, and the monitoring software monitors up to 1536 (32x48) units simultaneously in real time.The cabling of outdoor and indoor units is simple.The MDS system…
-
2.6 Wiring Diagram
2.6.1 Wiring Diagram of Indoor Units Model MCC008/010/015/018/020/025/030/040/050/060T SW-PB KEY1 JP7 J1 J5 J4 HF MF LF J3 LINE J2 EXV CON3 MOTOR B CON5 A J6 SW2 DIP 5 ON 4 CON2 low middle high 3 DIP red blue N L TR1 N TR2 CON6 yellow/green white white M ~ white white Fan motor 1 M ~ yellow/green…
-
Model MCK025/030/040/050T
SW-PB KEY1 JP7 J1 J5 J4 HF MF LF J3 LINE J2 MOTOR B CON5 A J6 EXV CON3 CON2 L ON 1 blue N N N SW3 ON 2 3 SW1 DIP 4 SW2 DIP 5 ON DIP CON9 ROOM 8 1 CON4 red JP5 JP3 JP4 1 Connecting indoor/ outdoor units communication NEUTRAL JP2 JP1 JP6 OUTID2 WATER CON6 TR1 TR2 red blue black yellow/green M ~ Swing…
-
Model MCM050T
SW-PB KEY1 JP7 J1 J5 J4 HF MF LF J3 LINE J2 blue N L N LF MF HF SW3 ON 2 3 SW1 DIP SW2 4 ON 6 CON2 DIP 5 ON blue red yellow/green Fan motor 1 black M ~ M ~ Fan motor 2 Fan motor 3 Indicator (220V~/50Hz) Notes: 1.Set jumper JP:For JP1,upper two are set to OFF,the lower two to ON,and other JPs are set…
-
2.6.2 Wiring Diagram of Outdoor Units
Model MDS030A 220V~/50Hz N FU 2 PWMV KM 5 4WV 1L1 3L2 5L3 8 10 LOW-FAN FIXED COMP 7 DIG COMP PWMV 3 HI-FAN EXV MID-FAN N L KM LIVE 2T1 4T2 6T3 RY1 RY2 RY3 RY4 RY5 RY6 RY7 NEUTRAL N blue brown red orange red J2 NEUTRAL TRAN-H C2 McQuay OV-COMP2 TRAN-L M ~ OV-COMP1 14 J1 black Compressor Fan 1 JP1 GND…
-
Model MDS040A
220V~/50Hz N 2 PWMV KM 5 4WV 1L1 3L2 5L3 8 10 LOW-FAN FIXED COMP 7 DIG COMP PWMV 3 HI-FAN FU MID-FAN N L KM LIVE 2T1 4T2 6T3 RY1 RY2 RY4 RY3 RY5 RY6 RY7 NEUTRAL J2 brown yellow blue orange brown yellow blue orange N NEUTRAL blue blue TRAN-H OV-COMP2 red OV-COMP1 J1 Fan 2 JP1 LP 11 LP HP 12 HP JP2…
-
Model MDS050A
220V~/50Hz N 2 PWMV KM 5 DIG COMP 1L1 3L2 5L3 8 10 LOW-FAN 7 FIXED COMP 4WV PWMV 3 HI-FAN FU MID-FAN N L KM LIVE 2T1 4T2 6T3 RY1 OV-COMP1 J1 LP 11 LP HP 12 HP Fan 2 JP2 AI-IN MidLet GND DLT A B InLet JP1 Connecting indoor unit communication Description of components and parts: Coil middle…
-
V1+
-
LPT
-
N
-
OL3 11
-
RED
-
HPT
-
2.7 Electric Connection
2.7.1 MDS030A/AR MDS040A/AR MDS050A/AR Indoor unit 1 Outdoor Indoor Indoor unit 2 Unit electric control box Unit electric control box Main board Main board Main power terminal support L N 220V/1~/50Hz 220V/1~/50Hz Unit electric control box Communication port Power supply Power supply 220V/1~/50Hz…
-
2.7.3 MDS080 240B/BR
Indoor e Bpc Apc Bin A Outdoor pli fie d fig ur 380V/3N~/50Hz Indoor unit 1 la m Unit electric control box Indoor unit 2 Te rm ina L1 L2 L3 N Main board Main board Communication port Communication port Shielded wire QF R S T N Communication port Bpc Apc Bin A in Main board Main power terminal…
-
2.8 Electric Data
2.8.1 Outdoor Unit MDS MDS030A/ Model MDS040A/ MDS050A/ MDS060A/ MDS050A/ MDS060A/ MDS030AR MDS040AR MDS050AR MDS060AR MDS050AR MDS060AR 380V /3N /50Hz Power supply 220V /50Hz 2 6(2.5) 4(2.5) Power Cross section area(mm ) cable Q.T.Y 2(1) 4(1) MDS080B/ MDS080BR Model MDS100B/ MDS100BR MDS120B/…
-
3 Selection
3.1 Load Calculation 3.1.1 Planning and Cooperation McQuay recommends you to estimate and plan the following before engineering. Based on the air conditioning area function, calculate cooling/heating load (depending on the temperature,humidity, and ventilation). Query related meteorologic…
-
calculate the heating load )] and outside volume V (m3), we can as follows: Qtotal = aqvV( tn tw) Where, a is the correction factor. For details, see the table. qv is the heat performance index of the building. It is the heating load when the difference between the indoor temperature and the outdoor…
-
3.2 Selection of Indoor Units
The selection of indoor unit should be based on the several factors, including customer s requirement, indoor air distribution, indoor decoration, etc. Ceiling concealed, ceiling cassette, high pressure duct unit and ceiling exposed are available now. The indoor unit should be selected to meet the…
-
3.3 Selection of Outdoor Units
For the allowed combinations, please refer to the "Total Capacity Indexes of a Combination of Indoor Units" table. The standard combination is the one with which the total indoor unit capacity is most proximate to but less than 100% of the capacity of the outdoor unit combination. 3.3.1 Capacity…
-
3.3.7 Actual Capacity Calculation
Based on the model and combination rate of the outdoor unit, select an appropriate door unit capacity table. Then find out the capacity of the outdoor unit (kW) and that of each indoor unit (kW) according to the related temperatures of the indoor and outdoor units.The formula is as follows: IUC=OUC…
-
3.3.10 Temperature-related Cooling Capacity Correction Factors
3.3.11 Temperature-related Heating Capacity Correction Factors 27 18 1.15 1.10 1.05 20 Corre ction facto r 1.00 0.90 0.70 0.95 22 0.80 0.65 24 0.60 -15 -10 -5 -57-
-
3.4 Design of Air System
The air cooled pipeline unit is an important and complex part of the air system. The air system must be designed in compliance with Design Code for Heating, Ventilation and Air Conditioning and Code of Design on Building Fire Protection. The air pipe diameter, processing, air outlet, muffling static…
-
The conflux of the return air inlet brings little affect on the air flow pattern in the room. So, its structure is simple. Some only have a metal mesh in the orifice, or a shutter or grille. The return air inlet location and shape depend on the air flow pattern. If it is installed in the lower area…
-
Select the loop with most resistance and that with minimum resistance, and then
calculate the frictional resistance and local resistance loss of each pipe segment. Check the unbalance ratio of the loop of most resistance to that of minimum resistance must be less than 15%. Otherwise, redesign the air pipe system, or satisfy the balance ratio requirements by adjusting with the…
-
Wall thickness of the air pipe
The wall thickness directly relates to the effect and life of the pipe.Too thin wall will cause unstable installation, and thus the pipe will heavily with noise increased. Even worse, the friction might compound the problem, shortening the service life of the air pipe or even the entire air…
-
Acceptable (CO2) density
Room type Acceptable CO2 density L/m3 g/kg Place where people stay for a long time 1 1.5 Place where children and patients stay 0.7 1.0 Place where people stay regularly (government agency) 1.25 1.75 Place where people stay for a short time 2 3.0 In actual practice, the fresh air volume is generally…
-
3.5 Slection of Refnet Joint
3.5.1 Copper Pipe Selection ( MDS100BR ) Diameter of the main pipe and that of the remotest pipe(equivalent length<90m) Main pipe: 12.7/ 28.6(the same as the outdoor unit The remotest pipe: the same as the indoor unit Refer to the refrigerant pipe to calculate the cooling capacity of downstream A…
-
The following tables show the refrigerant copper pipe dimension specifications
-
Refnet joint type selection
-
Type : MDS-C1
Unit: mm Type MDS-C2 MDS-C3 OD ͺ9.7 OD ͺ12.9 OD ͺ16.1 204 Four places of silver & copper brazed A B C D E OD ͺ19.3 250 550 Refnet joint type Refnet joint type ͺ(mm) A(outer diameter) B C D E MDS-C2 28.6 28.9 25.7 22.5 19.5 MDS-C3 25.4 25.7 22.5 19.3 16.1 Unit: mm 3.6 Selection of E-EXV Box To reduce…
-
4 Installation
4.1 Outdoor Unit Installation To choose location of installation To ensure good cooling and heating performance of the units, follow up the below to pick up right place to install units: To avoid discharged air returns to the air inlet, to avoid hot air discharged by other units; ensure enough space…
-
FRONT
FRONT BACK BACK Ľ600mm Ľ450mm FRONT BACK FRONT FRONT FRONT FRONT BACK BACK Ľ 900mm FRONT BACK Ľ450mm BACK Ľ900mm BACK ¡ 450mm Design & installation Guide For McQuay MDS Multi System Handling outdoor units Please refer to the followings to move units; To use 4 supporting points to move units instead…
-
Installation of the Combined Outdoor Units (Suitable for Model of MDS260/280/300)
Two outdoor units can be grouped as one outdoor unit, to connect with indoor units. The installation of combined units is more complicated than that of the single outdoor unit; please read the below notes carefully before installation, and strictly follow the installation instructions. Select the…
-
Balance pipe connection
Balance pipe must be installed. Balance pipe shall be connected through the hole of side panel or base panel or the position with the other outdoor unit. Balance pipe shall be installed horizontally and orderly, and shall be lower than the access valve for balance pipe. Protect the balance pipe…
-
Wall or ceiling shall be strong enough to support indoor units. Otherwise, it may cause the unit
falling off. Do not expose to sunshine. Do not install units to the place where steam or oil smoke exists. Do not install units to the place where burning gas leakage may happen. Do not install around the high frequency equipment (such as high frequency electric welding machine). Do not install…
-
Duct Working Installation
Air supply duct working installation Two types of air supply duct working: round and rectangle. Round air duct working can be connected up to the air supply inlet directly; while the rectangle one needs to be connected with a transition air duct to air supply inlet, and separate to the air diffuser.…
-
h. To adjust distance between the bottom panel and ceiling to 35.0mm
i. To check whether the installation is horizontal, and indoor units are fixed tightly without dropping off and vibration. Steeve nut indoor unit (drill hole in ceiling) 890.0mm washer 790.0 ceiling 35mm washer 620.4 (machine dimension) 820mm (drill hole in ceiling) 890.0mm nut (machine dimension)…
-
There are also the hole for fresh air and exhaust air for connection with outside in indoor unit, but as for air piping, and only be the other side of refrigerant piping connector. If the indoor unit is installed to the place with a barrier (such as a head lamp) or a small space, the connecting pipe…
-
Installation of MDB-T series indoor unit
To mount the MDS050~060T in ceiling. As the air outlet flange is close to the unit bottom, when the unit is mounted in ceiling, the pipe can be laid out easier, effectively reducing the requirement for room height. After the installation, only the air inlet/outlet is exposed, as shown below. duct…
-
Installation of MCM-T Series Indoor Unit
To Check the Accessories are Ready To install the indoor unit There are two types of installation. Make sure the hook can bear the unit weight in ceiling mounting; a slope for the drainage direction is a must both for ceiling/floor standing mounting; ensure there is enough space for maintenance…
-
2. To fix the suspending panel with screw bolt as shown as above right figure
3. To hang the unit to the suspending panel and fix screw bolts, after installation of refrigerant pipe and drainage pipe, install the return air grill and frame, as shown below left figure: return air grill indoor unit flare joint E-EXV box liquid pipe gas pipe Install the E-EXV box: All models of…
-
4.3 Refrigerant Piping Design and Installation
4.3.1 Refrigerant Piping Design ( Including Selection of Refnet Joint ) Capacity combination The indoor units & outdoor units should have a relationship as follows: indoor units' cap 50% 130% outdoor units' cap Note:We strongly recommend that the capacity modulation equals to 100%. Refrigerant…
-
Equivalent length
Equivalent length = actual pipe length + number of elbows X equivalent length of each elbow + number of oil traps X equivalent length of each oil trap. Item Diameter elbow(m) oil trap(m) 9.52 0.18 1.3 12.70 0.20 1.5 15.88 0.25 2.0 19.02 0.35 2.4 22.02 0.40 3.0 25.40 0.45 3.4 28.58 0.50 3.7…
-
Connection of refnet joint and distributor kit
Outdoor unit Refnet joint Indoor unit controller Only connected by the refnet joint Outdoor unit Distributor kit Indoor unit controller Only connected by the distributor kit Outdoor unit Refnet joint Distributor kit controller Connected by the refnet joint and the distributor kit -80-
-
Refrigerant Piping Installation
Refrigerant piping should use the appointed diameter pipe; Refnet joint must be installed horizontally or vertically. (Horizontal line) A viewer OR (Horizontal line) B viewer Distributor kit must be installed horizontally. Liquid distributor kit Gas distributor kit To the indoor unit To the indoor…
-
The EXV must be installed vertically
EXV The throttle is installed vertically To indoor unit To outdoor unit 4.3.2 Refrigerant Piping Assembly Process Sequence install the indoor unit welding blow cut the piping required air leakage test install the pipe nitrogen charging dry Three principle of the refrigerant piping assembly…
-
Air
leakage Moisture Dust 4.3.3 Exchange Way of Nitrogen Gas (When Welding Copper Tube) Suppose no nitrogen gas is injected into refrigerant pipe when welding, the oxide air bubble will come into being in the internal surface of tube. This will result in some damage to the system. In order to avoid…
-
4.3.4 Transportation and Conservation of Copper Tube
When transport the connecting pipe, please be careful to keep it in shape. Copper cap should be used to prevent the dirt and water from entering it. When store it, the side of the connecting pipe should be sealed as follows: Copper pipe welding welding area Open inlet PVC belt Nip it to flat Return…
-
Steps
Put the pressure adjustor on the nitrogen bottle Connect the pressure adjustor with the liquid pipe of the outdoor unit Seal any other connecting port, Open the valve of the nitrogen and adjust it which the pressure is 5kg/cm2. Check to see if the nitrogen go through the liquid pipe of point A. Air…
-
4.3.7 Process Sequence of Air Leakage Test
No Pressure charging refrigerant piping assembly finished is the pressure released? Pass yes check and maintain it Main points of testing Please test as follows: The Pressure charging must be tested both in liquid pipe and gas pipe. First step, keep 3.0kg/cm2 pressure gas for more than 3…
-
4.3.8 Air Leak Gap Checking
Test 1 (when the pressure reduces) Hearing use your ear to find it out. Touching use your hand to find it out. Soap water use soap water to find it out. Test 2 (when step 1 can not find out , then the following should be adopted) Reduce nitrogen pressure to 3.0kg/cm2; Charge the nitrogen with R22 to…
-
Only the gas pip e is heatinsulated
Gas pipe Liquid pipe Heat preservation Heat preservation Liquid pipe Control cable Control cable Surface binding Heat preservation The gas and liquid pipe are heatinsulated Surface binding Moisture preservation support Heat preservation Liquid pipe Gas pipe Surface binding Control cable The…
-
A Valve handle
E F (Before pipe connection, vacuum pumping and additional refrigerant filling for delivery, make sure this valve is closed completely. After the above operations, please fully open it.) G B Stop pin (prevent the valve handle from turning over 90 degrees) C Sealing plate (annex) D Connection pipe…
-
4.3.11 Refrigerant charging
Calculate the refrigerant amount according to the length of the liquid pipe Add additional refrigerant The refrigerant amount of fill of the outdoor unit before delivery (excluding the refrigerant to be filled in the site pipe) The additional amount of the refrigerant depends on the liquid pipe…
-
-560 200 -700 60 -710 50 -720 40 30 -730 Necessary vacuum -740 20 Absolute pressure (mmHg) 0 -60 -160 -260 -360 -460 2 Surface pressure (kg/cm ) Design & installation Guide For McQuay MDS Multi System 10 Outdoor temperature range 5 -755 Frozen point -760 -20 -10 0mmHg Selection of vacuum pump When…
-
Type of vacuum pump and the vacuity
Application Type Max. exhaust volume Vacuum drying Air discharge Suitable Suitable Unsuitable Suitable Unsuitable Suitable 0.02mmHg Vacuum pump with lubricant 100L/min 10mmHg Vacuum pump without lubricant 40L/min 0.02mmHg 50L/min Sequence of vacuum drying According to the different ambient, vacuum…
-
Special vacuum drying
This vacuum drying way is used when there are some moisture in the copper pipe. Operating sequence: Vacuum drying: pumping the system for 2 hours; Nitrogen charging: Charge the nitrogen to the pressure of 0.5kg/cm2; As Nitrogen is a dried gas, so it can dry the system; but if the moisture is too…
-
4.4 Design, Processing and Installation of Condensated Drain Pipe
4.4.1 Design of Condensated Piping Size selection of main pipe and vertical pipe of condensated water Choose the pipe size according to the condensated water flow from the main pipe of indoor unit and the following table; Suppose the condensated water flow of 1 HP is 2L/h, then the condensated water…
-
4.4.2 Making and Mounting Condensate Pipes
Procedure: Install the indoor units check for water leakage connect the condensate pipe insulate the pipe from heat 4.4.3 Slope and Supporter of Condensate Pipe The slope condensate pipe should be more than 1/100 The length of condensate pipe should be as short as possible to discharge the…
-
4.4.5 The Main Drainage Pipe of Multiple Indoor Units
The pipe should be mounted from the upstream, and the diameter of the downstream connecting pipe should be as long as possible. The pipe should be as short as possible and the number of the indoor units must be as small as possible. Condensate pipe group of multiple units 2HP 25 1/ or more 2HP 4HP…
-
4.4.8 Installation of the Drainage Lift Pipe
Use the gradienter to check if the indoor If the drainage pipe needs to be lifted up, it unit is parallel to the ceiling, should be less than 300mm. If it is more than 500mm, maybe it will result in the refrigerant leakage. After 300mm 200mm Connecting pipe Spring hose After 500mm 1ċ1.5m Air vent…
-
5 Testing
5.1 Hardware Diagram and Configuration 5.1.1 MDS Series Indoor Units 3-speed fan Power supply Electronic expansion valve Temperature measurement Communication port 1 indicator Communication port 2 Electric heater Swing Memory 3 The indoor unit consists of a three-speed fan and an electronic…
-
Model 2 setting
SW3.5 SW3.8 Model 2 SW3.5 SW3.6 SW3.7 SW3.8 MCC MCK MCM MWM MDB MDBX Reserve Power setting SW3.1 SW3.4 Power SW3.1 SW3.2 SW3.3 SW3.4 0.8HP 1.0HP 1.5HP 1.8HP 2.0HP 2.5HP 3.0HP 4.0HP 5.0HP 6.0HP 7.0HP 8.0HP 9.0HP 10.0HP 11.0HP 12.0HP 5.1.2 MDS-A Series Outdoor Units Solenoid valve Four-way Digital…
-
Description of controller hardware
Input port: The system contains 5 test ports designed for high/low pressure test, digital compressor overload, constant speed compressor overload 1 and constant speed compressor overload 2 (used when 3 compressors are available) Output port: The system contains 9 output control ports including PWM…
-
D1 D5 indicate the local address during intercommunication: J2.1 J2.2 J2.3 J2.4 J2.5 Address J2.1 J2.2 J2.3 J2.4 J2.5 Address J2.6, ON: cooling only OFF: heat pump J2.7, J2.8 reserved JP1 and JP2 are used to set matched resistance for communication terminals. The last switch on the manifold must be…
-
DIP switch setting
Note: 1: 1: ON, 0: OFF S1 (1~2) MDS A Cooling only 0 MDS B Heat pump S1 3~8 indicate the number of connected indoor units Qty Qty S2 (1) S2 (2 3) 0 Slave module 1 Master module Initial opening extent of the valve -103-
-
S2 (4~8) addresses of the outdoor unit
-
5.2 Trial Run
Precautions Power up the system 12 hours while you run it for the first time so that the shaft can be preheated in advance; After the main power supply is switched off, please don start the second trial run until the system is powered for 2.5 hours; If the heater is not heated, to protect the…
-
6 Servicing and Maintenance
6.1 User Guide 6.1.1 Responsibilities and Obligations This product is covered under MacQuay warranty during the warranty period. Only MacQuay technicians or experienced professionals designated by MacQuay are allowed to install, test, repair and maintain this product series. 6.1.2 Unpacking…
-
6.2 Servicing and Maintenance
Caution: Do not use or place inflammable and explosive articles beside the air-conditioning unit; Power the indoor units in a centralized way; Please check the parts like installing support often to see if they are damaged after longtime service; Do not alter or repair the product without…
-
Fan motor
This component requires only a little care. As the motor is lubricated and sealed before the equipment leaves factory, no more lubrication is needed. After the unit remains in service for six months, be sure to check the fan motor is entirely insulated from the ground. Heat exchanger Clean the dust…
-
Part
Procedure Recommended interval Air filter (indoor unit) 1. Open the air input grid and take out the air filter and air refresher; 2. Disassemble the air filter and the air refresher; 3. Clear the dust away from the air filter using a cleaner or water below 40 containing neutral detergent. Never wash…
-
the heat exchanger. If the unit is operating in an oily, salty, wet or dirty environment, do clean
it with special-purpose detergent. It is not advised to wash it with water. Please use specialpurpose detergent to clean a dusty heat exchanger (for example, SF-98 or YD-402). Please note the following while using the unit: While the unit is running, please do not point any pole or any other hard…
-
7 Fault Codes and Troubleshooting
Fault codes here refer to the codes that appear on the remote control. If a host computer is available, the fault cause is directly displayed. 7.1 Fault Codes for MDS-A/B Series No. Fault code Description No. Fault code Description 1 E0 System malfunction 34 H5 Sensor broken, high pressure 2 E1…
-
7.2 Indoor Unit Malfunction Code
F1 Sensor broken (indoor inlet coil) F2 Sensor broken (indoor mid coil) F3 Sensor broken (indoor outlet coil) F4 Sensor broken (indoor return air ) F5 Sensor broken (indoor supply air) F6 Indoor and controller communication malfunction FA Controller storage malfunction FB Water pump(indoor drain…
-
Annexes
Annex 1(1) Parameters designed for various kinds of buildings Cooling load (w/m2) Building Office School Occupants Lighting Air flow Max. noise Sensible cooling load Total cooling load m2/person W/m2 L/S dB(A) Middle Far side Individual office Meeting room Classroom 130 190 2.5 Library Cafeteria 150…
-
Annex 1 (2) Heat load indexes designed for air-conditioning in some of the Chinese buildings
No. Building type and room name Heat load index W/m2 No. Building type and room name 1 2 Heat load index W/m2 Office building,school 58-80 6 Store 64-87 Residential building 46-70 7 Single-floor residential building 85-105 3 Hospital, kindergarten 64-80 8 Dining room 116-140 4 Hotel 58-70 9 Cinema…
-
Annex 6 Confirmation Form
1. Use the Confirmation table to add more secondary refrigerant Calculate the additional amount of secondary refrigerant required according to the diameter and length of the copper pipes. The table below lists the formula used to calculate the additional amount of secondary refrigerant needed for…
-